Page 19
Yosemite Wood Stove
R
7004-187L
October 13, 2015
C. Installing Chimney Components
Chimney Connector
Single wall connector or stove pipe.
This must be at least 24 gauge mild steel or 26 gauge blue
steel. The sections must be attached to the appliance and
to each other with the crimped (male) end pointing toward
the stove. All joints, including the connection at the fl ue
collar, should be secured with 3 sheet metal screws. Make
sure to follow the minimum clearances to combustibles.
Where passage through the wall, or partition of combustible
construction is desired in Canada, the installation shall
conform to CAN/CSA-B365.
Factory-built listed chimney connector (vented).
A listed connector (vented) must be used when installing
this unit in a mobile home. The listed connectors must
conform to each other to ensure a proper fi t and seal.
Flue Gas
Direction
Crimped
End
Toward
Stove
Secure pipe sections with a
minimum of 3 screws
Figure 19.2 Chimney Connector (Stove Pipe)
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer
to the owner’s information manual provided with this appli-
ance. For assistance or additional information consult a
qualifi ed installer, service agency or your dealer.
WARNING
WARNING
ONLY use connector:
• Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
• Attic or roof space
• Closet or similar concealed space
• Floor or ceiling
Maintain minimum clearances to combustibles
Fire Risk.
Follow Chimney Connector Manufacturer’s
Instructions for Proper Installation.
Thimble Assembly:
12 in. (305mm) of
brick separation
between clay liner
and combustibles.
Fireclay liner 5/8 in.
(16mm) Minimum
or Equivalent.
Sill support
Header
Wood Stud 2 in.
(51mm)
Clearance from
chimney wall
Fireclay liner 5/8 in.
(16mm) Minimum
or Equivalent.
Figure 19.1
Masonry Chimney Liner (Cont'd)
Horizontal Flue Heat Shield, Accessory Part
HTSHLD-7006 is required for rear vent instal-
lations.
Optional Fire Screen, part SCR-7006, can only
be used in full vertical installations.