as indicated above. Note: the unit can only be powered down 

while in the Idle Mode

 

5. Chill Mode Operation 

a. The controller can run one of four possible chill modes, by either 
manual selection or automatically depending on certain prior conditions. 
This is explained more fully below: 
i. Idle Mode 

1. This mode is automatically started when the On key is 
depressed. 
2. This mode is returned to automatically when any chill modes 
have 
been stopped. 
3. Operation: 

a. When the controller enters the Idle Mode, the display 
will showthe text “IdLE,” briefly on the segmented 
display, followed by the display of the air temperature. 
b. The unit will pre-chill the cabinet to the Product 
Temperature Set Point (PtSP)
. The Air temperature will 
be displayed and will be accompanied by a flashing Air 
status LED indicator. Once Air temperature reaches the 
set point temperature, the Air status LED indicator will 
illuminate solid, meaning the air temperature is at or 
below the “Safe” temperature. Any food probe inside the 
cabinet will be validated in a similar fashion should their 
individual temperature readings reach the “Safe” 
temperature. 
c. In the event any food probe reaches a temperature 
greater than the Temperature Alarm (tALn) preset, the 
display will flash the offending probe temperature while 
toggling the corresponding status LED indicator. Refer 
to the Auto Mode section for further details on the 
Temperature Alarm feature.  
d. During this mode, the Fan relay is on and the 
Compressor Relay is activated “On” when Air 
temperature is above Product Temperature Set Point 
(PtSP) 
Product On/Off Differential (PdiF) and “Off” 
when Air temperature is below Product Temperature Set 
Point (PtSP) 
Product On/Off Differential (PdiF). Note: 
Since no mode has actually been selected, no mode 
LED’s will be illuminated. 

ii. Auto Mode 

1. Can be manually selected by pressing the Mode key once 
(illuminating 
the Auto LED) and started by pressing the Start key. 
2. Can also be directly started by just pressing the Start key 
when no 
mode LED’s are illuminated. 

Содержание BC-18-PUB

Страница 1: ...nsignee to inspect the container upon receipt of same and to determine the possibility of any damage including concealed damage Unified Brands suggests that if you are suspicious of damage to make a n...

Страница 2: ......

Страница 3: ...ts Congratulations on your recent purchase of Randell brand food service equipment and welcome to the growing family of satisfied Unified Brands customers Our reputation for superior products is the r...

Страница 4: ...design and specifications without prior notice NOTICE Please read the entire manual carefully before installation If certain recommended procedures are not followed warranty claims will be denied MOD...

Страница 5: ...on and set up In the event equipment was shipped to a site other than the final installation site Unified Brands will warranty for a period of three months following installation with proof of startin...

Страница 6: ...ell covers all non electrical components under the same guidelines as our standard domestic policy 2 All electrical components operated on 60 cycle power are covered under our standard domestic policy...

Страница 7: ...ges must be filed immediately within 10 days by the consignee with the freight carrier and all cartons and merchandise must be retained for inspection RETURNED GOODS Authorization for return must firs...

Страница 8: ...it Specifications Model L D H Pan Capacity 12 x 20 x 2 5 HP Volts Hz Ph Amp Draw NEMA BTU Requirements for Remote Installations Ship Wt BC 18PUB 40 35 12 71 75 18 1 5 120 208 230 60 1 16 14 20P 12100...

Страница 9: ...unlight Also avoid locating in an unheated room or where the room temperature may drop below 55 F 13 C or about 86 F 32 C INSTALLATION CHECKLIST After the final location has been determined refer to t...

Страница 10: ...cated on the rear interior wall NOTE It is important that a voltage reading be made at the compressor motor electrical connections while the unit is in operation to verify the correct voltage required...

Страница 11: ...ed and used for set point control or a temperature alarm indication ii Solid Indicated probe has reached the Safe set point or purposely selected for display monitoring iii Solid Momentary Indicated p...

Страница 12: ...solid meaning the air temperature is at or below the Safe temperature Any food probe inside the cabinet will be validated in a similar fashion should their individual temperature readings reach the S...

Страница 13: ...e indicator Green LED for food probes Red LED for Air temperature probe will be illuminated The display will show the warmest probe temperature as denoted by a flashing LED Under varying load conditio...

Страница 14: ...Down arrow keys and then started by pressing the Start key 2 Note Manual Mode is the default mode if no product probes are present During this case an attempt to start the Auto Mode by either manual...

Страница 15: ...current mode and return the operation of the controller back to the Idle Mode iv Defrost Mode 1 This mode is manually selected by depressing the Mode key three times illuminating the Def LED and is st...

Страница 16: ...to Table 1 that are used to govern chiller operation Each preset is user adjustable and can be changed at any time the controller is activated b Presets are accessed via a user friendly Menu as follo...

Страница 17: ...dify other RTC settings v Depress the Stop key to exit the preset menu vi Note After approximately one minute of keypad inactivity the Clock Calendar Menu will automatically be exited 9 Alarms a Door...

Страница 18: ...l operation or when printing a History of prior chill information c Log Data Specification i The log memory consists of a nonvolatile storage device capable of holding 1489 records equivalent to appro...

Страница 19: ...being resumed after a defrost cycle k Door Alarm Door_Alarm Indicates the point in which the door alarm was activated L Air Probe Alarm Air_Prb_Alarm Indicates the point in time that the air probe ma...

Страница 20: ...l time stamp events during Chill Cycle or Sample 15 minute interval time stamp events during Hold Cycle plus Begin_Hold and Resume_Hold events 11 USB Flash Drive a Data stored from previous blast chil...

Страница 21: ...robe as indicated by Select LED indicators iii Use the up down arrows to add or subtract from the displayed probe reading The displayed reading will reflect the raw reading plus the offset iv Exit men...

Страница 22: ...l Time dint 2 AM 0 to 23 hours in 24 hr format 10 Daily Defrost Frequency dFrq 1 every 24 hrs 0 to 4 defrosts per day 11 Fan Defrost FdEF On Off On 12 Printer Enable Prnt Off Off On 13 Printing Filter...

Страница 23: ...ANS IN RACKS INSIDE THE UNIT INSERT FOOD PROBE IN PRODUCT CENTER AND CLOSE DOOR 4 PRESS START STOP BUTTON ONCE NOW IN AUTO MODE UNIT WILL BLAST CHILL UNTIL THE WARMEST FOOD PROBE REACHES 39 F 5 PRESS...

Страница 24: ...tive Maintenance Unified Brands strongly suggests a preventive maintenance program which would include the following Monthly procedures 1 Cleaning of all condenser coils Condenser coils are a critical...

Страница 25: ...STEEL NOTE Do not pressure wash equipment as damage to electrical components may result Proper maintenance of equipment is the ultimate necessity in preventing costly repairs By evaluating each unit o...

Страница 26: ...3 Probe faulty 3 Replace probe Freezing product or product not cold enough 1 Check temperatures on Food Probe 1 2 3 4 2 Check AIR Probe temp 1 Clean probes and test probes to see if there are within...

Страница 27: ...unifiedbrands net 27 Electrical Diagram...

Страница 28: ...28 800 621 8560 Electrical Diagram Control Wiring...

Страница 29: ...unifiedbrands net 29 Replacement Parts Blast Chiller...

Страница 30: ...30 800 621 8560 Replacement Parts Blast Chiller Control Panel...

Страница 31: ...unifiedbrands net 31 Replacement Parts Blast Chiller Door Assembly...

Страница 32: ...32 800 621 8560 Replacement Parts Blast Chiller Condensing Unit...

Страница 33: ...unifiedbrands net 33 Replacement Parts Blast Chiller Evaporator Coil Assy...

Страница 34: ...FOSS 120V 18Z7612 19 RF VLV005 VALVE LIQUID LINE SOLENOID 32F1157 EVR3 DANFOSS 20 RF CON151 COND UNIT 1 5HP 230V 1 PHASE FJAM A150 CFV 007 404A 21 RF FLT376 FILTER DRYER 3 8 P H EKP 053S 22 RF COI9903...

Отзывы: