37
Appendix E: AlarmAgentTM RTU Specification
MODELS
AlarmAgent.com Wireless Remote Terminal
Units (RTU) are offered in 2 different models:
AA-102DC
AlarmAgent.com RTU
with NEMA 1 Enclosure
AA-102DCNEMA4X
AlarmAgent.com RTU with
NEMA 4X Enclosure and Outdoor Antenna
ELECTRICAL
Eight Digital Inputs
: For connection to dry
(unpowered) contacts. Open circuit voltage
5VDC; closed circuit current 2mA DC.
Pulse Totalizing
: Minimum closed pulse width 50 millisaconds;
maximum pulse rate 10 pps.
Two Universal Signal Inputs
:
Digital:
Open circuit voltage 5VDC; closed
circuit current 2mA DC.
Analog:
4-20MA, single ended. Maximum
voltage drop 2.5 VDC.
Resolution:
0.1%, absolute accuracy is 0.25%.
Two Relay Outputs
: Normally Open Relays,
0.5-ampere @ 120VAC
Battery Backup
: 24 hours, 12 volt @ 1.2 Amp Hr
Power Management
: System intelligently
manages power during power failure.
Power Requirements
:
User supplied. The RTU operates on
12 to 24 VDC power input.
With 12 VDC input, current is
1-ampere peak, 200 mA average.
With 24 VDC input, current is
0.5-ampere peak, 100 mA average.
Battery Charging
: Precision voltage controlled
to maximize battery life and rapidly recharge
the battery after power failure.
Power Failure
: Automatic alarm for external
power failure and low battery detection.
Power Consumption
: 2 watts nominal
Solar Power
: In solar power mode, average
current is 60 ma @ 12 VDC (0.72 watts)
Surge Protection
:
Digital inputs are opto-isolated and rated
at 5,000 volts.
Universal inputs are rated at 600 watts.
Power input is protected to 1,500 watts peak.
The fuse is automatically reset.
PHYSICAL
Enclosure
:
Open chassis: 9.6" H x 4.0" W x 2.44" D
NEMA 1 enclosure: 9.6" H x 4.35" W x 2.75" D
NEMA 4X enclosure: 11.5" H x 4.33" W x 5.5" D
Mounting Centers
:
Open chassis: 3-1/2" x 5-15/16"
NEMA 1 enclosure: 3-1/2" x 6-19/32"
NEMA 4X enclosure: 4" x 8-3/4"
Weight
:
Open chassis:
2.4 lbs w/Indoor antenna
NEMA 1 enclosure:
2.7 lbs w/Indoor antenna
NEMA 4X enclosure:
5.5 lbs w/Conical Outdoor antenna
ENVIRONMENTAL
Temperature range:
Operating, -30 to + 70°C (-22 to +158°F)
Storage, -40 to + 85°C (-40 to +185°F)
Humidity:
0 to 95% non-condensing
COMMUNICATIONS
Bi-directional RTU communications are handled
by the AlarmAgent.com secure server via the
wireless cellular network.
SYSTEM CONFIGURATION
The RTU is configurable via two possible
means: via dipswitch, or wirelessly via
AlarmAgent.com. In most cases, a notebook
computer connection is not required. By selecting
from 4 templates that are optimized for duplex
pump stations with or without totalizer and triplex
pump stations with or without totalizer, rapid
installation and error proof startup are virtually
guaranteed. Three additional templates are
available for more general applications.
ALARM AND SYSTEM MESSAGES
User defined alarm and system messages
are delivered via voice calls, SMS messages,
alphanumeric pagers, and e-mail to an unlimited
number of user specified destinations. Authorized
personnel acknowledge alarms during voice calls
via a toll free number, e-mail, or through the
AlarmAgent.com Web site.
OPERATOR INTERFACE
The AlarmAgent.com RTU includes pushbuttons
to turn the unit on or off, to arm or disarm the unit,
to cause a special Test Call to be generated, and a
digital input Accept function to assist in the setup
of the RTU.
LEDs are used extensively throughout to indicate
the status of the following subsystems: AC power
status, battery status, network service availability,
a 10 segment LED bar graph for service signal
strength, actively transmitting, test report, customer
account status, template setting status, individual
input channel state, individual relay output state,
and if any channels have exceeded their daily
limit of transmissions.
WARRANTY
Three year parts and labor warranty,
FOB factory Emeryville, CA
FIELD UPGRADES
AlarmAgent.com RTU firmware is
field upgradeable.
Содержание AlarmAgent.com AA-102DC
Страница 1: ...RACO MANUFACTURING ENGINEERING COMPANY AA RTU Installation Manual v3 2...
Страница 6: ...5...
Страница 7: ...6 RTU Interior View...
Страница 34: ...33 Solar Power Mode Wiring Diagram...
Страница 35: ...34...
Страница 36: ...35...
Страница 37: ...36...
Страница 40: ......
Страница 41: ...40 Appendix G AlarmAgentTM RTU Digital Upgrade Field Wiring Worksheets...
Страница 42: ...41...