REGULATION INSTRUCTIONS
TA05A140.A0307
33
P
ARAMETER
13
–
D.H.W
PRIORITY
Not applicable
P
ARAMETER
14
–
T
YPE OF BURNER
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter:
00 = boiler with atmospheric burner;
01 = boiler with premix burner 25 kW;
02 = boiler with premix burner 29-34 kW ;
03 = boiler with premix burner 50 kW ;
7. Press and release button ‘S’ to confirm. The parameter number (14)
will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER
15
–
Z
ONED SYSTEM
6. If the system is fitted with zone valves, set the parameter at ‘01’. If a
remote control is installed, an extra interface board must be installed
to control the zone valves. Then set the parameter at ‘01’.
7. Press and release button ‘S’ to confirm. The parameter number (15)
will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER
16
–
T
ELEPHONE CONTROL
6. If a telephone interface is installed, enable the board by setting
parameter 16 at ‘01’;
7. Press and release button ‘S’ to confirm. The parameter number (16)
will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
N.B.: The connection of the telephone interface to contact TA of the
terminal board must be wired in parallel with the remote control using
two non-polarised conductors.
S
S
S
S
S
S
01
13
S
S
14
02
15
16
00
00