PX3TS Transfer Switch Quick Setup Guide
5
QSG-PX3TS-0A-v2.6-E
255-80-0032-00 RoHS
For example, 192.168.84.4 cycles in this sequence:
192, 168, 84, 4
Note: If your network only supports IPv6 or static IPv4
addresses, the IP address must be configured using a serial or
USB port. See
Addendum
(on page 6) for instructions.
Step 3: Log in to the PX3TS Web Interface
1. Open a browser and type the IP address of the PX3TS
device.
2. The default credentials are: user
admin
, password
raritan
.
3. Click Login. The PX3TS home page displays.
4. Change the password if prompted.
Step 4: PX3TS Web Configuration Overview
1. From the Dominion PX Explorer pane, click the Transfer
Switch icon.
2. Click Setup to configure the transfer options.
3. Click Power Quality Setup to configure power quality.
Transfer Options Setup
1. Enable/disable the front panel Manual Transfer button.
2. Enable/disable automatic retransfer. Retransfer is the
transfer back to normal operation when preferred inlet
power is restored.
3. Enter the time (seconds) preferred inlet power must be in
the normal state before retransfer occurs.
4. Enable/disable retransfer when inlets are out of phase.
5. (Optional) Thresholds for inlet phase angle difference
reporting. Values do not affect phase sync detection or
transfers.
Power Quality Setup
Inlet power quality state (normal/warning/critical) is derived
from the inlet's voltage and frequency quality - whichever is
lower. If voltage or frequency is critical, power quality is critical.
If either is warning, quality is warning. When both are normal,
power quality is normal.
PX3TS transfers to standby operation when preferred inlet
power quality goes critical and retransfers to normal operation
when power quality returns to normal. The warning state does
not cause transfers and is intended as an early warning
indication of a possible problem.
When quality goes from better to worse, the state change is
said to assert. You configure how long the quality must remain
in the worse state before the state change actually occurs.
When quality goes from worse to better, the state change is
said to deassert. You configure the hysteresis - how much the
quality must be better than the threshold - before the state
change occurs.
Voltage and frequency configuration is identical.
1. Enter upper and lower thresholds for warning and critical.
2. Enter assertion times (seconds).