MMU2-1600GE series Operations Manual Rev Apr 2020                Page 

10

 of 51 

Modifying Inputs

:  

Red Enable

: All red fail testing will be disabled when this input is below 70V

RMS

Load Switch Flash bit (bit 112) of the Type 0 Frame

: All red fail testing will be disabled when this bit is set to 

one. 

Feature Interactions

Per Channel Red Enables

: When Co-Channel / Per Channel Red Enables are enabled only channels that have 

been programmed as active for this feature will be included in the displays checked for red fail. 

LED Thresholds

: When LED Thresholds is enabled the Greens, Yellows, Reds, and Walks are sensed as ON 

when their voltage is above 70V

RMS

 and OFF when below 50V

RMS

 for the red fail test. 

Flashing Greens (also known as Canadian Fast Flash)

: When Flashing Greens are enabled the timer 

thresholds are changed from 800 milliseconds to 1500 milliseconds for fault detection and from 300 
milliseconds to 200 milliseconds for the reset of the fault timer. 

PPLT5

: The Green of the child channel will be included in the red fail test for that channel.  If Co-Channel 

Includes Yellow is also enabled then the Green and Yellow of the child channel will be included in the red fail 
test for the channel with the Green ball (Parent). 

Flashing Yellow Arrow Left Turns

:  A FYA signal is a logical combination of 4 indications.  If the any of the 

indications is off for 800ms then a red fail is indicated.  

If FYA GREEN SOLO is selected and IGNORE UNUSED CHAN is YES the unused Red and Yellow signals 
of the FYA parent channel are ignored for red fail. 

If FYA SOLO is selected, the channel must have both RED ENABLE and FIELD CHECK/DUAL 
INDICATION OFF, no MYCD jumper, and is not selected as a pedestrian channel then the unused indication 
(Green or Yellow) of the FYA channel is ignored for red failure. 

2.5.3

 

DUAL INDICATION MONITORING 

Configuration:

 All channels with a setting of “Y” for Dual Indication / Field Check will be monitored for the dual 

indication fault.  The testing defaults for this feature are all channels enabled for dual indication testing. 

Test Preformed:

 When operating in the Type 12 mode the following dual indications are checked for:  

Red, Green  + Red, Green + Yellow, and Walk + Yellow.  When operating in the Type 16 mode the following dual 
indications are checked for:  Red, Green + Red, and Green + Yellow.  When a channel has multiple 
displays active a dual indication timer is started.  If one of the indications turns off the dual indication timer is 
stopped (it is not cleared) and a single indication timer is started.  If both of the indications turn  off the dual 
indication timer is stopped (it is not cleared) and a no indication timer is started.  If the dual indication condition 
returns the single indication and no indication timers are stopped (not cleared) and the dual indication timer 
continues timing from its prior value.  If the dual indication timer reaches 600 milliseconds or more the monitor 
will latch a dual indication fault.  If the single indication timer reaches 1000 milliseconds the dual indication timer, 
the single indication timer, and the no indication timer are reset to zero and the dual indication is ignored.  If the no 
indication timer reaches 300 milliseconds the dual indication timer, the single indication timer, and the no 
indication timer are reset to zero and the dual indication is ignored.  The normal voltage thresholds for this test are: 
Reds  –  ON when above 70V

RMS

  and OFF when below 50V

RMS

, Greens / Yellows / Walks –  ON when above 

25V

RMS

 and OFF when below 15V

RMS

.

 

Fault Action:

  The monitor transfers the Output relay contacts to the fault condition (continuity between the 

Normally Open and Common contacts), illuminates the 

DUAL IND

 indicator on the front panel, and sets the Spare 

Bit #2 bit (bit 68) of the Type 129 Frame to 1.  The Signal Sequence log and the Prior Faults log will record this 
fault. 

Resetting the Fault:

 The monitor remains in this fault condition until the unit is reset by the activation of the front 

panel reset pushbutton or the activation of the reset input.  Power loss or power interruption will not reset this fault.  
The Reset log will record the resetting of this fault. 

Modifying Inputs: 

Red Enable

: All dual indication testing will be disabled when this input is below 70V

RMS

Load Switch Flash bit (bit 112) of the Type 0 Frame

: All dual indication testing will be disabled when this bit 

is set to one. 

Feature Interactions: 

Field Check

: Enabling dual indication monitoring will also enable field check monitoring.

 

Содержание MMU2-1600G Series

Страница 1: ...1600GE series Malfunction Management Unit pn 889 3819 00 Revision April 2020 MMU2 1600G series Malfunction Management Unit Firmware Version 02 00 05 Operations Manual NEMA TS 2 Amendment 4 2012 Malfun...

Страница 2: ......

Страница 3: ......

Страница 4: ...BLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC ARE UNDER COPYRIGHT MAINTENANCE NOTE IT IS AN E...

Страница 5: ......

Страница 6: ...bility 6 2 3 2 Minimum Flash 6 2 3 3 Minimum Yellow Change Channel Disable 6 2 3 4 Voltage Monitor Latch 6 2 3 5 Serial EEPROM 6 2 4 FEATURES 6 2 4 1 Monitor Power Failure 6 2 4 2 Minimum Flashing Ind...

Страница 7: ...g Field Changes 20 2 7 7 2 Log Local Flash Events 20 2 7 7 3 Log CVM Events 20 2 8 Diagnostics 20 2 8 1 Memory 21 2 8 2 Microprocessor Monitor 21 2 8 3 Internal Voltage Monitors 21 2 8 4 Diagnostic Co...

Страница 8: ...4 Other AC and Miscellaneous Inputs 46 4 6 5 5 DC Inputs 46 4 6 6 Diagnostic Info 46 4 6 6 1 LED Test Settings 46 4 6 6 2 Screen Test 46 4 6 6 3 Fault Codes 46 4 6 6 4 Diagnostic SDLC Frames Menu 46 4...

Страница 9: ......

Страница 10: ...ovide downward compatibility with a 12 channel conflict monitor unit CMU conforming to TS 1 1989 The signal monitor portion of the monitor is capable of checking for the presence of voltage on conflic...

Страница 11: ...Series is comprised of the following monitors Model MMU2 1600G Reno USA For applications calling for a NEMA TS 2 2003 compliant Malfunction Management Unit with integral graphics display Model MMU2 16...

Страница 12: ...The LED thresholds are more restrictive than the standard thresholds Therefore you will not miss a fault using the LED thresholds that would have been detected using the standard thresholds In the Sta...

Страница 13: ...troller Voltage Monitor input Connector A Pin V is a logic level input This input must stay in a low state nominal 0 volts for normal signal operation When high or floating the monitor will be in the...

Страница 14: ...9 Frame to 1 At all other times the Start Up Flash Call bit of the Type 129 Frame is set to 0 Typical Connection One set of contacts is used to control the flash transfer relays the other is usually u...

Страница 15: ...tored in the serial EEPROM is used 2 4 FEATURES 2 4 1 MONITOR POWER FAILURE The monitor responds to a Power Failure by entering a non latching flash state The monitor responds to a Power Failure wheth...

Страница 16: ...ort does not support handshaking signals Both the COM port and the optional Ethernet port can be used at the same time See Section 3 4 for connector pin assignments 2 4 6 ETHERNET PORT The monitor has...

Страница 17: ...ng configuration settings are monitored Programming Card jumpers Type Select input Factory Options Dual Indication Field Check Per Channel Red Enables Flashing Don t Walk Monitoring Flashing Yellow Ar...

Страница 18: ...ram card settings of the parent channel If ALLOW CONCURRENT YEL is YES then the yellow following a FYA will not conflict with the opposing thru yellow If IGNORE YEL TRAP is YES then the Yellow of the...

Страница 19: ...d for Yellow Red Green Red Green Yellow and Walk Yellow When operating in the Type 16 mode the following dual indications are checked for Yellow Red Green Red and Green Yellow When a channel has multi...

Страница 20: ...nds or more the monitor will latch a dual indication fault If the single indication timer reaches 1000 milliseconds the dual indication timer the single indication timer and the no indication timer ar...

Страница 21: ...RT CLEARANCE MONITORING Configuration All channels will be monitored for a short clearance fault Test Preformed When a channel has a Green or Walk that turns off a conflict channel cannot display a Gr...

Страница 22: ...Co Channel Per Channel Red Enables are enabled only channels that have been programmed with a Per Channel Red Enable setting of Y will be included in the channels checked for a field check fault Flas...

Страница 23: ...ed A voltage greater than 22VDC applied to the 24 Volt Monitor II input is recognized as adequate for proper operation A voltage of less than 18VDC is recognized as inadequate for proper operation Whe...

Страница 24: ...s to the fault condition continuity between the Normally Open and Common contacts illuminates the LOC FLASH indicator on the front panel and sets the Local Flash bit bit 79 of the Type 129 Frame to 1...

Страница 25: ...a flashing Red input is never checked for conflicts 2 6 2 PPLT5 MONITORING Configuration The setting of Co Channel Per Channel Red Enables determines if this feature is active All channels with a set...

Страница 26: ...yellow If IGNORE YEL TRAP is YES then the Yellow of the FYA channel can be on with the opposing thru green indication following a flashing yellow arrow If GREEN SOLO is selected and IGNORE UNUSED CHA...

Страница 27: ...RED ENABLE input is not active The testing defaults for this feature are all Per Channel Red Enables enabled and Co Channel Per Channel Red Enables set to no Tests Modified Red Fail Normal red fail te...

Страница 28: ...is changed from 800 milliseconds to 1 5 seconds Red Fail Reset time is changed from 300 milliseconds to 200 milliseconds Dual Indication Green Yellow Dual Indication Reset time is changed from 300 mi...

Страница 29: ...and Walks RMS Voltages of all Greens Yellows Reds and Walks Status of all DC inputs Status of Red Enable AC Line Voltage Red Enable Voltage and DC Input Voltages Time Mode The Signal Sequence Log reco...

Страница 30: ...aults will not be logged by the monitor as any one of these voltages being invalid will immediately place the monitor in a diagnostic failure mode with the microprocessor held in reset This prevents a...

Страница 31: ...nominal AC VOLTAGE INPUTS NORMAL THRESHOLDS Green Signal Inputs OFF 15 VRMS ON 25 VRMS Walk Signal Inputs OFF 15 VRMS ON 25 VRMS Yellow Signal Inputs OFF 15 VRMS ON 25 VRMS Red Signal Inputs OFF 50 V...

Страница 32: ...c Detect 1000 msec Typical 800 msec CVM FAULT No Fault 125 msec Detect 175 msec Typical 150 msec 24 VDC MONITOR No Fault 125 msec Detect 175 msec Typical 150 msec CLEARANCE FAIL No Fault 2 8 sec Detec...

Страница 33: ...12 Only I Channel 10 Walk I b Channel 10 Yellow I Channel 10 Yellow I c Channel 9 Yellow I Channel 9 Yellow I d Channel 8 Yellow I Channel 8 Yellow I e Channel 7 Yellow I Channel 7 Yellow I f Channel...

Страница 34: ...Type 16 Only I U Start Delay Relay N C Open During Start Delay O Start Delay Relay N C Open During Start Delay O V Channel 10 Red I Channel 10 Red I W Channel 14 Red I Channel 14 Red Type 16 Only I X...

Страница 35: ...erved 20 5 9 5 10 5 11 20 Reserved Reserved Reserved 21 5 12 5 13 5 14 21 Minimum Flash b8 Minimum Flash b4 Minimum Flash b2 22 5 15 5 16 6 7 22 Minimum Flash b1 24V Latch Enable CVM Latch Enable 23 6...

Страница 36: ...EDs ON Fault Blip Fault Disabled Fuse 1 4 Amp Slo Blo Connector B Channel Red Inputs Red Enable Start Delay Relay Local Flash 24V Monitor II Connector A Channel Green Yellow and Walk Inputs Output Rel...

Страница 37: ...rrent To Pending Compare Config To Current Compare Config To Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log C...

Страница 38: ...is button will display the Configuration Shortcuts menu Right Pushbutton The pushbutton labeled is used to navigate through menu selections or settings being viewed If the setting being viewed can be...

Страница 39: ...r five seconds until the monitor gives five quick confirmation beeps or navigate to the Fault Monitoring Menu and select Save Changes 4 4 4 UPGRADE PENDING When new firmware has been downloaded in to...

Страница 40: ...ious display LOCATION This text field is 40 characters long The user can edit this field This field is typically used to store the intersection that the monitor is installed at example VIRGINIA AVE LO...

Страница 41: ...his monitor to the factory defaults WIZARD Access the configuration wizard that can be used to automatically configure most settings in the monitor 4 6 2 1 1 START CONFIGURATION Before a change can be...

Страница 42: ...gs LOGGING View and or modify the logging settings OTHERS View and or modify other miscellaneous settings 4 6 2 1 7 1 PROGRAMMING CARD MENU MENU TEXT MENU FUNCTION PER CHANNEL PERMISSIVES View the per...

Страница 43: ...tor will only perform Red Fail and Field Check monitoring for channels that have been enabled for this feature when the Red Enable input is active Only the Red Fail and Field Check monitoring are affe...

Страница 44: ...Yellow and Red drivers of the Parent Channel are ignored for conflict dual indication short clearance and short yellow monitoring If No is selected the Yellow and Red signal indications are monitored...

Страница 45: ...tion 2 7 7 3 for more information The factory default for this feature is YES 4 6 2 1 7 9 OTHERS MISCELLANEOUS LOCATION SETTINGS Use the up or down pushbutton to navigate between the settings Use the...

Страница 46: ...T This left turn is a standard protected left turn movement This is the default left turn type MMU2 Allows the selection of sixteen FYA configurations types A thru P This includes the eight Flashing Y...

Страница 47: ...s This is important because the MMU2 has a limited number of channels Type A B C and D require 1 channel for each protected left turns 1 3 5 7 and 4 channels for the 4 FYAs The MMU2 uses 16 channels t...

Страница 48: ...and 16G Type G and H require 1 channel for each protected left turn 1 3 5 7 and the Ped Yellow for the FYA The Controller Unit must be able to use the Ped Yellow as a FYA FYA Type G has the Peds on c...

Страница 49: ...plays the opposing Ped Yellows on channels 13G 14G 15G and 16G Type K and L require 1 channel for each protected left turns 1 3 5 7 and 4 channels for the 4 FYAs Type K assigns the Green of channels 9...

Страница 50: ...LT4 This left turn uses a five section head with a Green arrow Green ball Yellow ball and a Red ball If this type is selected other setting will be displayed FYA allows the selection of the channels w...

Страница 51: ...98V to 135V in one volt increments The recovery voltage is automatically set to three volts lower than the alarm voltage The factory default for this setting is 130V LOW VOLTAGE The AC low voltage ala...

Страница 52: ...guration changes COMPARE CONFIG TO CURRENT View the differences between any previous configuration and the current configuration COMPARE CONFIG TO PRIOR View the differences between any previous confi...

Страница 53: ...e Red Enable Voltage and DC Input Voltages are recorded This display is view only The display consists of a voltage section two status sections and a single line footer showing the Fault Type and the...

Страница 54: ...ghlighted setting Press the ENTER pushbutton to accept and store the modified Daylight Saving Time Ahead settings Press the ESCAPE pushbutton to exit 4 6 4 4 VIEW UP TIME The MMU 1600G warranty covera...

Страница 55: ...NOTE In most instances once the LED Test has been completed the function should be turned OFF If the LED Test has been left ON repeat the procedure outlined above or press the RESET pushbutton to turn...

Страница 56: ...r of breaks received BREAKS number of parity errors received PARITY number of frames received with a checksum error CHKSUM number of start of frame errors SOF and number of end of frame errors EOF Thi...

Страница 57: ...C line voltage is above 98VRMS When the AC line voltage is below 89VRMS the indicator will flash at a 1 Hz rate to indicate low line voltage While the AC line voltage is low all field status indicator...

Страница 58: ...through the RaeComM software or via the front panel See Section 4 6 2 1 7 9 4 8 1 CRITICAL FAILURE When the monitor main microprocessor is held in the reset state due to a critical hardware failure th...

Страница 59: ...A E web site www renoae com 3 Connect the monitor to the computer through the COMM PORT or ETHERNET 10 100 port on the MMU 1600GE 4 Start the RaeComM program 5 Ensure that the RaeComM software can com...

Страница 60: ...ompare Config To Current Compare Config To Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log C...

Отзывы: