INSTRUCTIONS
FIELD-ADJUSTABLE SR™ INSTALLATION
RAB Lighting is committed to creating high-quality, aff ordable, well-designed and energy-effi cient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
SR - IN - 0922
RAB WARRANTY:
RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
Answered promptly - [email protected]
Free Lighting Layouts
Answered online or by request
© 2022 RAB LIGHTING Inc.
P-100266
PINK
LIGHT
FIXTURE
Vaux 12V
YELLOW
GROUND
GROUND
( - ) DIM V
( + ) DIM V
COMMON
LINE
BLACK
WHITE
PURPLE
Fig. 12
FIELD ADJUSTMENT
Follow instructions below to change the
Fixture Power
(W)
and/or
Color Temperature
(CCT)
from factory settings:
Factory Settings:
SR2 19/14/10W 19W / 4000K
SR4 40/30/20W 40W / 4000K
SR8 60/50/40W 60W / 4000K
1.
Locate the
Field Adjustable Switches
on the side of
Fixture
Housing
as shown in Fig. 10.
2.
Select
Power
(W) and
Color Temperature
(CCT)
by sliding
respective switch to the desired value
(Fig. 10).
40W
30W 2
0W
5000K
4000K
3500K
Follow instructions below to change the Fixture Power (W) and/or Color Temperature
Power
(W)
Color Temperature
(CCT)
Fig: 10
PIR MODELS
Screw
Sensor Head
onto the
Bracket
as shown in Fig. 11. See factory
settings below
(optional remote sold separately for custom settings,
CAT# MSR1).
Factory Settings:
•
Brightness: 100%
•
Hold Time: 1 Minute
•
Daylight: Disabled
•
Sensitivity: 100%
Bracket
Sensor Head
0-10V DIMMABLE WIRING
RISK OF FIRE.
Universal voltage driver permits operation at 120V
through 277V, 50 or 60 Hz. For 0-10V dimming follow the wiring
directions as shown in Fig. 12.
1. Connect the black fi xture lead to the LINE supply lead.
2.
Connect the white fi xture lead to the COMMON supply lead.
3. Connect the green GROUND wire from fi xture to supply ground.
4.
Connect the purple fi xture lead to the (V+) DIM lead.
5.
Connect the pink fi xture lead to the (V-) DIM lead.
6.
Cap the yellow fi xture lead, if present. Do NOT connect.
SR VHOOK ACCESSORY KIT
SR JOIN Kit includes the following:
•
Joiner Bracket w/ 8 Screws
•
Nuts
(12)
SR JOIN ACCESSORY KIT
TROUBLESHOOTING
1. Check that the line voltage at the fi xture is correct. Refer to
wiring diagram.
2.
Be sure the fi xture is grounded properly.
CLEANING & MAINTENANCE
CAUTION: Be sure fi xture temperature is cool enough to touch.
Do not clean or maintain while fi xture is energized.
1. Clean
polycarbonate
lens with non-abrasive cleaning solution.
2.
Do not open the fi xture to clean the LEDs. Do not touch the LEDs.
SR VHOOK Kit includes the following:
•
40” Chain
(2)
•
V-Hooks
(2)
•
Wires
(12 - Tinned copper)
Fig. 11
Note:
These instructions do not cover all details or variations in equipment nor do
they provide for every possible situation during installation, operation
or maintenance.
MVS MODELS
(Internal)
•
Sensitivity: 50%
•
Stand-by dimming level: 20%
•
Stand-by time: 1 Minute
(optional remote sold separately for custom settings, CAT# MSR1).