background image

Installation Manual  

Wall Hung Boiler with D.H.W. Storage Cylinder Low Nox – Cod. 99881NA – July 2001 

 

 

16 

ELECTRICAL CONNECTION

2

1

 

TECHNICAL DATA 

DIFFERENTIAL AIR PRESSURE SWITCH FOR FAN CONTROL 

To guarantee maximum safety in flue exhaust, a differential pressure switch is 

installed on room-sealed boilers and on forced draught boilers. This pressure 

switch automatically controls perfect functioning of the fan and the passage of 

both external air and exhaust flue pipes. 
Natural draught boilers are equipped with a device (see fig. 1) to control correct 

exhaust of combustion gases. This device guarantees maximum safety of 

operation if the flue should become partially or totally blocked, or if its section is 

not suitable for exhaust of combustion gases. 

Before resetting the device, check the exhaust flue section and make sure there 

are no. blockages obstructing the correct escape of fumes. 
 

N.B. 

It is strictly forbidden to tamper with the device.

 

 

RESETTING

before resetting the thermostat, carry out the following 

operations: 

• 

turn off the main power supply switch;

 

 

• 

turn the summer-winter selector switch to the OFF position, detach the 
electrical connection (1) on the flue safety thermostat (see fig.1), press 

the button (2) between the two electrical contacts and then attach the 

electrical connection 1 again.; 

• 

turn the main power supply switch on again and set the summer/winter 

selector switch to the position required.

 

 

DIVERTER VALVE VC 6012MG6000 

The diverter valve is the device which controls the boiler switching from 

central heating to d.h. water circuit and vice versa. The diverter valve is fitted 

with a manual command lever C (fig. 3) which, when set on the top position, 

towards the valve head, allows the boiler operating on the domestic hot water 

circuit while, when set on the low position, the boiler operates on the central 
heating circuit.  

When the C  lever is set on the central position, it allows the actuator on 

midway. 

In this position, 

to be used only in case of motor failure or damage

, both 

central heating and domestic hot water ports are open and both domestic hot 
water and central heating circuits are operating. 
 

To restore the initial position, separate the actuator and the valve body 

following instructions from no.1 to no.4 (see fig.2). 

To separate the motor from the valve body proceed as follows (fig.2): 

1. 

Press button A under the motor. 

2. 

Simultaneously keep the A button pressed and turn the actuator counter-

clockwise; 

3. 

Lift off the motor 

4. 

To disconnect the power supply cable press the B tap located on the pin C. 

 

See fig. 4 to perform the electrical wiring of the diverter valve to the main printed circuit board.  

 

DOMESTIC HOT WATER PRODUCTION 

The boilers are designed and built for the production of domestic hot water with a 25 lt. capacity storage tank. One advantage of 

this system is the amount of water immediately available, thanks to the large exchanger surface of the coil inside the boiler 

which allows different services to be used simultaneously. 
As well as the use of a porcelain treated glass coating on both the coil and the internal boiler surface to guarantee high levels of 

hygiene, the inside of the boiler also has a magnesium anode which, in the event of galvanic currents, preserves it from 

corrosion to ensure it a longer working life.  

FLUE SAFETY THERMOSTAT 

Fig. 1 

-

 

Common

D.H. Water

Central Heating

CENTRAL HEATING SETTING

M5 TERMINAL

RAMIRE P.C. BOARD

light-

bl

ue

D.H. WATER SETTING

bl

ac

k

br

ow

n

Light-blue

  

Brown        
Black

Fig. 2 

Fig. 3 

Fig. 4 

Содержание RMA

Страница 1: ...BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION USE AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS WITH DOMESTIC HOT WATER STORAGE CYLINDER Model RMA TYPE B OPEN C...

Страница 2: ......

Страница 3: ...REQUIREMENTS page 6 BOILER INSTALLATION page 8 ELECTRICAL CONNECTIONS page 10 19 22 BOILER CONTROL PANEL page 11 STARTING UP THE BOILER FOR THE FIRST TIME page 11 BOILER ADJUSTMENTS page 13 MULTIGAS O...

Страница 4: ...ADDING AN OPTIONAL TIMER SELF DIAGNOSTIC LEGEND see fig 2 6 OPERATING POWER INDICATOR 7 DOMESTIC HOT WATER OPERATION 8 HEATING OPERATION 9 FLASHING LIGHT DENOTING AIR PRESSURE SWITCH FAILURE 10 FLASH...

Страница 5: ...re range can be adjusted from a minimum of 30 C to a maximum of 80 C REGULATING THE HOT WATER TEMPERATURE The hot water temperature is regulated by turning knob 4 see fig 1 pag I turn it counter clock...

Страница 6: ...mogeneous highly functional unit that is easy to install and simple to operate The wall mounted boiler is equipped with all of the approved accessories required to make it a true independent heating p...

Страница 7: ...ating unit has been constructed to heat the home and to produce hot water The constructor declines all responsibility for incorrect installation and or use of the device Do not leave the device on whe...

Страница 8: ...KCal h 22950 23090 Kw 26 68 26 85 BTU h 91066 91621 Minimum rated output KCal h 12950 12900 Kw 15 06 15 BTU h 51386 51187 Heting temperature adjustment C 30 80 30 80 Max working pressure heating bar 3...

Страница 9: ...ength by 0 8 m Kit B Double exhaust emission twin flue system with 360 rotation It allows the flue exhaust into a flue duct and the air intake directly from an external wall To insert a bend reduce to...

