POINT SETUP SUB-MENU
Parameter
Factory
User
Tag
TAG-(factory ID)
Switch Control Mode
Deadband
Deadband
5°F (3°C)
Prop Band
*n/a (4°F (2°C))
Cycle time
*n/a (10 min)
Switch Rating
*n/a (30.0 A)
Circuit Breaker
*n/a (30.0 A)
Outlet Limit Mode
Disable
Max. Power
*n/a (7200 W)
Max. Current
*n/a (30.0 A)
3 Ph Pwr Calc
No
TS Fail Mode
Off
TS CTL Mode
TS1-Fail Off
TS 1 Hi Limit
*n/a Disable
TS 2 Hi Limit
*n/a Disable
Volt Turns Ratio
1.00 to 1
Current Turns Ratio
1.00 to 1
Auto-cycle
Enable
Auto-cycle Interval
8
Auto-cycle Units
Hours
Override Source
Remote
Load Shedding
*n/a
Limiter Cutout Temp.
*n/a (50.0°C)
Limiter Current Sense *n/a (Disable)
MISC. SETUP SUB-MENU
Parameter
Factory
User
Temp. Units
°C
n/a
Version
V1.0X.XX
Limiter version
*n/a (V1.0X.XX)
Ext. Input
Not used
Flash Alarm Output
Yes
Alarm output
N.C.
Language
English
Passcode
0
Scroll Delay
0.15 secs
Load Defaults
(See user manual)
Limiter Installed
No
COMMUNICATION SETUP SUB-MENU
Parameter
Factory
User
Protocol
Modbus RTU
Modbus Addr
*n/a (1)
Modbus Sub Addr
*n/a (0)
Baud Rate
Auto
Parity
*n/a (None)
Tx Deley
0.06 secs
* n/a: Parameter may only appear if certain features are
enabled. Values shown in brackets are the Factory defaults
if the settings are enabled.
This information defines the default 915 Series Control
Module configuration as set by the Factory for firmware
V1.0X. These settings are subject to change without notice.
It is the user’s responsibility to verify that all configuration
parameters are chosen appropriately for the intended
application.
OTHER ALARMS CONFIGURATION SUB MENU
Parameter
Factory
User
Lo Load
Enable
Lo Load
1.0 A
Lo Load Filter
0 sec
Hi Load
Disable
Hi Load
*n/a (30.0 A)
Hi Load Filter
*n/a (0 sec)
Hi GFI
Enable
Hi GFI
20 mA
Hi GFI Filter
0 sec
GFI Trip
Enable
GFI Trip
30 mA
Lo Volt
Enable
Lo Volt
90 V
Lo Volt Filter
0 sec
Hi Volt
Disable
Hi Volt
*n/a (270 V)
Hi Volt Filter
*n/a (0 sec)
Lo Resist
Disable
Lo Resist
*n/a (50%)
Lo Resist Filter
*n/a (0 sec)
Hi Resist
Disable
Hi Resist
*n/a (50%)
Hi Resist Filter
*n/a (0 sec)
Nominal Resist
*n/a (6.00 Ω)
Overcurrent Trip
*n/a (Enable)
Switch fail
Enable
HTC Reset
Disable
C.B. Limiting
*n/a (Disable)
Output Limiting
*n/a (Disable)
Switch Limiting
*n/a (Disable)
Contactor Count
Enable
Contactor Count
200,000
EEROM data Fail
Enable
nVent.com | 7