1. INSTALLATION
INST
ALLER
KIT CK 50 - VERTICAL CO-AXIAL SYSTEM Ø80/125
INTERNAL POLYPROPYLENE DUCT.
It allows fumes discharge and air intake directly
from roof.
Suitable only for condensing boilers.
It allows fuel gas discharge and air intake for
combustion through co-axial ducts, the external
one for air intake, the plastic internal one for fumes
discharge.
PLEASE SEE THE MAXIMUM DISCHARGE LENGTH
IN THE TABLE IN CHAPTER “TECHNICAL DATA”.
The maximum discharge length (or linear reference
length) can be calculated summing the length of the
linear tube and that equivalent to each additional
curve with respect to the first.
Subsequent addition of a curve is similar to adding
a linear length of tube according to the indications
below:
curve Ø80/125 at 90° = 0.8 m
curve Ø80/125 at 45° = 0.5 m
Ø125
Ø 80