nVent.com | 49
4.2.29
Acknowledging and Resetting Alarms
Purpose
To acknowledge and reset any alarm conditions that may exist. Use
the Up / Down Arrow keys to examine the next/previous active
alarms.
Setting/Range
See Alarm Filter Times
Factory Default
N/A
Alarm Filter Times
Alarm Type
Filter Time
Lo TS 1 and 2
15 minutes
Hi TS 1 and 2
15 minutes
Lo load current
2 minutes
Hi ground-fault alarm
10 seconds
Hi ground-fault trip
< 1 second
OPEN / SHORTED TS 1 and 2
10 seconds
Contactor count
< 1 seconds
Switch failure
2 minutes
Содержание C910-485