background image

 

 

 

Additional Loggers 

EQ LTE, Logger, Flow - complete case kit 

2014900361 

2014900361 Kit Contains 

Logger Case 
EQ LTE, Logger, flow - logger assembly 

EQ LTE, Sensor, flow 

EQ LTE, Power Supply (100 - 240vAC input / DC output power supply c/w plug assortment) 

 

 

EQ LTE, Logger, Temperature - complete case kit 

2014900365 

2014900365 Kit Contains 

Logger Case 

EQ LTE, Logger, temperature - logger & sensor assembly 

 

 

EQ LTE, Logger, Moisture (dewpoint) - complete case kit 

2014900362 

2014900362 Kit Contains 

Logger Case 

EQ LTE, Logger, Moisture (dewpoint) - Logger assembly 

EQ LTE, Sensor, moisture (dewpoint) 

EQ LTE, Sensor, moisture (dewpoint) mounting chamber 

EQ LTE, Power Supply (100 - 240vAC input / DC output power supply c/w plug assortment) 

 

 

EQ LTE, Logger, 4 - 20mA - complete case kit 

201400363 

2014900363 Kit Contains 

Logger Case 

EQ LTE, Logger, 4 - 20 mA - logger assembly 

EQ LTE, Logger, 4 - 20 mA - counter connector 

EQ LTE, Power Supply (100 - 240vAC input / DC output power supply c/w plug assortment) 

 

 

EQ LTE, Logger, 0-60bar. case kit 

2014900358 

2014900358 Kit Contains 

EQ LTE, Logger, Case - flow - case only 

EQ LTE, Logger, 0-60bar-log. & sensor 

EQ LTE, Power Supply (100 - 240vAC input / DC output power supply c/w plug assortment) 

 

 

 

Note: 

All battery powered loggers are supplied with batteries included. 

Содержание EQ LTE 2014900479

Страница 1: ...Equipment Technical Manual Base Station...

Страница 2: ...wer Supply 100 240vAC input DC output power supply c w plug assortment Note No case is supplied with this kit items are supplied loose EQ LTE Logger Pressure 0 16BAR complete case kit 2014900357 20149...

Страница 3: ...t Logger assembly EQ LTE Sensor moisture dewpoint EQ LTE Sensor moisture dewpoint mounting chamber EQ LTE Power Supply 100 240vAC input DC output power supply c w plug assortment EQ LTE Logger 4 20mA...

Страница 4: ...st use 4 2 4 General operation 4 2 5 Power supply 4 2 6 Logger battery compartment 4 2 7 Keypad 4 2 7 1 Bluetooth key and LED 4 2 7 2 Diagnostic key and LED 4 2 8 Data logger installation 4 2 9 EQ LTE...

Страница 5: ...hat an organization or website is referred to in this work as a citation and or a potential source of further information does not mean that the author or the publisher endorses the information the or...

Страница 6: ...he licensed materials including the specific design and structure of individual programs constitute trade secrets and or copyrighted material of Quincy Compressor Customer agrees not to disclose provi...

Страница 7: ...the device personnel must use relevant safe working practice and observe all relevant local health and safety requirements and regulations Lethal voltages may be present at or around the device Elect...

Страница 8: ...the ratings supply voltage frequency pressure temperature altitude humidity and environmental rating for which it is designed Do not operate the device without battery door enclosure open or covers r...

Страница 9: ...ated The very latest Bluetooth technology then enables this information to be effortlessly transferred from multiple data loggers to a single intelligent EQ LTE base station In turn the base station t...

Страница 10: ...g device ID serial number and original equipment manufacturer bar code data is located on the back elevation of the base station 4 1 2 Preparing for first use Each EQ LTE base station is supplied with...

Страница 11: ...onment and EQ LTE data loggers Once EQ LTE data loggers return from the audit location simply synchronize with the EQ LTE base station once more and transfer your logged data from the EQ LTE base stat...

Страница 12: ...Wizard configuration files from base station to logger s using Bluetooth Base to logger s Distributing logger configuration files to loggers Logger s to base Used to transfer data files from logger s...

Страница 13: ...t locks either side of carry handle Transportation feet for stability when stacked Formed cushion insert Tamper resistant label providing device ID serial number and original equipment manufacturer ba...

Страница 14: ...data loggers also feature an external power supply input This is used to power the data logger sensor Note The use of an external power supply unit does not eliminate the use of or need for the data...

Страница 15: ...Slow flash Not configured Troubleshooting Create audit configuration transfer from cloud to base station and then from base station to logger Fast flash Configured not sensing data Troubleshooting Ch...

Страница 16: ...ing temp 0 C 55 C 32 F 131 F Power batteries Four AA lithium primary cells Li SOCI2 3 6V 2700mAh Real time clock Precision real time clock temp compensated crystal Maximum deviation 0 4s day Sample ca...

Страница 17: ...wet environments Do not use the device if it operates incorrectly Protection can be compromised Examine the test leads for damaged insulation or exposed metal Check test lead continuity Replace damage...

Страница 18: ...deviation 0 4s day Sample capacity More than 1 4 million samples 16 days continuous logging Sample frequency 1 second fixed resolution 4 2 10 2 Sensor installation Warning risk high pressure Isolate...

Страница 19: ...and should be chosen according to practical constraints Observe and maintain safe working practices at all times Identification EQ LTE Logger temperature 2014900365 EQ LTE EQ LTE Temperature data log...

Страница 20: ...point data logger Precision data logging Definition Function Logger A D resolution 16 bits Bluetooth slave 2 1 EDR enhanced data rate Bluetooth range 10 meters 33 feet The effective range varies due t...

Страница 21: ...ets at the sensor element Condensation or water on the sensor element may cause a fault and may corrupt sensor data The size of the inlet and outlet pipe diameter sections must not be less than the sp...

Страница 22: ...present in area L of the diagram below Be aware that the air flow sensor is directional L Length of pipe section At inlet L1 15 x inner pipediameter At outlet L2 5 x inner pipe diameter D Inner diamet...

Страница 23: ...39 69 Oxygen O2 176 4 578 74 Nitrous oxide N2O 181 4 595 14 Natural gas NG 109 4 358 92 DIN 1343 0 C 1013 25mbar Maintenance The sensor head should be checked regularly for dirt and cleaned if necessa...

Страница 24: ...slave 2 1 EDR enhanced data rate Bluetooth range 10 meters 33 feet The effective range varies due to propagation conditions material coverage production sample variations antenna configurations and b...

Отзывы: