A typical Q256 512x512 installation is shown below. With four Q256 units the power density is high and
there is 6.5KW of heat to be dissipated. The cooling air is drawn from right to left so in this example racks A
and C will be getting the hot exhaust air from racks B and D. To avoid this ensure that the inter-rack spacing
is as large as possible and install a metal baffle between the routers. Ideally this should be the same size as
the router side panel and placed centrally in the gap between the routers.
43U Rack
43U Rack
512x512 Front View
‘A’ Chassis
‘C’ Chassis
‘B’ Chassis
‘D’ Chassis
512x512 Rear View
‘B’ Chassis
‘D’
Chassis
‘A’ Chassis
‘C’
Chassis
Cooling
air
Cooling
air
Baffle
"A" Chassis
"B" Chassis
"C" Chassis
"D" Chassis
Issue 1.72
edited: 26 Sept 2005
Page 28