Страница 10: ...ust fans into single chimney collective flues with natural draft or multiple combined flues follow the directions set out in the UNI 10640 standard CONNECTION OF FLUE PIPES All boilers must be connect...

Страница 11: ...should ensure a nominal dynamic pressure of 20m Bar 8 in wg at the boiler Installation pipes should be fitted in accordance with BS6891 1988 Pipework from the meter to the boiler must be 22mm copper t...

Страница 12: ...r sources of natural air infiltration or forced ventilation air conditioning systems If this should occur the appliance MUST BE TURNED OFF IMMEDIATELY and the local gas region consulted Where the lowe...

Страница 13: ...nect pipes and valves as shown in the picture 5 Position the boiler paying attention to hang it to the hanging bracket do not lean the boiler on the JIG and make final connections WATER CONNECTIONS To...

Страница 14: ...5 C Heating sensor and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost...

Страница 15: ...d with the earth symbol see fig 3 connect the blue wire to the terminal marked with the letter N connect the brown wire to the terminal marked with the letter L CONNECTION OF ROOM THERMOSTAT NOTE use...

Страница 16: ...s no sign of leaks in any case double check by using a soapy solution and eliminate all eventual leaks The checking procedure for the gas burner attachment is carried out with the boiler working make...

Страница 17: ...ignition procedure press release button 2 see fig 1 pag 11 and then try the ignition procedure once again If the boiler does not start press the reset button 2 see fig 1 pag 11 IMPORTANT should the bo...

Страница 18: ...crewdriver for any adjustments Turn clockwise to increase gas pressure to the burner at start up by setting the trimmer to maximum calibration pressure of modulator see page 16 Turn counter clockwise...

Страница 19: ...to suit the type of gas used undo fixing nut 8 on the thin aluminium gas pipe 9 and change the jet g replace the gas setting plate that indicates the type of gas and nominal pressure for the boiler W...

Страница 20: ...biliser Fig B Widen locking clips 2 Fig C Slide out the coil 1 located above the gas valve Fig D Tighten plastic screw 3 by turning it clockwise be careful not to break it Fig E Use a no 17 spanner to...

Страница 21: ...hich when set on the top position towards the valve head allows the boiler operating on the domestic hot water circuit while when set on the low position the boiler operates on the central heating cir...

Страница 22: ...ot water see fig 2 item B fig 3 It allows conversion to hot water even with a minimum hot water demand 2 litres min using an electromagnetic principle with electrical switching by means of a relay The...

Страница 23: ...AUTOMATIC AIR VENT 18 HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 19 DRAINING TAP 20 WATER PRESSURE GAUGE 21 WATER PRESSURE SWITCH 22 HEATING SENSOR 23 HOT WATER SENSOR 24 3 WAY DIVERTER VALVE 25 FLOW...

Страница 24: ...IR VENT 17 AUTOMATIC AIR VENT 18 HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 19 DRAINING TAP 20 WATER PRESSURE GAUGE 21 WATER PRESSURE SWITCH 22 HEATING SENSOR 23 HOT WATER SENSOR 24 3 WAY DIVERTER VA...

Страница 25: ...5 LED6 RAVI II J2 D2 J3 FA1 C3 R48 C20 R49 R17 R23 R24 R47 R13 C8 J9 C6 C19 C21 C7 R15 R32 C13 R39 R37 R31 41 M9 R62 R61 R57 R16 42 C14 C9 R38 C5 RS1 J20 IC2 R18 IC1 R42 43 GPL 44 J7 46 45 R20 C12 R58...

Страница 26: ...5A 2019 4 PS 5 TS LB 7 6 9 9 8 11 11 10 10 12 12 8 13 EA ER 14 15 P 6 ELECTRONIC TEMPERATURE INDICATOR 54 50 51 53 52 55 56 58 57 RVB RVA RV 2 1 3 7 23 19 24 17 18 22 IG VD R CY CX L 20 5 21 16 4 NET...

Страница 27: ...F CONNECTORS 23 LED5 C6 C7 RS1 R58 R22 R21 4 2 1 3 15 14 22 LED2 LED1 LED3 LED4 RAVI II R31 42 R18 R17 yellow blue R48 FA1 C20 R49 R23 R24 R47 C19 C21 red brown R39 C9 M9 R62 R61 R57 J16 R38 C5 J20 R3...

Страница 28: ...OSTAT FLOWSWITCH MICRO SWITCH M F TS HEATING SENSOR D H WATER SENSOR SR SS 3 WAY DIVERTOR VALVE WIRING CONNECTION ONLY FOR Mod VC6012 VD black black black black brown orange black black M F WATER PRES...

Страница 29: ...water flow rate and temperature When dismantling the boiler casing be careful when removing the side panels after having removed the front panel the front panel is removed by undoing the lower and fr...

Страница 30: ...g 1 on a replace it b re connect or replace it c replace it d change over polarity e make earth connection f fit conversion kit 4 Boiler on temperature rises rapidly and extinguishes flame light 2 fig...

Страница 31: ...08LA 3 BAR PRESSURE RELIEF VALVE 1 2 16 96026LA D H W CYLINDER TEMPERATURE 90 PRESSURE 7BAR SAFETY VALVE 17 20030LA INSULATED 25 LT STORAGE CYLINDER 18 95006LA 10 LT EXPANSION TANK W BRACKET 19 96007L...

Страница 32: ...6 Tel 39 0721 498822 Fax 39 0721 499815 Email tecnico radiant it italia radiant it export radiant it Internet http www radiant it All descriptions and illustrations contained in this leaflet have been...

Отзывы: