B.E.S. - BOWLER ENTERTAINMENT SYSTEM
Pre-Installation Manual
Copyright 2007 Qubica S.p.A.
March 2007 – rev. 2B
5
A. Electrical Requirements
The bowling center proprietor is responsible for the materials and installation of all AC and
grounding requirements. All electrical installations must conform to all local and state codes,
statutes or standards defined by local jurisdiction and/or inspections.
All electrical circuit panels should be installed using a dedicated distribution circuit panel with
an isolated third wire (green) equipment tie down buss. These circuits must not share a panel
that is or will be used as a power source for any device other than Qubica automatic scoring
equipment. The dedicated distribution panel should get its power source from at least a building
main sub panel, but the main panel is recommended.
Where TV is used, check that the antenna or CATV cable are properly grounded.
Dedicated panel to service entrance ground buss is restrictive as follows:
•
If the total length of the buss is 200 feet or less, use a number 6 AWG – 4 mm Ø wire
for entire buss.
•
If the total length of the buss is 200 feet to 400 feet, use two sections. Use number 4
AWG - 5 mm Ø wire for the first section from the ground connection to the first unit,
then use number 6 AWG - 4 mm Ø wire for the remainder.
A.1
System Components
A.1.1
RDB Graphic Unit
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit for each couple of RDB units (4 lanes) is
required.
US Only - Three wire circuit with continuous insulated third wire (Green) equipment ground
connecting to the service entrance positive earth ground for each group of four lanes is required.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
RDB electrical specs: 100-240V, 1.6-0.6A, 50-60Hz.
A.1.2
RDB Graphic Unit with LCD Consoles
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit for each couple of RDB units (4 lanes) is
required.
US Only - Three wire circuit with continuous insulated third wire (Green) equipment ground
connecting to the service entrance positive earth ground for each group of four lanes is required.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
RDB electrical specs: 100-240V, 1.6-0.6A, 50-60Hz.
The LCD Consoles are powered by the Q-AC-PWR located on the curtain wall
A.1.3 RDB
Network
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit for for each group of thirty lanes or each
separate group of lanes is required.
US Only - Three wire circuit with continuous insulated third wire (Green) equipment ground
connecting to the service entrance positive earth ground for each group of four lanes is required.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
A.1.4 Overhead
Monitors
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit for for each group of four lanes is required.