-3-
OPTIONAL CONTROL VALVES
2 port on/off valves or 4 port diverting valves are available as factory fitted options.
(4 port modulating valves are also available - contact TEV Technical Sales Department).
2 pipe cool only systems require one valve per fan coil.
2 pipe heat/cool systems (supplied from a reverse cycle chiller, or c boiler) require one valve: if using an
auto changeover thermostat, they also need a means of signalling heating or cooling status of the flow eg a pipe
thermostat (kit shown on page 23).
4 pipe systems require two valves (but no pipe thermostat is needed).
VALVE POSITIONS
ELECTRICAL LOADS (A)
CWM (L)
Fan motor
Electric heater
55
0.4
5.2
75
0.4
7.2
105
0.5
9.2
OPTIONAL ELECTRIC HEATING (kW)
CWM (L)
240V 50Hz
230V 50Hz
55
1.3
1.2
75
1.8
1.7
105
2.3
2.1
AIRFLOWS (m³/s)
CWM (L)
LOW SPEED
MEDIUM SPEED
HIGH SPEED
55
0.17
0.19
0.28
75
0.24
0.31
0.37
105
0.25
0.34
0.49
COIL WATER VOLUMES (Litres)
CWM (L)
Chilled water coil
LPHW coil
55
1.6
0.18
75
2.0
0.24
105
2.5
0.30