Ground-fault Current Alarm level (Hi GF Alarm)
Purpose
This allows the user to set the ground-fault current alarm level.
Exceeding this limit will trigger the alarm to indicate that a ground-
fault condition exists in the heating cable circuit. To protect against
the risk of fire or shock, ground-fault level should be set at the lowest
level possible to allow normal operation of the cable.
Alarm time delay filter is factory set as immediate
Setting/Range
20 mA to 100 mA
Factory Default
20 mA