DESCRIPTION/APPLICATION

RANCO commercial pressure controls are used for either 

 

operating or protecting commercial refrigeration or air 

 

conditioning systems. They are suitable for R12, R22, and R502 
refrigerants and are available with either male flare or capillary flare 
nut connections. Both low pressure (suction sensing) and high 
pressure (discharge sensing) versions are available.

These controls, with NEMA 1 enclosures and snap action switches, 
may be used in a variety of applications: direct control of motors 
or compressors; with a contactor for pilot duty control; to control 
solenoid valves. The electrical ratings inside the control cover must 
not be exceeded.

O10 Single pole, single throw (SPST)

close (cut-in) on rise

open (cut-out) on drop

O11 Single pole, single throw (SPST)

open (cut-out) on rise

close (cut-in) on drop

O16 Single pole, double throw (SPDT)

2-3 close on rise, open on drop
2-1 close on drop, open on rise

O20 Double pole, single throw (DPST)

close (cut-in) on rise

open (cut-out) on drop

3

2

1

L

L

T

T

DIFFERENTIAL 
ADJUSTMENT
SCREW
CW increases
CCW decreases
See p. 3

RANGE
ADJUSTMENT
SCREW
CW lowers
CCW raises
See p. 3

COVER
SCREW

All O series are available in the automatic reset/cycling version. 
Manual reset versions of the O16 are available.

NO!

NO!

DIFF

HIGH EVENT

3

12”

0

10

20

30

40

50

0

1

2

3

35

25

15

5

2

1

PSI.      bar

CLOSES ON PRESSURE RISE.

SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF

bar      PSI.

DIFF

HIGH EVENT

3

12”

0

10

20

30

40

50

0

1

2

3

35

25

15

5

2

1

PSI.      bar

CLOSES ON PRESSURE RISE.

SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF

bar      PSI.

DIFF

HIGH EVENT

3

12”

0

10

20

30

40

50

0

1

2

3

35

25

15

5

2

1

PSI.      bar

CLOSES ON PRESSURE RISE.

SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF

bar      PSI.

YES!

IMPORTANT NOTICE

MANUAL OPERATION (tripping switch)

The switch can be manually operated by lifting 

the bellows to tabs as shown. Operating the 

control at any other point WILL CAUSE  

CONTROL DAMAGE AND VOID THE  

WARRANTY.

DO NOT REMOVE the protective switch cover.

INSTALLATION

CAUTION:

To prevent possible electrical shock or equipment damage, 

 

disconnect electrical power to unit before and during installation. 
DO NOT restore electrical power to unit until the control is properly 
installed and grounded. DO NOT locate the control in an explosive 
atmosphere as a safety hazard can result due to possible spark 
generation in the control.

Controls are not to be located in areas of extreme moisture,  
dirt or dust, or in a corrosive or explosive atmosphere. These envi-
ronments can shorten control life.

1

INSTALLATION DATA

O10/011/O16/O20

SINGLE PRESSURE CONTROL

Содержание O10

Страница 1: ...tomatic reset cycling version Manual reset versions of the O16 are available NO NO DIFF HIGH EVENT 3 12 0 10 20 30 40 50 0 1 2 3 35 25 15 5 2 1 PSI bar CLOSES ON PRESSURE RISE SWITCH LOW EVENT IS HIGH EVENT MINUS DIFF bar PSI DIFF HIGH EVENT 3 12 0 10 20 30 40 50 0 1 2 3 35 25 15 5 2 1 PSI bar CLOSES ON PRESSURE RISE SWITCH LOW EVENT IS HIGH EVENT MINUS DIFF bar PSI DIFF HIGH EVENT 3 12 0 10 20 30...

Страница 2: ...apillary to rest against sharp edges or rub against metal surfaces where it can be damaged by friction 3 The capillary should be straight within 4 inches of the pressure connection so the pulsations do not work harden the capillary 4 Purge all tubing and lines before connecting pressure controls 5 Route the capillary so that it will be safe draining to minimize PREFERRED H P L P No Alternate oil l...

Страница 3: ...ly for reference and the final set ting should be verified with a gauge set As a final check the system should be run through several cycles to assure proper settings and installation LOWEST EVENT DO NOT set the control below the lowest event On automatic reset controls if the combination of the Range R H pointer minus the Differential L H pointer is lower than the Low est Event the control will n...

Страница 4: ...allow the pressure to increase observing the high switch closing or opening Adjust the settings as necessary HIGH PRESSURE CHECK High pressure control settings can be checked by selectively dis connecting various stages of fans or by blocking the air flow on air cooled condensers On water cooled condensers reduce or shut off the water flow while observing the cut out and adjust as required CAUTION...

Отзывы: