SMOKE SENSOR TESTING

 

  Allow smoke from a cotton wick or a test smoke aerosol to enter 

the detector-sensing chamber for several seconds. When 
sufficient smoke has entered the chamber, the detector will signal 
an alarm, this being visible by a continuous illumination of the LED. 
Reset each detector and/or control unit before attempting to test 
any additional detectors in the same zone. If the alarm fails in this 
step, it indicates a defective unit, which requires service. 

 

HEAT SENSOR TESTING 

The detector to be tested should be subject to a flow of warm air at a 
temperature of between 65

°

C and 80

°

C. (This requirement can be 

met by some domestic hair dryers). 
Proceed as follows: 
1.  Switch on the warm airflow and check that temperature is correct 

and stable. 

2. From a distance of several inches, direct the airflow at the guard 

protecting the thermistor. The detector should alarm within 60 
seconds. 

3. Upon alarm, immediately remove the heat source and   check 

that the red LED of the detector is illuminated. Reset the detector 
from the control panel. 

4.

If detector fails to go into alarm mode within 60 seconds it is too 

insensitive and needs to be returned to the distributor for servicing. 

5. 

After testing, check that the system is set for normal operation and 
notify the appropriate authorities that the testing operation is 
complete and the system is active again. 

 

 
 

 
     

SPECIFICATION 

Fixed Temperature Sensor: 138

F (59

C) 

Rate-of-Rise Temperature Sensor: 20

/min(11.1

C /min) 

Humidity Range:    0% to 95% Relative Humidity, non condensing 
Operating Temperature Range: -10

°

C to 37.8

°

The maximum number of detectors allowed to be connected to each 
initiating device circuit of the control unit is 32. 
Compatible Panel: Ravel Electronics Pvt Ltd., RE -2504 / 08.   
Height: 1.8 inches (46 mm) with base 
Diameter: 3.93 inches (100 mm) with base 
Detail as shown in Form.1 

 
Smoke detectors are not to be used with detector guards unless 
the combination as been evaluated and found suitable for that 
purpose. 
 
MAINTENANCE 

The recommended minimum requirement for detector maintenance 
consists of an annual cleaning of dust from the detector head by 
using a vacuum cleaner cleaning program should be agreed to the 
individual environment in conformance with NFPA-72A standard. 
 

CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE 
FACTORY SEALED SMOKE DETECTOR. THIS ASSEMBLY IS 
SEALED FOR YOUR PROTECTION AND IS NOT INTENDED TO 
BE OPENED FOR SERVICING BY USERS. OPENING THE 
DETECTOR HEAD WILL VOID THE WARRANTY. 
 
REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO. 
NBTB20081017, REV.F   

RE316 USER

s MANUAL ,REV.F 

Form.1 

Note: 

  * 1 If a model with the 

-2

 suffix, the Base model no. is RE-312 

*2 If a model with the 

-2L

 or 

-4

 suffix, the Base model no. is RE-314

 

 

LIMITED WARRANTY STATEMENT 

RAVEL ELECTRONICS, Inc. represents that this product is free from defects in material and workmanship. And it will repair or replace any product or 
part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from the date of purchase but not to exceed 
eighteen (18) months after shipment by the manufacturer. For a full description of RAVEL ELECTRONICS

S LIMITED WARRANTY, which, among 

other things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. 
Please read the entire LIMITED WARRANTY on the RAVEL quotation. Acceptance of order and/or original invoice which will become part of your sales 
agreement. Please contact RAVEL ELECTRONICS directly for a return merchandise authorization (RMA) number before returning goods to the factory 
in Chennai, India R.O.C. Shipment must be prepaid and RAVEL will repair or replace your returned detector.

RAVEL ELECTRONICS PRIVATE LIMITED. 

150A, Electronic Industrial Estate, Perungudi, Chennai – 600 096. Tamil Nadu, India. 

Tel: +91-44-2496-1004 / 0825 / 3241 / 3251;      Fax: +91-44-4204-9599 

http://www.ravelfirepanels.com

 

ISSUE NO.NBUM 20081017 REV.F 

 

Model 2/4 

Wire 

Thermal Voltage Standby

Current 

Alarm 
Current 

Surge 
Current

Start-up
Time 

Reset
Time

Reset 
Voltage

Sample

Cycle 

Smoke 
Sensor

Heat 

Sensor

Reed 

Switch 

Relay 

Outpu

Remote 

LED 

Base model

RE316S-2 2 

9~33V 

50uA 

90mA 

170uA

60s 

3s 

<1V 

5s 

 

     RE-312 

RE316S-2M 2 - 

9~33V 

50uA 

90mA 

170uA

60s 

3s 

<1V 

5s 

 

 

 

  RE-312 

RE316S-4 4 

9~33V 

50uA 

40mA 

170uA

60s 

3s 

<1V 

5s 

 

 

 

 

 RE-314 

RE316S-4M 4 - 

9~33V 

50uA 

40mA 

170uA

60s 

3s 

<1V 

5s 

 

 

 

 

 RE-314 

RE316S-2L 2 - 

9~33V 

50uA 

90mA 

170uA

60s 

3s 

<1V 

5s 

 

 

 

 

 

RE-314 

RE316S-2LM 2  - 9~33V 

50uA 

90mA 

170uA

60s 

3s 

<1V 5s 

 

 

 

 

 

RE-314 

RE316H-2 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

    RE-312 

RE316H-2M 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

  RE-312 

RE316H-4 4 

59

9~33V 50uA 40mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 RE-314 

RE316H-4M 4 

59

9~33V 50uA 40mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 RE-314 

RE316H-2L 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 

RE-314 

RE316H-2LM 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 

RE-314 

RE316SH-2 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

    RE-312 

RE316SH-2M 2 59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

  RE-312 

RE316SH-4 4 

59

9~33V 50uA 40mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 RE-314 

RE316SH-4M 4 59

9~33V 50uA 40mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 RE-314 

RE316SH-2L 2 

59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 

RE-314 

RE316SH-2LM 2  59

9~33V 50uA 90mA 170uA

60s  3s  <1V 

5s 

 

 

 

 

 

RE-314 