Appendices:
Page 14
PM9605 Revision 1, 9605 Version 36.1.1
Appendix C: Installation
The 9605 is designed to be mounted in the door of an enclosure or on an operators console for ease of use. A
template is provided to assist in the drilling and cutting of the mounting holes for the unit. Care should be taken to
protect the unit from metal chips and conductive particles. Failure to protect the unit may cause damage when
power is applied and may void warranty.
A minimum clearance of six inches should be kept between the unit and any other device that generates heat. In
the event that the internal enclosure temperature periodically exceeds 55 degrees Celsius (131 degrees
Fahrenheit), fans or a purge air system should be used to increase the air flow, and eliminate "Hot Spots" that
occur within the panel.
Electrical Requirements
Power to the 9605 must be provided by an external power supply meeting the following requirements:
Output voltage: 5.1 VDC to 5.3 VCD at 30 mV max. ripple.
Output current: 450 mA (Minimum) .
Quartech Model 8552 power supply is an excellent choice for most applications.
Environment:
Operating Temperature: . . . . . . . . . . . . 0°c to 60°c
Storage Temperature . . . . . . . . . . . . . . -20°c to 70°c
Operating Humidity . . . . . . . . . . . . . . . . 0% to 95% (non-condensing)
Storage Humidity . . . . . . . . . . . . . . . . . 0% to 95% (non-condensing)
Vibration (10Hz to 55Hz) . . . . . . . . . . . Displacement: 0.5mm, Constant X,Y,Z axis
Shock . . . . . . . . . . . . . . . . . . . . . . . . . . 40G
Wiring Considerations
Care should be taken when routing DC power supply cable and the communication cable. Follow these guidelines
for a trouble free installation.
‚
The power supply should be mounted as close as possible to the 9605. If the 9605 is to be mounted a
long distance from the SLC-500, the power supply should be mounted local to the 9605 to allow short
supply cables.
‚
Use at least 16 AWG wire for the 5 VDC power supply cable. If the 9605's power source
must be 10 ft or longer 14 AWG wire should be used. Do not make a power supply cable
longer than 20 ft.
‚
The DC power lines and communication cable must be kept away from AC power lines. Keep both at
least one foot away from 120 VAC lines, and two feet away from higher voltage lines. This especially
applies to the communication cable. If the cables must cross AC power lines, cross them at right angles
(90°).
‚
Keep the cables away from sources of high energy fields such as arc welders, AC motors, motor starters,
servo controllers, generators, induction heaters, and transformers.