SANTA FE FREESTANDING

EMBER PROTECTION: 

It is necessary to install a Type I 

floor protector.

Floor protector must be non-combustible material, 

extending beneath appliance 

with a minimum of 6 

inches 

(152mm) in front of glass and 6 inches (152mm) to both 

sides of the fuel loading door. Open the door and measure 

6 inches (152mm) from the side edge of the opening in the 

face of the appliance.*

See exception. 

27 in

minimum

26-1/2 in 

minimum

6 in

from the fuel door 

opening

6 in

USA

15 in

6 in

FUEL DOOR OPENING

152MM

FROM FUEL DOOR 

OPENING

152MM

686mm

minimum

673mm

 minimum

CANADA

Must extend 51mm 

beyond each side 

of pipe (shaded area) 

to the wall thimble.

152MM

FUEL DOOR OPENING

USA INSTALLATIONS

: A

 non-combustible floor protection 

is recommended extending beneath the flue pipe when 

installed with horizontal venting or under the Top Vent 

Adapter with vertical installation.

CANADA INSTALLATIONS

: A non-c

ombustible floor 

protection 

extending beneath the flue pipe 

is 

required

 

with horizontal venting or under the Top Vent Adapter with 

vertical installation.

Figure 11.1

Figure 11.2

39-5/8 in

22-3/4 in

15 in

32-1/4 in

6 in.

from the fuel door 

opening

USA

1006mm

578mm

381mm

819mm

152mm

(front door opening)

CANADA

Must extend 51mm 

beyond each side 

of pipe (shaded area) 

to the wall thimble.

Figure 11.3

Figure 11.4

C. Hearth Pad Requirements (UL and ULC)

Fire Risk

Comply with all minimum clearances to 

combustibles as specified.

Failure to comply may cause house fire.

WARNING

Содержание SANTA FE SANTAFE-C

Страница 1: ...e could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If ap...

Страница 2: ...6 5 Venting Systems A Through The Wall 17 B Vertical into Existing Class A Chimney 18 C Through The Wall Vertical Exterior 18 D Vertical Interior Typical Installation 18 E Masonry 19 F Alternate Mason...

Страница 3: ...er operation It is against federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certification...

Страница 4: ...f such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause birth d...

Страница 5: ...to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdicti...

Страница 6: ...on to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally required...

Страница 7: ...n and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appli...

Страница 8: ...1mm 28 3 4 in 730mm 9 7 8 in 251mm 12 3 4 in 324mm 3 3 4 in 95mm 6 7 8 in 175mm 2 1 2 in 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top...

Страница 9: ...set Adapter 812 3570 18 1 4 in 464mm 21 in 533mm 16 3 4 in 427mm 28 3 4 in 730mm 26 7 8 in 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View wit...

Страница 10: ...rner Installation Inches Millimeters G Side Wall to Appliance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter wit...

Страница 11: ...area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the...

Страница 12: ...um Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installation...

Страница 13: ...ences and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted i...

Страница 14: ...ance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pel...

Страница 15: ...vertically or horizontally NOTE Follow venting manufacturers recommendations for sealing pipe joints NOTICE Hearth Home Technologies assumes no responsibility for the improper performance of the chimn...

Страница 16: ...t intended to represent any specific fuel type G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated previously and the...

Страница 17: ...or mobile home installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage throu...

Страница 18: ...76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations are a...

Страница 19: ...oncrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance with Fi...

Страница 20: ...ps head screwdriver wire cutters hole saw or jig saw 1 Measure distance from floor to air vent opening in appliance and mark location on wall Use a saw to cut opening in wall Cut a 2 1 2 to 3 inch 64...

Страница 21: ...e silicone on the 3 inch 76mm exhaust outlet Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Insta...

Страница 22: ...see Figure 22 4 TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUTLET Figure 22 1 Figure 22 2 Figure 22 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the...

Страница 23: ...PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 23 1 WARNING Products of combustion generate carbon monoxide and different fue...

Страница 24: ...24 09 20 7050 801E SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Страница 25: ...25 09 20 7050 801E SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Страница 26: ...apter 90 Cleanout TPVNT 6 Vent Adapter Rear 811 0620 Damper 3 inch PEL DAMP3 Y Damper 4 inch PEL DAMP4 Additional service part numbers appear on following page IMPORTANT THIS IS DATED INFORMATION Part...

Страница 27: ...of 24 226 0130 24 Y Pin 3 16 x 1 2 7000 229 Rivet Iron 1 4 X 1 1 4 Pkg of 25 229 0090 25 Screw 8 32 X 1 4 Qty 40 225 0240 40 Screw Hwh 1 4 20 X 3 4 Ns Pkg of 25 220 0080 25 Y Screw Flat Head Screw 1 4...

Страница 28: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Отзывы: