INSTALLATION INSTRUCTION & OPERATION MANUAL
PowerPlus RDIDC-100-3R-1U-X
www.raycap.com
© Raycap | All rights reserved.
•
(
320-1674) | Rev.A
Page 11 of 28
Scan QR for Complete Installation Instructions:
5.5
Single Module Configuration
(See Appendix for Cable Configurations)
Configuration 1
(we recommend using a 150A breaker)
Torque:
All PowerPlus
terminal
connections are
¼-20 studs.
Torque to 65
in-lbs.
DC Power Plant
150A
150A
RDIDC-9052-PDU-48
Use #6 AWG copper
wire for ground
Use #6 AWG copper
wire for ground
2 AWG for PowerPlus to PDU
1/O for
DC Power Plant to
PowerPlus and PDU
Recommended Lugs
For 1/O Use:
Panduit LCD1/O-14A-X
for Input & Output
For 2 Gauge Use:
Panduit LCD2-14A-Q
for Output
For 6 Gauge Use:
Panduit LCD6-14A
for Ground
-48V
OUT
(1)
-48V
OUT
(2)
-48V
OUT
Unused
-48V
-48V
IN
Return
OUT
Return
-48V Return
Return
IN
GROUND
Power Plus
100A
Module
Installed
Trunk to
Upper OVP
Use #6 AWG
copper wire
for ground