19
CHARACTERISTICS AND INSTALLATION
GB
INSTALLATION SITE
Install the battery charger in a dry, ventilated pla-
ce and as near to the batteries as possible. The
battery charger, although having high efficiency,
develops a certain amount of heat during use,
therefore, it is imperative that the installation
area has sufficient ventilation, enough to allow
use of the equipment at maximum power.
The battery charger can be installed in a horizon-
tal or vertical position with cables coming out in
the downward position. The vertical position is
recommended because the natural convection of
heat helps to cool the equipment. The perimeter
of the battery charger (except the base) must be
kept at a distance from walls or objects by a mi-
nimum of 5 cm.
FIG.1
PART. A
PART. B
WARNING:
the battery charger must be used only with re-chargeable lead/liquid electrolytic batte-
ries or lead/gel (sealed or non-sealed).
MODEL
Battery voltage
Battery capacity
Minimum output cable size
(Battery charger-junction “J”)
Minimum output cable size
(Junction “J”- battery)
SBC 1100 ADV PLUS FR
SBC 1450 ADV PLUS
SBC 1950 ADV PLUS
2 units in parallel
2 units in parallel
2 units in parallel
12 V
24 V
720 ÷ 1600 Ah
540 ÷ 1200 Ah
720 ÷ 1600 Ah
35
mm
2
25
mm
2
35
mm
2
70
mm
2
50
mm
2
70
mm
2
MODEL
Battery voltage
Battery capacity
Minimum output cable size
(Battery charger-junction “J”)
Minimum output cable size
(Junction “J”- battery)
SBC 1100 ADV PLUS FR
SBC 1450 ADV PLUS
SBC 1950 ADV PLUS
3 units in parallel
3 units in parallel
3 units in parallel
12 V
24 V
1080 ÷ 2400 Ah
810 ÷ 1800 Ah
1080 ÷ 2400 Ah
35
mm
2
25
mm
2
35
mm
2
120
mm
2
95
mm
2
120
mm
2
EQUIPMENT NECESSARY FOR INSTALLATION
Depending upon model, use the batteries and cables on the output terminals as specified in the following table:
Regarding the lengths of the output cables with several battery chargers connected in parallel, refer to the diagram
in figure 2C.
The cables connected to the output terminals have a maximum length of 4 metres. (With single battery charger).
MODEL
Battery voltage
Battery capacity
Minimum output cable size
SBC 1100 ADV PLUS FR
SBC 1450 ADV PLUS
SBC 1950 ADV PLUS
12 V
24 V
360 ÷ 800 Ah
270 ÷ 600 Ah
360 ÷ 800 Ah
35
mm
2
25
mm
2
35
mm
2