SANTA FE FREESTANDING
E. Masonry
F. Alternate Masonry
Figure 19.1
Figure 19.2
Non-combustible Hearth Pad
Airtight
Cleanout Door
Cleanout cover
Sheathing
3 in. (76mm) Minimum
1 in. (25mm) Clearance
Flashing
Fireclay flue
Liner with Airspace
Concrete Cap
1 in. (25mm) Clearance
with Firestop
6 in. (152mm)
Minimum
Non-combustible
Hearth Pad
Airtight Clean-out
Door
Sheathing
2 in. (51mm) Minimum
Flashing
1 in. (25mm) Clearance
1 in. (25mm)
Clearance with
Firestop
6 in. (152mm) Minimum
Fireclay Flue Liner
with Airspace
Concrete Cap
Fire Risk
Inspection of Chimney:
• Masonry chimney must be in good
condition.
•
Meets minimum standard of NFPA 211
•
Factory-built chimney must be a minimum
6 inch (152mm) UL103 HT.
WARNING