7
CT102 Thermostat
Z Wave
®
•
Temperature Filter Upper Bound (8-bit)
The thermostat will report ambient temperature changes for
temperature values greater than the upper bound. This field
must be between 0F and 124F. By default, this value is 0F
(report all temperature changes).
Thermostat Reporting Filter Report Command Definition
7
6
5
4
3
2
1
0
Command Class = COMMAND_CLASS_CONFIGURATION
Command = CONFIGURATION_SET
Parameter = 0x0A
Precision (0x00)
Scale
Bound Size (0x01)
Temperature Filter Lower Bound
Temperature Filter Upper Bound
•
Parameter (8-bit)
The parameter is set to 10 (0x0A) for the temperature
reporting filter.
•
Temperature Filter Lower Bound (8-bit)
The thermostat will report ambient temperature changes for
temperature values less than the lower bound. This field must
be between 0F and 124F. By default, this value is 124F (report
all temperature changes).
•
Temperature Filter Upper Bound (8-bit)
The thermostat will report ambient temperature changes for
temperature values greater than the upper bound. This field
must be between 0F and 124F. By default, this value is 0F
(report all temperature changes).
11. Simple UI Mode Enable / Disable
If set to 0, Simple UI mode is disabled. If set to 1, Simple UI mode
is enabled.
12. Multicast Enable/Disable (8-bit)
If set to 0, Multicast is disabled. If set to 1, Multicast is enabled.
Содержание CT102
Страница 3: ...3 Radio Thermostat Getting Started ...
Страница 11: ...11 Radio Thermostat Setup ...
Страница 17: ...17 Radio Thermostat Wiring Diagrams ...
Страница 26: ...Radio Thermostat 3 Product Overview ...
Страница 34: ...Radio Thermostat 11 Customization ...
Страница 48: ...RTCOA logo sheet 7aug07 CT102 THERMOSTAT Z WAVE REFERENCE ...