4. PERFORMING AIRFLOW MEASUREMENT FOR RA3.9.4.1.2(4) STEP 4

1.  Make sure whole house fan(s) are off and note the speed being tested on each if there are multiple

2.  Setup and install WHF-PFH on first fan to be tested if there are multiple fans and select appropriate 

ring

a.  If flow channel is reading “LOW” after you zero out with “open” Ring. Refer to blower door fan 

manufacturer instructions to install Ring “A”

3.  On both TEC and Retrotec fans, connect pressure tap from flow hood to channel A (pressure channel) 

input tap on digital gauge

4.  On both TEC and Retrotec fans, leave the channel A (pressure channel) reference tap open to read 

pressure inside the dwelling

5.  On TEC Model 3 fan, connect the pressure tap from the blower door fan to the channel B (flow 

channel) input tap 

6.  On Retrotec fans, connect the pressure tap from the blower door fan to the channel B (flow channel) 

reference tap

7.  On TEC Model 3 fan, leave the channel B (flow channel) reference tap open to reference inside the 

dwelling

8.  On Retrotec fans, leave the channel B (flow channel) input tap open to read pressure inside the 

dwelling

9.  It is suggested to turn on blower door fan prior to whole house fan to pressurize the flow hood 

slightly

10. Turn on whole house fan(s) and adjust blower door fan accordingly to “zero out” the pressure in the 

flow hood

11.  Document your airflow reading

Содержание WHF-PFH

Страница 1: ...OPERATION MANUAL HERS POWERED FLOW HOOD MODEL WHF PFH MAKERS OF THE QUIETCOOL ADVANCED WHOLE HOUSE FAN...

Страница 2: ...ce personnel should service the system The user should not attempt to service the product 6 Maneuvering the Unit When lifting stand or moving the unit around the house be very careful not to drag it a...

Страница 3: ...Velcro iv Coroplast rectangular cutout v Soft plastic tubing with 4 barbed tee fittings pressure taps vi Fiberglass poles QTY 4 Bottom square Frame 27 5 x 27 5 Top Octagonal Frame Telescoping Legs i 4...

Страница 4: ...Do not route cord under furniture or appliances Arrange cord away from traffic area and where it will not be tripped over Do not place this equipment or power cord in water or other liquid Use only t...

Страница 5: ...needs to be between 4 5 from ceiling ii It is recommended to adjust height of legs prior to adding top octagonal frame c FOR RETROTEC FANS i Slide Retrotec fan in between the 4 legs See pictures below...

Страница 6: ...completely or test may yield inaccurate results 4 Ensure hood is flush by lightly pushing up on bottom of hood a If you see the top of hood move readjust poles by going higher b Check again and repeat...

Страница 7: ...Gauge 1 Take the pressure tap coming out the bottom of the flow hood and connect it to the input tap to read pressure 2 See page 9 for complete connection details Complete WHF PFH with TEC Model 3 Fa...

Страница 8: ...procedures 1 Open the window s that are typically opened during WHF operation 2 Turn on all WHFs required to meet the dwelling unit WHF airflow rate Adjust multiple or variable speed WHFs to operate...

Страница 9: ...he channel A pressure channel reference tap open to read pressure inside the dwelling 5 On TEC Model 3 fan connect the pressure tap from the blower door fan to the channel B flow channel input tap 6 O...

Страница 10: ...e airflow Verify all tube connections are properly connected for airflow measurement apparatus and hood adapter system Ensure proper connection of the WHF PFH flow hood to testing fan apparatus has a...

Страница 11: ...ow rate listed on CF 1R report Title 24 reports that have modeled medium speeds for 2019 code only need to be tested at medium speed If the measured flow rate is failing too low try running WHF at a h...

Страница 12: ...12 Rev 6 11 20 MAKERS OF THE QUIETCOOL ADVANCED WHOLE HOUSE FAN...

Отзывы: