background image

Page  4

7050-128G

May 12, 2014

Santa Fe Pellet Stove 

R

1

Listing and Code Approvals

A.  Appliance Certifi cation

C.  Glass Specifi cations

E.  BTU & Effi ciency Specifi cations

This appliance is equipped with 5mm ceramic glass. 

 

Replace glass only with 5mm ceramic glass.  Please contact 
your dealer for replacement glass.

This appliance is approved for mobile home installations 
when not installed in a sleeping room and when an outside 
combustion air inlet is provided.  

The structural integrity of the mobile home fl oor, ceiling, and 
walls must be maintained.  The appliance must be properly 
grounded to the frame of the mobile home and use only listed 
pellet vent Class “L” or “PL” connector pipe.  

A Quadra-Fire Outside Air Kit must be installed in a mobile 
home installation.

Note:  The appliance is also approved for installation 
into a shop.

B.  Mobile Home Approved

NOTE:  

This installation must conform with local codes. In 

the absence of local codes you must comply with the 

ASTM 

E1509-95, ULC S627-00, ULC/ORD-C-1482-M1990, 
(UM) 84-HUD, 

D.  Electrical Rating

115 VAC, 60 Hz, Start 4.1 Amps, Run 1.1 Amps

NOTE:  

Hearth & Home Technologies, manufacturer of 

this appliance, reserves the right to alter its products, 
their specifi cations and/or price without notice.

Model:

Santa Fe Pellet Stove

Laboratory:

OMNI Test Laboratories, Inc.

Report No.

061-S-77d-6.2

Type:

Solid Fuel Room Heater/Pellet 
Fuel Burning Type

Standard:

ASTM E1509-04 and ULC S627-
00, ULC/ORD-C1482-M1990 
Room Heater Pellet Fuel Burn-
ing type and (UM) 84-HUD, 
Mobile Home Approved.

The Santa Fe Pellet Stove by Quadra-Fire is exempt from 
Environmental Protection Agency certifi cation under 40 CFR 
60.531 by defi nition [Wood Heater (A) “Air to Fuel Ratio].

WARNING! Risk of Fire! Hearth & Home Technologies dis-
claims any responsibility for, and the warranty and agency 
listing will be voided by the below actions.

DO NOT:
 

•  Install or operate damaged appliance

 • 

Modify 

appliance

 

•  Install other than as instructed by Hearth & Home 

Technologies

 

•  Operate the appliance without fully assembling all 

components

 • 

Overfi re

 

•  Install any component not approved by Hearth & 

Home Technologies

 

•  Install parts or components not Listed or approved

 

•  Disable safety switches

Improper installation, adjustment, alteration, service or 
maintenance can cause injury or property damage. 

For assistance or additional information, consult a qualifi ed 
installer, service agency or your dealer.

NOTE:  Some generator or battery back-up systems 
may not be compatable with the micro-processor elec-
tronics on this appliance.  Please consult the power 
supply manufacturer for compatable systems.

*BTU output will vary, depending on the brand of fuel you 
use in your appliance.  Consult your Quadra-Fire dealer for 
best results.

Particulate 
Emissions Rating:

1.8 grams/hr

*BTU Output:

8,500 - 28,200 / hr

Heating Capacity:

up to 1,500 sq. ft. depending on 
climate zone

Hopper Capacity:

45 lbs

Fuel:

Wood Pellets or Shelled Corn

Shipping Weight:

214 lbs

Effi ciency

78%

These heaters meet the US Environmental Protection 
Agency’s emissions limits for pellet heaters. Under specifi c 
conditions the PS35 stove has been shown to deliver heat 
at rates ranging from 8,500 to 28,200 BTU/hr.

Содержание Santa Fe Pellet Stove

Страница 1: ...ly Burning of any other type of fuel voids your warranty CAUTION O T L Tested and Listed by Portland Oregon USA OMNI Test Laboratories Inc C US SAVE THESE INSTUCTIONS CAUTION Important operating and m...

Страница 2: ...TOUCHER GARDEZLESENFANTSETLESV TEMENTSLOINDE L ESPACE D SIGN DE L INSTALLATION LE CONTACT PEUT CAUSER DES BR LURES LAPEAU VOIR L TIQUETTE ET LES INSTRUCTIONS Op rez cet appareil avec le couvercle de l...

Страница 3: ...hermostat Installation 22 Section 8 Operating Instructions A Combustible Non Combustible Material 23 B Fuel Size Material Storage 23 C General Operation Information 24 D Before Your First Fire 24 E St...

Страница 4: ...ype and UM 84 HUD Mobile Home Approved The Santa Fe Pellet Stove by Quadra Fire is exempt from Environmental Protection Agency certification under 40 CFR 60 531 by definition Wood Heater A Air to Fuel...

Страница 5: ...oca tion of the vent termination CAUTION If burning shelled field corn you must use ap proved venting specifically designed for corn to prevent corro sion or degradation Follow the instructions from t...

Страница 6: ...ppliance is drafting successfully all combustion byproducts are exiting the home through the chimney Considerations for successful draft include Preventing negative pressure Location of appliance and...

Страница 7: ...side wall vented The air intake is best located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply mo...

Страница 8: ...terials have been met 8 The masonry chimney is inspected by a profes sional and is clean or the factory built metal chimney is installed according to the manufac turer s instructions and clearances 9...

Страница 9: ...Dimensions Figure 8 2 Front View Figure 8 1 Top View Figure 8 3 Side View Figure 8 4 Side View with Top Vent Adapter 25 1 2 in 658mm 12 3 4 in 324mm 21 1 4 in 540mm 28 11 16 in 729mm 16 3 4 in 426mm 2...

Страница 10: ...Appliance 2 51 H Side Wall to Flue Pipe 3 76 Alcove Installation Inches Millimeters Minimum Alcove Height 43 1092 Minimum Alcove Side Wall 6 152 Minimum Alcove Width 38 965 Maximum Alcove Depth 36 914...

Страница 11: ...LATIONS A non combustible floor pro tection extending beneath the flue pipe is required with horizontal venting or under the top vent adapter with vertical installation Must extend 2 inches 51mm beyon...

Страница 12: ...vertical pipe be installed when appliance is vented directly through a wall This will create a natural draft which will help prevent the possibility of smoke or odor venting into the home during a po...

Страница 13: ...ll need to be cleaned more often Try to keep them as short as possible ONE 90 ELBOW Total Horizontal Minimum Vertical Vent Diameter 4 0 3 5 5 3 6 6 3 7 7 3 8 8 4 9 9 4 10 10 4 11 11 4 12 12 4 13 13 4...

Страница 14: ...ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference A Alcove Figure 14 1 All minimums listed are to a combustible surface Minimum Maximu...

Страница 15: ...llet pipe Follow stove pipe manufactures listed air clearances to combustibles and installation instructions for all reduced air clearances installations D Vertical into Existing Class A Chimney C Thr...

Страница 16: ...Non combustible Hearth Pad Airtight Cleanout Door Cleanout cover Sheathing 3 in 76mm Minimum 1 in 25mm Clearance Flashing Fireclay flue Liner with Airspace Concrete Cap 1 in 25mm Clearance with Firest...

Страница 17: ...shows venting going in both directions Choose which one is best for your installation 2 in 51mm Minimum 2 in 51mm Minimum 6 in 152mm Minimum 6 in 152mm Minimum Straight Out 6 in 152mm Minimum Non comb...

Страница 18: ...tructions when installing the vent system for use in a mobile home 8 Installation shall be in accordance with the Manufactur ers Home Safety Standard HUD CFR 3280 Part 24 Installation must comply with...

Страница 19: ...ut opening in wall Cut a 2 1 2 to 3 inch 64 76mm opening on inside wall and a 3 to 3 1 2 inch 76 89mm opening on outside of house 2 Remove cover plate and then install the collar assem bly 3 Use hose...

Страница 20: ...ws Figure 20 1 6 Install the vent pipe into the top vent adapter be sure to silicone all joints 7 To clean the top vent adapter open the clean out cover Figure 20 2 B Top Vent Adapter Installation Sil...

Страница 21: ...stalled on the grilles and after the grilles are installed on the appliance they are then finger bent into position 3 Attach the 4 grille bracket covers to the lower 4 grilles and the top 3 grilles Sl...

Страница 22: ...programmable thermostat or remote control It is equipped with an adjustable heat anticipator The current rating is 05 amps The anticipa tor needs to be adjusted to the lowest setting available 2 When...

Страница 23: ...bris Never burn corn straight from the field it will clog the auger mechanism Corn with excessive grain dust must be screened by sifting with 3 16 4 76mm inch mesh screening Do not use corn that conta...

Страница 24: ...en set the thermostat to the desired room temperature Adjust the heat output control switch to the desired setting NOTE We recommend the use of a 50 50 blend of corn and wood pellets The only change i...

Страница 25: ...rod upward towards the symbol to increase the feed rate and flame height or down towards the symbol to decrease the feed rate and flame height 4 Re tighten the wing nut Feed Adjustment Control Rod Set...

Страница 26: ...he firepot is dirty or there is too much fuel at start up and not enough air Close down feed rate 1 4 inch 6 35mm at a time until this no longer happens 6 Large flame at start up 6 This is normal Flam...

Страница 27: ...sure venting system is clean Make sure front door is closed Replace control box Call light on No fire Partially burned fuel in firepot Firepot clean out plate not closed Firepot is dirty missed ignit...

Страница 28: ...ox causing loss of vacuum Empty hopper of fuel Use a wet dry vacuum cleaner to remove remaining fuel from hopper including feed tube Check feed chute for obstructions Loosen 2 screws and jiggle feed a...

Страница 29: ...ick panels Change fuel brand to premium Check that firepot clean out plate is fully closed Reduce feed rate using feed rate adjustment control rod located inside hopper Nuisance shutdowns Low flame Sa...

Страница 30: ...Every 5 bags or more fre quently depending on the fuel type or ash build up OR X Beneath Heat Exchanger Every 1 ton of fuel OR X Blower Combustion Exhaust More frequently depending on the fuel type O...

Страница 31: ...rebox during cleaning so allow the appliance to completely cool The firebox ash should be removed every time the exhaust path is cleaned Frequent cleaning of the ash in the firebox will help slow down...

Страница 32: ...leaning 8 Cleaning the Exhaust Path Frequency Every 25 bags or monthly or more fre quently depending on ash build up By Homeowner a Appliance must be completely cool b Open cast hinge face Remove baff...

Страница 33: ...No Lubrication Frequency Yearly or as needed By Qualified Service Technician Task Contact your local dealer 12 Door Latch Inspection Frequency Prior to heating season By Homeowner The door latch is n...

Страница 34: ...the firepot overfills pellets back up into the feed tube and ash has accumulated in the firebox An inefficient and non economical method of burning of fuel caused by poor quality pellet fuel is shown...

Страница 35: ...ires together F Blower Replacement 2 Combustion Blower Replacement a Turn down the thermostat let appliance completely cool and then unplug appliance before servicing b Remove both upper and lower sid...

Страница 36: ...located in the hopper along the back Figure 36 1 Remove the rear screen of the appliance be sure the vent is disconnected by removing the seven screws Lift slightly upwards as to not damage the hoppe...

Страница 37: ...and re connect the power Thumb Screw Igniter Firepot Figure 37 1 H Baffle Brick Set Removal 1 Follow proper shutdown procedures in Section 10 2 The top baffle has a hook on the bottom left side that...

Страница 38: ...e flush against the back wall and the braket s notches will be exposed Figure 38 2 3 Pull the right edge of the brick forward and slide the brick into the notches both top and bottom of right bracket...

Страница 39: ...ottom and remove the rod Repeat for other side 3 Remove old glass and replace with new glass 4 Slide the retainer rod into the top hole first and then line up the bottom crimped end with the hole in t...

Страница 40: ...ting the preset temperatures of the green and red lights have been obtained When describing the location of a component it is always AS YOU FACE THE FRONT OF THE APPLIANCE 2 Convection Blower The conv...

Страница 41: ...et itself 19 Snap Disc 3 Back Burn Protector 250 F Snap disc 3 is mounted on the back of the auger tube in the center of the appliance and has a reset button To access it remove the right side panel I...

Страница 42: ...Fuse Control Box Vacuum Switch Junction Box High Med Low Heat Output Switch Reset Button Reset Button Combustion Blower Convection Blower TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUT...

Страница 43: ...November 21 2011 7050 128F Page 43 Date of Service Performed By Description of Service C Service And Maintenance Log...

Страница 44: ...Page 44 7050 128G May 12 2014 Santa Fe Pellet Stove R Date of Service Performed By Description of Service Service And Maintenance Log Cont d...

Страница 45: ...R May 12 2014 7050 128G Page 45 Santa Fe Pellet Stove D Warranty Policy...

Страница 46: ...Page 46 7050 128G May 12 2014 Santa Fe Pellet Stove R...

Страница 47: ...R May 12 2014 7050 128G Page 47 Santa Fe Pellet Stove...

Страница 48: ...and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instruc tions for safe installa tion and operation DO NOT DISCARD...

Отзывы: