1.0  SYSTEM DESIGN CONSIDERATIONS

 

 

1.1  INTRODUCTION 

 

The GP/XP/XR Series Radon Fans are intended for use by trained, professional Radon mitigators.  

The purpose of this instruction is to provide additional guidance for the most effective use of a fan.  

This instruction should be considered as a supplement to EPA standard practices, state and local 

building codes and state regulations.  In the event of a conflict, those codes, practices and 

regulations take precedence over this instruction. 

 

1.2  ENVIRONMENTALS 

 

The GP/XP/XR Series Fans are designed to perform year-round in all but the harshest climates 

without additional concern for temperature or weather.  For installations in an area of severe cold 

weather, please contact RadonAway for assistance.  When not in operation, the fan should be stored 

in an area where the temperature is never less than 32 degrees F. or more than 100 degrees F. 

 

1.3  ACOUSTICS 

 

The GP/XP/XR Series Fan, when installed properly, operates with little or no noticeable noise to 

the building occupants.  The velocity of the outgoing air should be considered in the overall system 

design.  In some cases the "rushing" sound of the outlet air may be disturbing.  In these instances, 

the use of a RadonAway Exhaust Muffler is recommended. 

 

1.4  GROUND WATER 

 

In the event that a temporary high water table results in water at or above slab level, water may be 

drawn into the riser pipes thus blocking air flow to the GP/XP/XR Series Fan.  The lack of cooling 

air may result in the fan cycling on and off as the internal temperature rises above the thermal 

cutoff and falls upon shutoff.  Should this condition arise, it is recommended that the fan be turned 

off until the water recedes allowing for return to normal operation. 

 

1.5  SLAB COVERAGE 

 

The GP/XP/XR Series Fan can provide coverage up to 2000+ sq. ft. per slab penetration.  This will 

primarily depend on the sub-slab material in any particular installation.  In general, the tighter the 

material, the smaller the area covered per penetration. Appropriate selection of the GP/XP/XR 

Series Fan best suited for the sub-slab material can improve the slab coverage.  The GP & XP Series 

have a wide range of models to choose from to cover a wide range of subslab material.  The higher 

static suction fans are generally used for tighter subslab materials.  The XR Series is specifically 

designed for high flow applications such as stone/gravel and drain tile.  Additional suction points 

can be added as required.  It is recommended that a small pit (5 to 10 gallons in size) be created 

below the slab at each suction hole. 

 

 

 

 

 

Содержание XP101

Страница 1: ...o open Return unit to the factory for service 6 All wiring must be performed in accordance with the National Fire Protection Association s NFPA National Electrical Code Standard 70 current edition for all commercial and industrial work and state and local building codes All wiring must be performed by a qualified and licensed electrician 7 WARNING Do not leave fan unit installed on system piping w...

Страница 2: ... considered in the overall system design In some cases the rushing sound of the outlet air may be disturbing In these instances the use of a RadonAway Exhaust Muffler is recommended 1 4 GROUND WATER In the event that a temporary high water table results in water at or above slab level water may be drawn into the riser pipes thus blocking air flow to the GP XP XR Series Fan The lack of cooling air ...

Страница 3: ... 90 CFM For more precision determine flow rate by using the chart in the addendum Under some circumstances in an outdoor installation a condensate bypass should be installed in the outlet ducting as shown This may be particularly true in cold climate installations which require long lengths of outlet ducting or where the outlet ducting is likely to produce large amounts of condensation because of ...

Страница 4: ...or electrical boxes are outdoor rated and properly sealed to prevent water penetration into the box A means such as a weep hole is recommended to drain the box 1 9 SPEED CONTROLS The GP XP XR Series Fans are rated for use with electronic speed controls however they are generally not recommended If used the speed control recommended is Pass Seymour Solid State Speed Control Cat No 94601 I 2 0 INSTA...

Страница 5: ...solation 2 4 ELECTRICAL CONNECTION Connect wiring with wire nuts provided observing proper connections See Section 1 8 2 5 VENT MUFFLER optional Install the muffler assembly in the selected location in the outlet ducting Solvent weld all connections The muffler is normally installed at the end of the vent pipe 2 6 OPERATION CHECKS _____ Verify all connections are tight and leak free _____ Insure t...

Страница 6: ...peration Reduce by 10 for High Temperature Operation Reduce by 4 per 1000 feet of altitude Power Consumption 120 VAC XP101 40 49 watts XP151 45 60 watts XP201 45 66 watts XR261 65 105 watts XP Series Inlet Outlet 4 5 OD 4 0 PVC Sched 40 size compatible XR Series Inlet Outlet 5 875 OD Mounting Mount on the duct pipe or with optional mounting bracket Recommended ducting 3 or 4 Schedule 20 40 PVC Pip...

Страница 7: ...ation Reduce by 10 for High Temperature Operation Reduce by 4 per 1000 feet of altitude Power Consumption 120 VAC GP501 70 140 watts GP401 60 110 watts GP301 55 90 watts GP201 40 60 watts Inlet Outlet 3 5 OD 3 0 PVC Sched 40 size compatible Mounting Fan may be mounted on the duct pipe or with integral flanges Weight 12 lbs Size 13H x 12 5 x 12 5 Recommended ducting 3 or 4 Schedule 20 40 PVC Pipe S...

Страница 8: ...donAway 5 YEAR EXTENDEDWARRANTY WITH PROFESSIONAL INSTALLATION RadonAway will extend the Warranty Term of the fan to 5 years from date of manufacture if the Fan is installed in a professionally designed and professionally installed radon system or installed as a replacement fan in a professionally designed and professionally installed radon system Proof of purchase and or proof of professional ins...

Отзывы: