RAB GOTCHA PLUS GT500 Скачать руководство пользователя страница 4

INSTRUCTIONS

GOTCHA

®

 PLUS INSTALLATION

RAB Lighting is committed to creating high-quality, aff ordable, well-designed and energy-effi  cient LED lighting and controls that make it easy for electricians to install

and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]

Location Considerations

•  Choose a location from which the sensor can “see” all the paths 

of movement that will be illuminated by its lights.

•  If wall mounting, locate 8-10’ high for optimum range and 

detection. Lower mounting height will reduce range. Sensor 
must be below and as far as possible away from lights. 

•  Mount on stable surface that is protected from rain.
•  Do not mount on a pole or tree that sways in the wind.
•  Sensor functions best when the direction of expected 

movement is across its detection pattern, not towards 
the sensor. 

(Fig 10)

Test Period:

The sensor has a 

Test Mode

 which allows it to be aimed and “walk 

tested” day or night.

•  Switch the sensor to 

Test Mode

 by adjusting the time control 

to test setting. Power on sensor. 

•  During the 60 second warm up period, the lights will be 

turned on. During this time, test that all fi xtures and lamps 
function properly.

•  After the warmup period, the sensor will keep lights on for 5 

seconds each time it detects movement in its 

Detection Zone

•  Once the 

Detection Zone

 is tested, adjust the sensor Time 

control to desired standby time. 

PICKING A LOCATION

AIMING & TESTING

WALK TESTING

Fig: 11

4

70ft

50ft

8-10ft

50ft

Detection Pattern

Start

Finish

To keep lights on at night, fl ip the wall switch two times 
(OFF-ON-OFF-ON) within 5 seconds. Sensor resets to auto mode 
after 6 hours. Switch the power ON and OFF once (OFF-ON) quickly 
to go to AUTO mode. No extra wiring needed.

Time Control: (Fig 12)

 Sets the time that lights will remain on after

the Detection Zone is vacated. Time setting ranges from 
approximately 5 seconds to 15 minutes.  Turn gently.  Do not turn 
past stops. 

Sensitivity: 

 Increases or decreases the responsiveness and range 

of the sensor.

MANUAL OVERIDE

ADJUSTING TIME & SENSITIVITY

Fig: 12

Fig: 10

Less Sensitive

More Sensitive

The purpose of the 

Walk Test

 is to check and adjust the 

coverage pattern.

1.  Aim the sensor approximately to cover the area you desire. 
2.  Start outside the 

Detection Zone (Fig 11) 

and walk across 

the zone until the lights go on. As distance from the sensor 
increases, it will take more movement to be detected. For 
instance, at 10 feet, a half step will be enough, while at 30 feet, 
several steps will be necessary.

3.  To reduce range tilt sensor down. Repeat steps #2 and #3 until 

you are satisfi ed with the coverage. 

4.  After testing is complete, adjust the time setting to desired 

setting by turning time control knob 

(5 sec to 15 mins).

5.  Your sensor is ready for operation. See the Technical Tips pages 

if additional help is needed.

Содержание GOTCHA PLUS GT500

Страница 1: ...arp objects SPECIFICATIONS CONTENTS GT500 Voltage 120V 277VAC 60Hz UL Listing Suitable for wet locations raintight Time Adjustment 5 sec to 15 min Test Mode Set Time Adjustment Knob on sensor to Test Mode Switching Capacity 500W 120VAC Tungsten 500W 277VAC Tungsten 600W 120VAC Electronic Ballast LED 1350W 277VAC Electronic Ballast LED Power Consumption 4 Watts Surge Protection 6 kV Operating Tempe...

Страница 2: ...nd rectangular or octagonal surface or recessed box 1 Attach Cross Bar to Surface Junction Box using three bar screws supplied Fig 4 2 Bring sensor wires through the Surface Adaptor Plate 3 Make connections to the supply wires in the junction box according to the Basic Kit Wiring diagram on pg 5 4 Push connected wires into the Surface Junction box 5 Place the O Ring over the 1 4 20 Screw and inser...

Страница 3: ...r the experienced installer because it becomes difficult to troubleshoot Single sensors that control their own lights pinpoint movement more accurately and operate better Fig 9 Fig 7 Fig 8 Fig 9 3 FactoryPre wired WireDuring Installation WIRING Cautions All wiring MUST comply with local electrical codes and should be installed by qualified electrician Read entire Installation Manual before proceed...

Страница 4: ... in its Detection Zone Once the Detection Zone is tested adjust the sensor Time control to desired standby time PICKING A LOCATION AIMING TESTING WALK TESTING Fig 11 4 70ft 50ft 8 10ft 50ft Detection Pattern Start Finish To keep lights on at night flip the wall switch two times OFF ON OFF ON within 5 seconds Sensor resets to auto mode after 6 hours Switch the power ON and OFF once OFF ON quickly t...

Страница 5: ...URN ON 1 Check that lamps and fixtures work Compare wiring to the Wiring Diagram in this manual Check that the power is on 2 Check that lights from other sources such as adjacent porch lights garden lights streetlights or lights from inside the house are not in the sensor s view See 1 under Lights Turn Off Too Quickly 3 Was sensor wired hot If so circuitry may have been damaged 4 If sensor is pain...

Страница 6: ...nsitivity control settings mount in a more protected area and or mask the lens if this is a constant problem TOLL FREE TECHNICAL ASSISTANCE If you need technical assistance please do the following 1 Re read the Technical Tips sections of this manual 2 Call the Tech Help Line at 888 722 1000 8AM to 4PM Eastern Time M F and we will be glad to help you Before you call please have the following inform...

Отзывы: