32
CANopen
HBM
QuantumX
Sensor calibration period
Object description
Index
611B (hex)
24859 (dec)
This value provides the recommended time
period between transducer calibrations The
Object name
AI sensor calibration period
period between transducer calibrations. The
value may be added to the calibration date
Object code
Array
value may be added to the calibration date
to calculate the date for the next calibration.
Data type
Time difference
The calibration period is also defined in
IEEE14514
CiA standard
Yes
IEEE14514.
Value description
Sub
-
index
0 (hex)
1 (hex)
2 (hex)
to
C7 (hex)
Description
Number of entries
AI sensor
calibration period 1
AI sensor
calibration period 2
AI sensor calibration
period 199
Entry category
Mandatory
Mandatory
Optional
Optional
Access
ro
ro
ro
ro
PDO mapping
No
No
No
No
Value range
1
−
199
see CiA301
see CiA301
see CiA301
Default value
No
No
No
No
AI TEDS control
Object description
Index
611C (hex)
24860 (dec)
Object name
AI_TEDS_control
Object code
Array
Data type
UINT8
CiA standard
To be incorporated
Value description
Sub
-
index
−
Description
Controls the handling of TEDS and non-TEDS sensors in the DAQ system
Access
rw
PDO mapping
possible
Values
0
Ignore TEDS
Means that the DAQ system will not use the
data stored in the sensor to adapt the settings.
2
Use TEDS if
available
Means that the DAQ system will use the TEDS
data to setup the DAQ. But if there is no TEDS
available in the sensor, the DAQ system will not
go to an error state.
3
TEDS required
Means that the DAQ has to use the TEDS data.
If there is no TEDS data available, the DAQ
system indicates an error.
Default value
−
Содержание CX27
Страница 1: ...I2720 2 0 en Operating Manual CX27 Gateway ...
Страница 2: ...d ...
Страница 4: ...4 HBM QuantumX 10 Abbreviations 54 11 Support 55 ...
Страница 55: ...55 Support HBM QuantumX ...