4
In order for the stove to work and draw properly, sufficient air is important! Be especially
aware of any mechanical fans (e.g. kitchen or bathroom) that may affect the proper draw.
In addition, make sure that the floor and sub-flooring is designed to carry the extra weight
of the stove.
The floor in front of the insert (if placed lower than 5” above ground) must be thermal
protected by a minimum of ½” (1cm) non-combustible material having a thermal
conductivity of k=0.84, where k=BTU in./hr. ft
2
°F (based on 1” thickness). To substitute
alternate material, you need to know the k value of that material. The formula to calculate
thickness in inches is (k of the alternate material / 0.84) x ½”.
When installing the insert, the heat distribution to other rooms should be taken into
consideration. The RAIS 60 Inserts have a heating capacity of approximately 1,076 ft²
(100m²) based on a standard ceiling height.
Specifications
UL 1777 Listed 6” (15cm) diameter chimney liner up through the block off plate of an
existing masonry chimney, a zero-clearance chimney, or Class A, UL-103 HT, 6” (15cm)
diameter chimney. In Canada, a full length chimney liner is required.
Optimal Thermal Output – 23,900 BTU
(7 kW);
range is 10,200 - 27,300 BTU (3 - 8 kW)
Minimum stove draft pressure at above output –
0.06” WC (15 Pascals)
Efficiency – 67% based on DS standard testing
Tested EPA emission particulate rate – 7.23 grams/hour
Minimum distances from edge of Insert Face Plate to combustible material – as shown:
A = Distance to a combustible
adjacent sidewall – 12”
(30cm)
B = Distance to a combustible
mantel – 16” (41cm)
C = Distance to ¾” protruding
combustible top trim – 14”
(36cm)
D = Distance to ¾” protruding
side trim – 2” (5cm)
E = Side floor protection – 8”
(20cm) from the fuel-loading door
F = Distance to furniture – 36” (91cm)
G = Front protection – 20” (51cm) to unprotected combustible floor
B C
D
A F
E G