background image

Use and maintenance manual Flexi 7 - Flexi 9

Pag.39 

Rev.0  01/03/2023

EN

The first setting allows the activation of the COMFORT CLIMA function. This function is intended to ensure that the room tem

perature set is maintained steady upon setting the maximum period of “X” minutes (SWITCH-OFF DELA Y: 5 MIN) before switch-ing

to ECO STOP phase. The STOVE maintains this state until the temperature drops below the set value (DELTA COMFORT CLIMA:

5°C). For example, with the room temperature at 21 ° C, the stove switches of f when this temperature is reached and restarts when

the temperature reaches 16°C (21°C - 5°C). You can also activate the function using an external thermostat, keeping in mind that this 

does not include the value of hysteresis.

Setting

Below are the steps to follow, starting from the Home screen, to access the Home menu.

After following the above procedure

Settings > Enable thermostat

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

 

📌

In “Home” mode, instead of room temperature measured and settable, appears the line T ON if the room in which the 

thermostat is installed has not reached the temperature requested or the writing T OFF if the temperature in the room is 

reached.

User’s manual HANDHELD TOUCH RADIO

User’s manual HANDHELD TOUCH RADIO

Pag.22 

Pag.23 

Vers. 01 of:07.04.14

Vers. 01 of:07.04.14

Loading the auger

MENU

USER

SCREW FEEDING

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

USER

MANUFACTURER 

ENGINEER

MENU

USER

MANUFACTURER 

ENGINEER

USER

USER

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

ENABLE COMFORT

ENABLE COMFORT

ENABLE COMFORT

RESTART DELTA

RESTART DELTA

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

ENABLE COMFORT

ENABLE COMFORT

COMFORT CLIMA DELTA

COMFORT CLIMA DELTA

RESTART DELTA

SHUTDOWN DELAY

SETTINGS

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

ALWAYS EMPTY THE BRAZIER BEFORE TURNING THE STOVE ON AND ALWAYS CHECK  

THAT ALL NONE OF ITS HOLES IS CLOGGED NEVER EMPTY THE RBAZIER INSIDE THE HOPPER.  

FIRE HAZARD.  

Carry out this operation to facilitate stove’s first start operations; You should also check that you have introduced pellets  

into the hopper and wait until the stove is in “SHUTDOWN” or “FINAL CLEANING” mode. The number expressed in sec-

onds indicates the rotation time of the infeed screw during the first loading cycle. Once this time has elapsed, the infeed  

screw stops immediately and then pellets are emptied from the grate before turning on the equipment.  

Below are given the steps for accessing the relative menu.  

Press the key  “access 

menu” to access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

At the end of the auger loading, the display shows 0 “and automatically switches to the USER menu page.  

Press the key for several times until the Stand-by page is displayed.  

Setting operating temperature and power: 

Set the two values following the indications given in the chapter “Description of thr display” 

Turning the device on 

Keep the key ON/OFF pressed for a few seconds to turn on the stove.  

Press CONFIRM to enable  

the rotation of the auger  

The appearance of the message “ADJUST THE RDS SYSTEM” indicates that the initial parameter testing procedure  

and calibration has been unsuccessfully. This indication does not cause stove blockage (see the SIGNALLING POP UP  

section).  

On the display of the handheld set appears the following:  

Press and hold the ON/OFF button to turn off the stove door, and reset any alarms triggered.  

In case the infeed screw operations described avobe have not been executed, the stove may fail to turn on. In this case,  

carry out the operations described above and   empty the brazier and reset the alarm.  

If the stove still fails to turn on, check that the grate is properly installed and perfectly adherent to the base, and also check that  

there are no deposits that prevent the smooth passage of air to enable ignition. If the problem persists, contact the support ser

-

vice. 

Sequence of ignition phases  

SWITCH-ON- initial pellet loading phase; 

WAIT FLAME - flame 

development  wait  

phase; 

FLAME PRESENT - flame stabilization  

phase and reduction of combustible  

inside the brazier;  

What happens if the batteries are empty?  

If the battery is discharged, within the  

“drop” is shown a symbol that indicates  

that the battery is empty, while maintain-

ing active the features of your device.  

WORK - operation phase 

described in  

the dedicated chapter;  

As soon as the level of the battery  

prevents the radio communication  the 

handheld set displays on full screen  the 

picture of empty battery and all device 

functions are locked  until the batteries 

are replaced   

CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT, THEREFORE, NOT POWERED. MORE-

OVER, WE RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3°C IF YOU INTEND TO USE  

THE COMFORT CLIMA FUNCTION.  

Operating phases of the appliance 

Modulation 

During the work phase, the appliance should reach the room temperature set; when this condition is met, the stove switches to  

MODULATION mode in which fuel consumption and ventilation are minimum.  

If you wish to detect the ambient temperature by means of an external thermostat (optional), this must be connected to  

the appropriate connector on the rear side of the stove; and you will have to activate the reading in “SETTINGS - EN  - 

ABLE THERMOSTAT.” On display appears the writing TON / TOFF based on thermostat request.  

Comfort climate 

The activation of this function enables the stove to reduce pellet consumption by activating the modulation phases, after the desired  

temperature has been reached. Subsequently, the stove checks that the temperature is maintained steady for a preset  time. If this 

condition is met, it automatically switches off, and on display appears the writing ECO.  

The stove turns on again when the temperature drops below the set threshold. 
Below are given the steps for accessing the relative menu.  

Press the key  

“access menu” to 

access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

Once you have accessed the Climate Comfort menu, it is possible to operate on the 3 types of settings dedicated to the function:  

Press the key for several times until the Stand-by page is displayed.  

Press the key “selection” for  

“selection”  

to switch to the second page  

of USER MENU and select  

CLIMATE COMFORT.   

User’s manual HANDHELD TOUCH RADIO

User’s manual HANDHELD TOUCH RADIO

Pag.20 

Pag.21 

Vers. 01 of:07.04.14

Vers. 01 of:07.04.14

2

3

1

2

3

1

FIRST INSTALLATION?

PRESS THE KEY RADIO 

ADJ ON THE STOVE

YES

MENU

USER

USER

SETTINGS

SETTINGS

DATE-TIME

USER

COMFORT CLIMA

MANUFACTURER 

ENGINEER

ENABLE EXT. TH.

CONTRAST

FW VERSION

ADJUST

LANGUAGE

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

Handheld touch radio initialization 

In order  to operate correctly, the handheld set should be interfaced with the electronic board installed inside the stove.  For this  

reason, on display appears the following message:  

If the handheld set is used for the first time, select 

YES

 using the selection keys and confirm with the dedicated key. 

On the display of the handheld set appears the following:  

Hold down for a few seconds the button of radio communication (RADIO ADJ) of the PCB, located on the back of the stove, to  

initialize the device.  

The flashing yellow LED indicates that the circuit board is waiting to receive the signal from the handheld set. 
By pressing the enter key on the handheld set, the components start communicating with each other. A check sign on the display,  

accompanied by a sound signal, shows that the initialization of the handheld set has been completed sucessfully 

.  

When you replace the batteries, you do not have to run the initialization procedure of the handheld set. In this case, when  

on display appears the message “FIRST INSTALLATION ?”, select 

NO

 and press the confirmation key.  

Description of the display 

The display of the handheld set is described below (in stand-by mode):  

After 5 minutes of inactivity, the display of the handheld set turns dark, switching to “SLEEP” mode, while maintaining the  

radio connection with the stove. By pressing the key ON/OFF, the display becomes active again. 

The first pressure of any key with the display active, lights up its backlight, but it is not, however 

considered a   command.  

The display is subdivided into three parts:  

1. It shows the current room temperature measured by the handheld set. Moreover, if you press the DOWN scroll key you will 

display 

the temperature settings that can be changed using the two UP/DOWN keys. Any change made is confirmed automatically 

within 3 seconds from the change or by pressing the confirmation key. A sound signal indicates that the change has been con

-

firmed. 

In the inactive phases (combined with the 3rd part of the display) indicates the state of the stove.  

In the active phases, it indicates the operating power of the stove. 

In addition, by pressing the DOWN scroll button, you can display the power settings, that can be edited using the two scroll  

keys        

UP/DOWN: The confirmation of any change takes place automatically within 3 seconds from the change or by pressing the con

-

firmation key. A sound signal indicates that the change has been confirmed.  

Time and date setting 

Below are given the steps for accessing the relative menu.  

Press the key  “access menu” to 

access  

the  

MENU page  

Press the key  

“confirm” to  

access the  

SETTINGS  

page  

Press the key  

“confirm”  

to access the  

USER page  

Press the key  “con

-

firm”  

to access the  page 

DATE-TIME  

Press the key “selection” for  

“selection”  

to switch to the second page  

of USER MENU and select  

SETTINGS.   

Press the increase key to change every single value 

Press the increase key to change every single value 

Press “confirm” to confirm the settings and switch to the next 

value. 

By pressing the key “back” for several times you will display 

the  stand-by page.  

COMFORT CLIMA

ACTIVATE COMFORT

DELTA RESTART

DELAY SWITCH OFF

DELAY SWITCH OFF

DELAY SWITCH OFF

MENU

USER

TECHNICIAN

PRODUCER

USER

LOADING AUGER

CHRONOTHERMOSTAT

SET AIR-PELLET

STOVE STATUS

USER

COMFORT CLIMA

SETTING

SETTING

DATE - HOUR

ENABLE T.EXT

CONTRAST

VERSION FW

ADJUST

LANGUAGE

SETTING

DATE - HOUR

ENABLE T.EXT

CONTRAST

VERSION FW

ADJUST

LANGUAGE

Содержание Flexi 9

Страница 1: ...USE AND MAINTENANCE MANUAL Flexi 7 Flexi 9...

Страница 2: ...hermostat room temperature control No Useful efficiency NCV as received with electronic room temperature control No Useful efficiency at nominal heat output th nom 94 4 with electronic room temperatur...

Страница 3: ...room temperature control No Useful efficiency NCV as received with electronic room temperature control No Useful efficiency at nominal heat output th nom 93 5 with electronic room temperature control...

Страница 4: ......

Страница 5: ...do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informatio...

Страница 6: ...gations and forbidden actions 14 Characteristics of the fuel 15 TECHNICAL CHARACTERISTICS 16 Technical Data 16 Minimum clearances from combustible materials 17 Measurements 17 Technical diagram Flexi...

Страница 7: ...nce of ignition phases 36 Modulation 36 Description of menu functions 36 Setting 39 Ventilation menu 41 Single ducting 41 Stove phase general layout 44 Warning Pop Up 45 Alarms table with reference co...

Страница 8: ...ollowing harmonised standards and or technical specifications have been applied EN 14785 EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 EN 60335 1 EN 60335 2 102 EN 62233 EN 50581 ETSI EN 300220 1 Al...

Страница 9: ...tzungsanweisungen Distanza minima da materiali infiammabili Minimum distance from flammable materials Distance moindre de mat riels inflammables Distancia minima de materiales inflamables Minimale afs...

Страница 10: ...glass the gaskets the paint job the stainless steel or cast iron combustion grille the resistance the Majolica cladding the aesthetic parts any damages caused by unsuitable installation and or use of...

Страница 11: ...re if any inconsistency arises it will be necessary to follow the text in the original language or contact our Technical Documentation Office Symbols used in the manual symbol definition This symbol i...

Страница 12: ...e Only use original spare parts Any tampering and or replacements that have not been authorised by Ravelli can pose a danger to the user s safety In the event of particularly adverse weather condition...

Страница 13: ...the contract and herein the operating manual procedures are followed routine maintenance is carried out according to the times and methods set forth extraordinary maintenance is promptly carried out...

Страница 14: ...o a regulation chimney provide a suitable system for the supply of combustion air air intake or intake duct for watertight appliances always perform maintenance with the appliance off and cold perform...

Страница 15: ...r of 6 mm and a variable length between 10 and 40 mm Their density is equal to approximately 650 kg m3 Due to their low water content 10 they have a high energy content The UNI EN ISO 17225 2 2014 sta...

Страница 16: ...125 Smoke flow g s 3 0 3 7 3 0 4 4 Minimum draft Pa mbar 8 10 0 08 0 1 9 10 0 09 0 1 Electrical connection Hz V 50 230 50 230 Electrical power consumption max W 320 320 Electrical power consumption r...

Страница 17: ...side mm 200 200 L Left side mm 200 200 B Rear mm 200 200 A Front mm 1000 1000 Measurements Unit of measurement Flexi 7 Flexi 9 D co Flexi 9 Glass Flexi 9 Steel Height mm 1050 1050 1050 1050 Width mm 5...

Страница 18: ...Use and maintenance manual Flexi 7 Flexi 9 Pag 18 Rev 0 01 03 2023 EN Technical diagram Flexi 9 530 1050 530 574 574 80 CANALIZATION 395 50 AIR INLET 130 80 SMOKE OUTLET 192 305 72 5...

Страница 19: ...the sofa using the handheld remote control Ravelli s patented cleaning system minimises maintenance by the user There is no longer any need to clean the brazier before each lighting and all maintenanc...

Страница 20: ...uching the CONFIRM button you can read the detail of the warning doors and ash pan open If the combustion chamber door the pellet hopper lid and or the ash drawer are not closed within 1 minute the st...

Страница 21: ...rical system of the house is up to standard equipped with a grounding circuit and all the safety systems required by the standards It should be noted that the stove s operating program has been design...

Страница 22: ...1 1 DISEG VERIF APPR FABB Qual SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE LINEARE ANGOLARE FINITURA INTERRUZIONE BORDI NETTI NOME FIRMA DATA MATERIALE NON SCALARE DISEGNO R...

Страница 23: ...talled that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly or installation operation Local administrative regula...

Страница 24: ...the Manufacturer Do not connect the appliance to a collective chimney The chimney must be built applying the following regulations it must observe product standard EN 1856 1 it must be made of materi...

Страница 25: ...ion in the presence of other combustion appliances or VMC system it is necessary to check the appliance for correct operation The appliance must be placed inside living quarters It must never be insta...

Страница 26: ...re is another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draught problems in the ap...

Страница 27: ...ld quickly obstruct smoke passage causing draught problems in the appliance See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fitting with collection c...

Страница 28: ...stove s power cable must only be connected after the installation and assembly has been completed of the appliance and must remain accessible after installation To make the electrical connection proc...

Страница 29: ...f the ducting pipe to avoid heat dispersion It is compulsory to connect the stove to the duct of the house before lighting Make sure that it is not possible to touch the fan blades installing the nece...

Страница 30: ...AC 2 1 E S A F O R T U E N M1 M2 M3 T1 T2 T3 S2 S3 G2 S4 R1 G1 G1 G3 M4 Generico G1 Encoder lettura giri estrattore G2 Conta colpi pulitore automatico G3 Palmare Radio Touch S2 External thermostat S3...

Страница 31: ...ure switch T2 Resettable thermal breaker T3 Pellet tank contact Motors M1 Auger gear motor M2 Automatic cleaning system M3 Flue gas fan M4 Room fan M5 Ducting fan Resistance R1 Igniter Probes S1 Flue...

Страница 32: ...his reason on display appears the following message If the handheld set is used for the first time select YES using the selection keys and confirm with the dedicated key On the display of the handheld...

Страница 33: ...cover of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the remote control and observe the poles Instal...

Страница 34: ...ERSION ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into three parts 1 It shows the current room temperature measured by the handheld set Moreove...

Страница 35: ...DELTA COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT THEREFORE NOT POWERED...

Страница 36: ...contact therefore not powered moreover we recommend you use a thermostat with a minimum offset of 3 C if you ntend to use the comfort clima function Description of menu functions Press the key to acce...

Страница 37: ...perature If the type of system designed requires controlling the 3 way valve diagram 1 and 3 it is necessary to purchase the optional kit from the retailer or the authorized Ravelli dealer CHRONO CHRO...

Страница 38: ...ER WE RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3 C IF YOU INTEND TO USE THE COMFORT CLIMA FUNCTION Operating phases of the appliance Modulation During the work phase the appliance shoul...

Страница 39: ...SION FW VERSION LANGUAGE LANGUAGE LANGUAGE LANGUAGE ADJUST ADJUST ADJUST ADJUST In Home mode instead of room temperature measured and settable appears the line T ON if the room in which the thermostat...

Страница 40: ...u will confirm of data and switch to the page within SETTINGS menu The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and the...

Страница 41: ...erating modes manual and automatic Manual mode the user manually sets distribution of warm air between front ventilation and ducting Automatic mode the stove automatically manages distribution of warm...

Страница 42: ...from three options EQUAL if the cubature of the two rooms is more or less the same REAR if the cubature of the room with ducting is larger than the one with the stove FRONT if the cubature of the roo...

Страница 43: ...ion it is possible to set the room temperature reached by the ducting and the speed of the fans Press the increase decrease keys to modify the setting Press the confirm key to confirm the new setting...

Страница 44: ...ture set is reached see the dedicated section WAITING START RESTART Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically IGNITION RESTART The...

Страница 45: ...the Support Service If the problem persists contact the Support Service AL 04 FAN BROKEN Fume exhaust encoder is not working or is connected incorrectly Contact the Support Service No power to fume e...

Страница 46: ...tage AL 15 AUGER TRIAC An internal part of the electronic board that controls the pellet auger is faulty Check the flue is free and clean Possible voltage drops or incorrect input voltage Check the ma...

Страница 47: ...g 47 Rev 0 01 03 2023 EN EXTERNAL POWER SUPPLY WITH MICRO USB CONNECTOR WIFI MODULE BOARD WITH CONNECTORS FOR EXTERNAL POWER SUPPLY CONNECTION Wifi kit Wifi external power supply kit if applicable MOT...

Страница 48: ...martphone tablet entrare nel menu Android Impostazioni Connessioni Wi Fi iOS Impostazioni Wi Fi Selezionare la rete WINET XXXXXXXX ed inserire la chiave WPA indicata nell etichetta del dispositivo wi...

Страница 49: ...odel name e g KTR AIR and then click Yes The screen offers a list of firmware once you have identified your model click on Select Yes Close the App and go to step 6 to register the account 4 CONNECTIO...

Страница 50: ...open where you can register the WiFi device WiFi device registration When you click the link in the confirmation E mail the window to register the new device will open click Register your wifi device...

Страница 51: ...l number and give the module a name e g living room stove STEP 3 complete with your information click Next and then Complete registration STEP 2 enter the product serial number and give the module a n...

Страница 52: ...e pellet the stove operating mode and combustion control can affect maintenance activity frequency Cleaning Perform the cleaning operations so as to guarantee correct stove operation The table below l...

Страница 53: ...emove them if necessary Extraordinary maintenance Extraordinary maintenance activities must be carried out by staff from the Authorised Assistance Centre Do not wait for components to be deteriorated...

Страница 54: ...F APPR FABB Qual SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE LINEARE ANGOLARE FINITURA INTERRUZIONE BORDI NETTI NOME FIRMA DATA MATERIALE NON SCALARE DISEGNO REVISIONE TITOLO...

Страница 55: ...tches 3 Clean the ashes eventually use a brush or similar and reassemble everything Note the hatches are equipped with gaskets therefore before reassembling them make sure that the gaskets are not wor...

Страница 56: ...valves at the inlet and outlet for prolonged downtime DISPOSAL AT END OF SERVICE LIFE Warnings for the correct disposal of the product Demolition and disposal of the appliance is under the exclusive l...

Страница 57: ...Displays Sensors Spark plugs Electronic boards Batteries Dispose of separately at authorised centres in accordance with WEEE 2012 19 EU and its national transposition E METAL STRUCTURE Dispose of sep...

Страница 58: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Страница 59: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Страница 60: ...free to make any variations to the features of its products without notice Aico S p A Headquarter Via Consorzio Agrario 3 D 25032 Chiari BS Italy Research and Development Centre Viale del commercio 1...

Отзывы: