background image

CONTROL BODY MOUNTING

Select a location that will permit proper capillary routing. It is  
important not to twist or strain the control body as shifting of the 
calibration may result.
RANCO pressure controls can be mounted in any position, 

 

either vertically or horizontally, without affecting performance. The 
control can be mounted on an existing bracket, on the bracket 
provided, or can be flush-mounted without a bracket. Whichever 
method is selected, use only the mounting holes provided; no 
other holes are to be added to the control frame.

1. Secure the control to a bracket with the 10-32 x 3/16 
screws 
  by using the two tapped holes in the back of the control.  
 

If other mounting screws are used, they must not  

  protrude into the control more than 1/8” to avoid  
 damage.

2. When using the angle bracket, the control can be mounted to 
  the compressor or any flat surface by using two or more of 
  the four slotted holes in the base of the angle bracket.
3. When flush mounting the control, use the .20 inch holes in  
  the back of the control frame. Access can be gained by  
 

removing the front cover an securing 

  the control body to a wall or any flat surface. 

 

 

Mounting to an uneven surface may cause improper  

  control operation.

CAPILLARY CARE AND MOUNTING

Compressors vibrate. Copper work-hardens and fractures when 
flexed beyond its physical limits. Combine these two factors 
and broken capillaries can result. Breakage can be prevented by  
proper installation practices.

1. Minimizes the number of times the capillary is bent. Each 
  time it is rebent, it work-hardens making it more susceptible 
  to breakage.
2. Avoid sharp bends, kinks, strains or pinch marks in the  
  capillary. Never allow the capillary to rest against sharp  
  edges or rub against metal surfaces where it can be 

 

  damaged by friction.
3. The capillary should be straight within 4 inches of the 

 

  pressure connection so the pulsations do not work-harden 
  the capillary.
4. Purge all tubing and lines before connecting pressure 

 

 controls.
5. Route the capillary so that it will be safe-draining to minimize 

PREFERRED

H.P.

L.P.

No

Alternate

  oil logging.
6. When the control is mounted directly on the compressor, the 
  capillary must be secured to the compressor so that ever 
  thing moves together. If the capillary or control is shaking or  
  vibrating against the compressor vibration, work-hardening 

Plastic or
Rubber Lined
Clamp

Coils can be taped
or tied. See
notes 8, 9 & 10

Compressor

COMPRESSOR  MOUNTING

  of the capillary may occur, leading to eventual failure.
7. When the control body is mounted remote from the 

 

  compressor and the pressure connections are on the 

 

  compressor, vibration coils must be used between the 

 

  compressor and the mounted control. The coils should not 
  touch. A section of rubber pipe insulation inserted into  the 
  vibration coils and secured with silicone adhesive will keep 
  the coils separated, yet allow them to absorb vibration.

The capillary between the vibration coils and the control body 
should be secured to a stationary member when that distance 

3” to 6”

If this distance is more 
than 6”, the tubing 
should be clamped 
as shown below.

Min. of 2 Coils

2 to 3 Inch
Diameter Coils

12” to 18”

Control

Coils Should Not
Touch

Compressor

REMOTE  MOUNTING

exceeds 6 inches.
The capillary between the vibration coils and the control body 
should be secured to a stationary member when that distance 
exceeds 6 inches.

12” Approx

Min. of 2 Coils
2 to 3 Inch Dia. 
Coils

Clamp Tube to 
Stationary Member

2 or More Coils of Tubing On 
Compressor Side Clamp

Coils Should Not 
Touch

Compressor

Control

REMOTE  MOUNTING

2

Содержание O10

Страница 1: ...tomatic reset cycling version Manual reset versions of the O16 are available NO NO DIFF HIGH EVENT 3 12 0 10 20 30 40 50 0 1 2 3 35 25 15 5 2 1 PSI bar CLOSES ON PRESSURE RISE SWITCH LOW EVENT IS HIGH EVENT MINUS DIFF bar PSI DIFF HIGH EVENT 3 12 0 10 20 30 40 50 0 1 2 3 35 25 15 5 2 1 PSI bar CLOSES ON PRESSURE RISE SWITCH LOW EVENT IS HIGH EVENT MINUS DIFF bar PSI DIFF HIGH EVENT 3 12 0 10 20 30...

Страница 2: ...apillary to rest against sharp edges or rub against metal surfaces where it can be damaged by friction 3 The capillary should be straight within 4 inches of the pressure connection so the pulsations do not work harden the capillary 4 Purge all tubing and lines before connecting pressure controls 5 Route the capillary so that it will be safe draining to minimize PREFERRED H P L P No Alternate oil l...

Страница 3: ...ly for reference and the final set ting should be verified with a gauge set As a final check the system should be run through several cycles to assure proper settings and installation LOWEST EVENT DO NOT set the control below the lowest event On automatic reset controls if the combination of the Range R H pointer minus the Differential L H pointer is lower than the Low est Event the control will n...

Страница 4: ...allow the pressure to increase observing the high switch closing or opening Adjust the settings as necessary HIGH PRESSURE CHECK High pressure control settings can be checked by selectively dis connecting various stages of fans or by blocking the air flow on air cooled condensers On water cooled condensers reduce or shut off the water flow while observing the cut out and adjust as required CAUTION...

Отзывы: