25
EN
SBC NRG
+
HIGH REV001B
NOTIFICATION SIGNS
NOTIFICATION SIGNS
LED
FLASHES
MESSAGE
DESCRIPTION
2
Output fuse open
Likely inversion of polarity in the connection of the batteries to the battery charger’s output
terminals.
The problem requires a check by a Quick
®
service center.
3
Output overvoltage
Software protection.
The battery charger, due to an internal malfunction, supplied for a very short time a higher
voltage than the rated value.
The problem requires a check by a Quick
®
service center.
5
Extended output overload
The battery charger has supplied the maximum current at a lower voltage value than half the
output rated value for too long.
Check the absorption of the battery bank and the connected loads.
6
Both fans blocked
Both cooling fans are stopped for external causes (foreign bodies which block the blades
movement) or malfunctioning.
The problem requires a check by a Quick
®
service center.
9
Almost two chargers in a
group with the same priority
Check the correct setting of the group and the priority of the battery chargers connected to
the network, by means of the RDS 1562 terminal (optional).
10
Internal temperature sensors
fault
Both internal temperature sensors are not working.
The problem requires a check by a Quick
®
service center.
11
BULK phase too long
The maximum time limit of 8 hours (Default) for the BULK phase has been exceeded.
Check the status of the battery banks and the absorption of the loads connected to them.
12
ABSORPTION phase too long
The maximum time limit of 24 hours (Default) for the ABSORPTION phase has been exceeded.
Check the status of the battery banks and the absorption of the loads connected to them.
PROBLEMS WITH MANUAL RESET
In order to solve problems with manual reset it is necessary to remove the cause that generated it, disconnect the battery
charger from the AC mains for 10 seconds and then reconnect it.
With this type of problems, the battery charger stops supplying power (except for problem 12, in which output voltage is
forced to the FLOAT value).
The ERROR LED flashes to warn about the kind of problem.
Refer to the table below to identify the kind of problem: