9
Maximum Static Pressure
is
10 bar
.
Recommended maximum flow velocity in pipelines is 2 metres/second.
Maximum Pressure Loss Ratio*:
should not exceed
10:1,
in favour of either supply,
during flow.
Recommended Maximum Dynamic Supply Pressure: 5 bar.
Maximum Static Supply Pressure: 10 bar.
Recommended maximum flow velocity in pipelines is 2 metres/second.
* Pressure Loss Ratio is determined by subtracting the resistance to flow of the outlet
pipework and outlet fittings (generally known as "back pressure", and measured at the
outlet of the mixing valve) from the dynamic pressures of the hot and cold water at each
inlet of the mixing valve. This is at its extreme when the mixing valve is being used at
its lowest flow-rate and when the maximum inequality occurs in the pressure of the hot
and cold water supplies.
Hydraulic Restriction: Flow Rate/Pressure Loss Graph
(mixing valve only, equal dynamic supply pressures and mid-blend
temperature setting).
Flow Rate
Litres/Min.
Pressure Loss - bar
.
50
40
30
20
10
0
0
0.5
1.0
1.5
2.0
Rada 215
Rada 222