Keyswitch Operation

Shorting and restoring the point sensor loop toggles the
system On and Off. All faulted points are bypassed. See
POINT CODES in the D2212 Program Entry Guide.

Silencing the Bell

To silence the bell (stop Alarm output) if the system is On (or
Part On), operate the keyswitch to turn the system Off. If the
area is Off, operating the keyswitch only silences the bell. It
does not turn the system On.

Easikey

You can use a Radionics Easikey access system to turn the
system Off. Program the 

Keyswitch prompt to Easikey (see

the 

D2212 Program Entry Guide for instructions). You must

use a 12VDC option for the Easikey installation. See the
Easikey Installation and Operation Instructions. Easikey is
not for use in UL installations.

Connect the Easikey door controller to the panel using a
D133/D134 Relay Module as shown in Figure 13. Make
certain to connect the common for the Easikey's 12VDC
power supply to terminal 10 on the panel.

Points

Point Parameters

On-Board Point 1

Point 1 is a powered sensor loop. Review the Radionics
Technogram: Smoke Detectors Compatible with the D2212
(73-07358-000) for a list of compatible detectors.

Point 1 is supervised with a 2.0K EOL resistor. The voltage
range for two-wire smoke detectors is 10.2 to 13.9 VDC.

Points 2 to 6

Points 2 to 6 are supervised with 1.0K EOL resistors.

Open Loop = Greater than 8.9 VDC, but less than

13.9 VDC.

Normal Loop = Greater than 2.5 VDC, but less than

8.5 VDC.

Shorted Loop = Greater than 0.0 VDC, but less than

2.0 VDC.

Points 7 and 8

Points 7 and 8 are 

not supervised with EOL resistors.

Open Loop = Greater than 2.4 VDC, but less than

13.9 VDC.

Normal (Closed) Loop = Greater than 0.0 VDC, but

less than 1.4 VDC.

Point Response Time

The panel scans point sensor loops every 500 milliseconds.
A point must be faulted for 2 scans (one second) before the
panel initiates an alarm.

Keyswitch

Description

You can connect a momentary contact arming station
(keyswitch) to turn the D2212 on and off. Connect the
keyswitch to any point sensor loop (except points 7 and 8).

You can use the external relay outputs and D133/D134
Relay Modules to activate arming status lights for keyswitch
arming stations. See the 

Relays section in the D2212

Program Entry Guide.

Programming

See 

POINT CODES in the D2212 Program Entry Guide for

the correct programming for points used for keyswitches.

Installation

Connect the end-of-line resistor for the point at the keyswitch
so that the switch shorts the resistor when it operates. An
open on the circuit produces an alarm if the area is armed
and a trouble if it is disarmed. See Figure 12.

Figure 13: Easikey

Figure 12: Keyswitch

Short and restoral
on circuit toggles
arming state.

COMMON

POINT INPUT

End of Line

Resistor

N/O 1

COMM 1

N/C 1

X1 -

X1 +

D133

Relay Module

Connect to any supervised
point programmed for
Keyswitch (Digit 1 = A, see
D2812 Program Entry Guide).

Shorting and restoring point
turns system OFF.

End of Line Resistor

+

-

EasiKey Control

To 12VDC, Switched

parallel to door strike.

P2

15

16

17

20

21

19

18

10

14

13

11

12

Connect the common for the Easikey's 12 VDC
supply to the terminal labeled Aux- on the panel.

www.PDF-Zoo.com

firealarmresources.com

Содержание D2212

Страница 1: ...74 07361 000 C 11 11 96 1995 1996 Radionics D2212 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone line Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 Contact the telephone comp...

Страница 3: ...es the following D222 Text Keypad with Point Expansion 4 points Installation Sheet 74 07362 000 User s Reference Card 71 04523 010 Security System User s Guide 71 07374 000 Getting Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Six wire point cable assembly 15 07251 000 Four 1k Ω end of line resistors 30 01098 102 Table of Contents Introduction 3 D2212 Cont...

Страница 4: ...ing Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Battery Order a D126 Battery 12 V 7 0Ah to complete a basic D2212 installation Enclosure Options The D2212 is shipped in the D2203 enclosure If you want to mount the D2212 in one of the optional enclosures listed below order the D2212M and the enclosure of your choice D8103 Universal Enclosure D8108A Attack...

Страница 5: ...wire maximum under the terminal Use a spade lug or splice for larger wire Do not connect any other panel terminals to earth ground The panel s common terminals and terminal 3 earth ground are electrically isolated Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel W...

Страница 6: ...using Point 1 as a fire point the number of detection devices you can connect to its sensor loop is limited See Point 1 on Page 7 The number of detection devices you can connect to the sensor loops for points 2 to 8 is limited only by the resistance on the loop Resistance must be less than 100Ω with the detection devices connected Continue Connections to the Panel Power Down First Unplug the trans...

Страница 7: ...onnections Warning Do not connect wiring for external devices directly to terminals 11 or 12 Install D133 D134 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1 The D133 draws 36mA when energized When both relays are energized the D134 draws 72 mA Connect the Points On Board Points Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered supervised ...

Страница 8: ...oint wiring Four Wire Smoke Detectors Connect any number limited by available power and the Authority Having Jurisdiction of 12 VDC four wire smoke detectors to any supervised point Install a suitable power supervision device according the manufacturer s instructions Route the power for the detectors through a D133 D134 Relay Module The relay module must be connected to one of the panel s external...

Страница 9: ...dular Phone Jack Premises Phone RJ31X Module Figure 6 RJ31X Phone Jack Program Entry Guide for programming options and keypad programming instructions If you re programming from the keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programmer Operation Manual for instruction...

Страница 10: ...0 VDC Battery restoral reports sent the keypad returns to normal operation 13 9 VDC Battery float charged Fill out the Point Chart Radionics recommends that you fill out the Point Chart on the Installation Label located on the inside of the D2203 Enclosure cover You must fill out the point chart if you programmed Point 1 for Fire with Verification Digit 1 2 See POINT CODES in the D2212 Program Ent...

Страница 11: ...ch the receiver 10 attempts if two phone number are programmed the panel goes into communication failure The panel clears any reports in its phone buffer The panel sounds a tone at the keypad indicating trouble Pressing the Clear key silences the tone When communication restores a report is acknowledged by the receiver the keypad returns to normal operation Ground Start Some telephone systems requ...

Страница 12: ...Shorted Loop Greater than 0 0 VDC but less than 2 0 VDC Points 7 and 8 Points 7 and 8 are not supervised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans one second before the panel initiates an alarm...

Страница 13: ...5 minutes for Commercial Burglary applications For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed Enclosures The D2203 enclosure is suitable for Household Fire and Burglary applications only Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications Radionics offers three opt...

Страница 14: ...electronic vibration sensor directly inside the metal cabinet of the D8108A Do NOT install the sensor within a quarter inch 1 4 of the components or traces of the printed circuit assembly System Chart Household Burglar Grade A Household Fire Household Fire Burglary Combined Central Station Burglary Grade C Police Connected Burglary Local Burglary Proprietary Burglary NFPA Standard 72 72 Min Hours ...

Страница 15: ...es System Wiring Diagram Issue A s s P P P D164 Phone Cord to RJ31X for Phone Line Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns P P P P D133 D134 Relay P P Supervised with 1k Ω EOL Resistor Typical Initiating Devices are Door Contacts NO NC Floor Mats Motion Sensors Glass Break Detectors etc NOT Supervised Normally Closed Typical Initiating Devices are ...

Страница 16: ...moke Detector Head D208 RF Receiver D216 RF Receiver Radionics Inc 1800 Abbott Street Radionics 1 Park Gate Close Bredbury Salinas California 93901 Stockport Cheshire SK6 2SZ England Customer Service 800 538 5807 Technical Support 061 494 0851 The Radionics logo is a registered trademark of Radionics Inc Salinas CA U S A 1995 Radionics Inc Salinas CA U S A All rights reserved D2212 Terminal Quick ...

Отзывы: