USER INSTRUCTIONS

 

 

4

M

  Topping-up the system with water 

 

The water pressure in the central heating circuit 
must  be  checked  during  the  entire  period  of 
operation  of  the  boiler.  In  this  respect,  the 
reading  on  the  pressure  gauge  M  (see  fig.  2), 
located on the lower part of the boiler, must not 
be less than 1 bar. 

If  there  is  insufficient  water  in  the  boiler,  the 
code H2O will flash on the display (see “Control 
panel”).  

To bring the system back up to pressure, open 
the  external  filling  loop  valve  (see  fig.  3)    and 
use the pressure gauge M (see fig. 2) to check 
that the system pressure reaches 1 bar and that 
the code H2O lights up.  

When  the  operation  is  complete,  close  the  fill 
valve.  

 
Diagnostics – Error codes: 

This paragraph contains a list of error codes that 
the  boiler  may  generate  on  the  display  7  (see 
“Control  panel”)  together  with  the  relative 
indications  and  the  operations  that  the  user  can 
carry out to reset the boiler. 

 

If  the  problem  re-occurs  after  the 
following  actions  have  been  taken, 
call an authorised Service Centre. 

 

 

_

E01

E01

E01

E01

  

Ionisation block

 

Code E01 lit continuously on the display.   

  Check that the gas valve on the boiler and gas meter are open and that there is gas in the mains supply (or in 

the tank).  

  Switch off then switch on the appliance using switch 1 (see “Control panel”) on the control panel. 

  When  the error code on the display disappears, the boiler will restart. 

If the problem persists, Call the Service Centre. 

 

_

E02

E02

E02

E02

_  Safety Thermostat tripped

 

Code E02 lit continuously on the display.  Call the Service Centre. 

 

_

E03

E03

E03

E03

_  Flue Gas Thermostat tripped

 

Code E03 lit continuously on the display.  Call the Service Centre. 
 

_

h2o

h2o

h2o

h2o

_  Water Pressure Switch tripped

 

Code H2O lit continuously on the display.   

  Check  the  water  pressure  in  the  central  heating  circuit.  The  reading  on  the  pressure  gauge  M  (see  fig.  2), 

located on the lower part of the boiler, must not be less than 1 bar . 

  If the pressure is less than 1 bar, top-up the system as described in paragraph “Filling the system”. 

  The boiler will restart automatically. 

If the problem persists, Call the Service Centre.

 

Fig.  2

 

Fig.  3

 

CWI

HF

12-00710

OPTIONAL

Содержание RK 25

Страница 1: ...0694 RK 18_25_34 RAD ING MAN UT 1104A DIGITECH 2 REGNO UNITO EXTRAHEAT CBD Technical specification by RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH User Manual for model RK 18 RK 25 RK 34 Premix condensing boiler ...

Страница 2: ......

Страница 3: ...current standards and where the minimum external temperature does not fall below 10 C The manufacturer will not be held responsible for installation in locations where the temperature falls to below 10 C The boiler is fitted with an antifreeze system If the boiler is installed in a location where there is a risk of freezing the anti freeze system will only come into operation if the power is on an...

Страница 4: ...RATURE CONTROL KNOB 3 NOT OPERATIVE KNOB 4 OUTSIDE TEMPERATURE DISPLAY ONLY WITH OPTIONAL OUTDOOR SENSOR 5 SERVICE BUTTON 6 WINTER MODE SELECTION BUTTON 7 TERMINAL BOARD FOR EXTERNAL WIRING 8 TEMPERATURE ERROR CODE AND OPERATING STATUS DISPLAY 9 TIME CLOCK optional 7 6 5 4 3 2 1 8 9 Fig 1 ...

Страница 5: ... mode press button 6 see fig 1 The boiler will only work for the central heating system The WINTER mode setting of the boiler is signalled by the symbol lit continuously on the control panel The automatic ignition system will light the burner every time there is a demand for room heating In this case the symbol on the control panel will flash Regulating the heating temperature The heating temperat...

Страница 6: ... have been taken call an authorised Service Centre _E01 E01 E01 E01_ Ionisation block Code E01 lit continuously on the display Check that the gas valve on the boiler and gas meter are open and that there is gas in the mains supply or in the tank Switch off then switch on the appliance using switch 1 see Control panel on the control panel When the error code on the display disappears the boiler wil...

Страница 7: ...y on the display Call the Service Centre _E35 E35 E35 E35_ Flame Detection Malfunction Code E35 lit continuously on the display Call the Service Centre N B If the boiler is to be left unused for a long period of time the user must do one of the following Make the boiler safe by disconnecting all the power supplies electricity and gas and draining the heating system and the condensate trap Leave th...

Страница 8: ...ON PURPOSES ONLY AND ARE NOT BINDING THE COMPANY RESERVES THE RIGHT TO APPLY VARIATIONS WITHOUT PRIOR NOTIFICATION NEITHER WILL THE COMPANY BE HELD RESPONSIBLE FOR ANY INACCURACIES IN THIS HANDBOOK DERIVING FROM PRINTING OR TRANSLATION ERRORS E OEALL RIGHTS RESERVED NO PART OF THIS DOCUMENT MAY BE REPRODUCED MEMORISED IN ANY FILING SYSTEMS OR TRANSMITTED IN ANY FORM WHATSOEVER INCLUDING ELECTRONIC...

Отзывы: