To install sensor in tee

 

1)  Apply a small amount of silicone grease to O-rings on sensor insert and chamfer on inside lip of tee.  Clean 

off any grease which could be deposited on the impeller.

 

2)  Align flow arrow on sensor with direction of flow.

 

3)  Carefully press sensor straight into tee. 

Caution: Impeller may strike sides of venturi cavity in tee if 

misaligned, causing damage to impeller or shaft.

 

4)  Install clevis pin through the tee, sensor, and conduit cap, and install split ring.

 

5)  Before pressurizing pipe, verify that:

 

• All threaded connections are tight.

 

• The flow direction arrows on the tee and sensor are aligned with the flow direction.

 

• The clevis pin and cotter ring are installed.

 

 

Mechanical Installation for Insert Sensors

 

The insertion depth and alignment of the sensor assembly are critical to the accuracy of the flow measurement. 
The Flat End of the sensor tube assembly MUST BE INSTALLED 1-1/2" from the inside wall of the pipe. In order 
to allow for variations in wall thickness, lining or coatings, the depth adjustment is controlled by the position of 
t h e  Hex Nuts on the three (3) threaded studs of the Hex Mounting Adapter. The Hex Mounting Adapter is 
provided with a 2" Male NPT connection.

 

There are two methods of mounting these Rain Bird sensors in a 

3” or larger pipe. One for PVC pipe uses a 2” 

NPT threaded pipe saddle. The other, for steel pipe, uses a welded-on fitting such as a Thredolet

®

, also tapped 

for a 

2” NPT connection.  In either case, cut a 2” hole through a depressurized pipe and then secure the saddle 

or welded fitting to the pipe. 

Note: Do not use a threaded outlet tee, the inside dimension of the tee is not 

the same as the pipe O.D. 

Install the 

2” NPT adapter provided, using a thread sealant to prevent leakage.

 

Tighten as necessary. Rain Bird insert style sensors are calibrated with the sensor inserted 1 

1/2” into the pipe 

flow.

 

To determine the proper insertion depth, proceed as follows:

 

1) 

Apply Anti-Seize thread lubricant, supplied with the sensor, to the threaded studs of the mounting 
adaptor.

 

 

2)  Determine the height to the upper adjusting nuts on the three 

1/4” studs using the insertion depth gauge 

contained in the RBIK Installation Kit. Set them at 3 3/4" above the inside wall of the pipe.

 

 

3)  Clean O-Rings and flow sensor sleeve, and lightly lubricate O-Rings with silicone grease from the packet 

provided or some other acceptable lubricant.  Take care not to get grease on the impeller or bearing.

 

 

4)  Insert the flow sensor into the 

2” NPT adapter so that the mounting holes in the positioning collar fit over the 

studs on the adapter.  Lower the sensor onto the previously adjusted nuts.  Install the lock nuts on top of the 
positioning collar and tighten.  Now tighten the lower jam

 

nuts firmly against the upper adjusting nuts to secure 
them for future removal of the sensor for inspection or 
service.

 

 

Alignment of Flow Sensor

 

1)  Loosen positioning collar set screws with a 

3/32” Allen 

wrench.  Place the alignment rod through the sight holes 
in the flow sensor.  Refer to Figure 2.  Using the 
alignment rod as a guide, align the flow sensor so that 
the flow label arrow matches pipe flow direction and so 
that the alignment rod is exactly parallel to the pipe. 
This  procedure aligns the impeller directly into the fluid 
flow.

 

As a backup to the flow arrow label, there is a small hole 
next to the larger sighting hole of the upstream side.

 

 

Figure 1

 

Installation of FS350B and FS350SS

 

 

 

 

            

 

 
 

            

 

 
 

            

 

¾” 

Содержание FS200B

Страница 1: ...wept impeller shape provides higher more constant torque than other impeller designs and is less prone to fouling by water borne debris The forward curved shape coupled with the absence of magnetic dr...

Страница 2: ...nics package inserted into a proprietary cast bronze pipe tee with threaded NPT female iron pipe thread FIPT connections They are available in the following sizes and thread types Model Thread Size FS...

Страница 3: ...ertical pipes 3 Small pipe PVC and Bronze Tee Type sensors are Factory Set but for insert sensors the Insertion depth should be set to 1 1 2 for accurate flow readings The following pages show methods...

Страница 4: ...tlet tee the inside dimension of the tee is not the same as the pipe O D Install the 2 NPT adapter provided using a thread sealant to prevent leakage Tighten as necessary Rain Bird insert style sensor...

Страница 5: ...n data transmission to connect the sensor to the transmitter monitor or controller 3 Make a water tight splice Direct burial silicone grease splices are recommended Rain Bird DBRY20 or 3M DBR Y 6 Two...

Страница 6: ...000 5 4 to 54 20 to 200 1 2 to 12 FS075P 3 4 PVC Tee Flow Sensor 0 1563 0 9000 3 3 to 33 13 to 125 75 to 7 5 FS050P 1 2 PVC Tee Flow Sensor 0 0780 0 9000 1 9 to 19 7 to 70 43 to 4 3 Description of Col...

Страница 7: ...80 2 500 Sch 20 8 625 8 125 41 653 0 283 80 2 500 Sch 30 8 625 8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80...

Страница 8: ...h 30 20 00 19 000 239 666 0 547 400 12 000 Sch 80 20 00 17 938 213 14 0 511 400 12 000 22 Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sc...

Страница 9: ...necessary 7 Refer to Figure 3 To reinstall position the impeller in the cavity oriented as in Step 4 so that the impeller blades point into the flow direction and toward the small alignment hole locat...

Страница 10: ...7 VDC in a No Flow situation or less than 3 VDC in a flow situation disconnect the sensor from the barrier strip and measure the voltage at the sensor input terminals of the barrier strip again It sh...

Страница 11: ...r recommended design flow range for FS100B Linearity 0 2 of full scale over recommended design flow range 0 7 of full scale over recommended design flow range for FS100B Transducer Excitation Typicall...

Отзывы: