Figure 5: Dimensions (Inches)

CONTROL MOUNTING

Mount the ETC to a wall or any flat surface using a combination of any 

two or more of the slotted holes located on the back of the control 

case. The control’s components are not position sensitive, but should 

be mounted so that they can be easily wired and adjusted. Avoid  

excessive conditions of moisture, dirt, dust and corrosive atmosphere.

The ETC has provisions for 1/2 inch conduit connections. The conduit 

hub should be secured to the conduit before securing the hub to the 

plastic housing of the control. When using the conduit entry in the rear 

of the case, a standard plug should be inserted into the conduit hole 

in the bottom. Caution should be exercised not to damage the control 

circuit board or wiring when installing 

a conduit connector.

CAUTION

Read all of the information in these instructions before installing 

or operating the ETC control.
The schematic drawings and other information included in these 

installation  instructions  are  for  the  purpose  of  illustration  and 

general reference only.
ETC controls are not to be located in areas of significant moisture, 

dirt or dust as use of the control in such environment may cause 

personal injury or property damage and is likely to shorten the 

control life.
It is the responsibility of the installer and the user to assure 

that the application and use of the ETC control is in compliance 

with all applicable federal, state, and local laws, regulations and 

ordinances,  including,  without  any  limitation,  all  requirements 

imposed  under  the  National  Electric  Code  and  any  applicable 

building codes.

PRÉCAUTIONS 

Lire toutes les informations contenues dans ces instructions avant 

d’installer ou d’utiliser le contrôleur ETC.
Les schémas et toutes les autres informations figurant dans ces 

instructions d’installation sont indiqués à des fins d’illustration et 

de référence générale seulement.
Les  contrôleurs  ETC  ne  doivent  pas  être  placés  dans  des  zones 

ayant un taux d’humidité élevé, de la saleté ou de la poussière, 

car l’utilisation du contrôleur dans de tels environnements peut 

engendrer des blessures ou des dommages matériels et est 

susceptible de raccourcir la durée de vie du contrôleur.
Il  est  de  la  responsabilité  de  l’installateur  et  de  l’utilisateur  de 

s’assurer que l’installation et l’utilisation du contrôleur ETC soit 

faites en conformité avec tous les règlements, lois, et ordonnances 

fédéraux,  provinciaux,  et  locaux,  y  compris,  sans  y  être  limité, 

toutes les exigences imposées par la National Electric Code ainsi 

que tous les codes du bâtiment, en vigueur.

ANTI-SHORT CYCLE COMPRESSOR DELAY

When the unit is configured for cooling and there is a call for cooling, 

the relay will not activate until the Anti-short Cycle Compressor 

Delay is satisfied. During an Anti-short Cycle Compressor Delay, the 

temperature will alternate with Cd to indicate the Relay On is delayed.
If Relay 1 is in Anti-short Cycle Compressor Delay, the temperature will 

alternate with aCd or S1 icon. If Relay 2 is in Anti-short Cycle Compressor 

Delay mode, the temperature will alternate with a Cd or S2 icon. 

Содержание ETC Series

Страница 1: ...y Electrical Ratings NO Contact 120V 208 240V Full load amps 9 8 Amps 4 9 Amps Locked rotor amps 58 8 Amps 29 4 Amps Resistive amps 9 8 Amps 4 9 Amps Horsepower 1 2 HP 1 2 HP NC Contact Full load amps 5 8 Amps 2 9 Amps Locked rotor amps 34 8 Amps 17 4 Amps Resistive amps 5 8 Amps 2 9 Amps Horsepower 1 4 HP 1 4 HP Pilot Duty 125 VA at 120 208 240 VAC Control Ambient Temperature Operating 20 F to 14...

Страница 2: ...s the SET key again to access the stage 1 cooling or heating mode The LCD will display the current mode either C1 for cooling or H1 for heating Then press either the up Ç or down È key to toggle between the C1 or H1 designation Step 5 Press the SET key again to access the Anti short Cycle Compressor Delay when in Cooling Mode Press the up Ç or down È keys to set the delay from 1 to 20 minutes Pres...

Страница 3: ...trôleur ETC NE PAS rétablir l alimentation élec trique de l appareil avant que le contrôleur ETC ne soit correctement installé et que le couvercle ne soit assemblé Risque d incendie Ne pas placer le contrôleur ETC dans une atmosphère explosive car un incendie pourrait être déclenché par d éventuelles étincelles survenant dans le contrôleur Toutes les commandes de l ETC sont conçues pour contrôler ...

Страница 4: ...regulations and ordinances including without any limitation all requirements imposed under the National Electric Code and any applicable building codes PRÉCAUTIONS Lire toutes les informations contenues dans ces instructions avant d installer ou d utiliser le contrôleur ETC Les schémas et toutes les autres informations figurant dans ces instructions d installation sont indiqués à des fins d illust...

Страница 5: ... representation of the sensor temperature with 0 volts 30 F and 10 volts 220 F See figure 8 for wiring information and Figure 5 for location of the entry hole The reference for this output is designated by the symbol on the wiring diagram The output signal is designated by the symbol Figure 8 0 10 V Analog Output Located on Power Lower Circuit Board Figure 7 Typical Wiring Diagram for 24 VAC Power...

Страница 6: ... a problem check sensor resistance to determine if sensor or control is at fault 4 To check sensor resistance disconnect sensor and measure the resistance across the leads while measuring temperature at the sensor SENSOR REPLACEMENT Figure 9 Sensor replacement on Display Upper Circuit Board Sensor Replacement ETC models are available with Quick Connect Sensor feature that allows for easy sensor re...