F.  Installing Adaptor and Termination Cap

For installation of termination cap see minimum vent 
heights for various pitched roofs (see Figure 8.5) . 

To install adaptor see Figure 8.6. 

Roof Pitch       H (Min.) Ft.
Flat to 6/12....................1.0*
Over 6/12 to 7/12 ........1.25*
Over 7/12 to 8/12 ..........1.5*
Over 8/12 to 9/12 ..........2.0*
Over 9/12 to 10/12 ........2.5*
Over 10/12 to 11/12 ..... 3.25

Figure 8.5  Minimum Height from Roof to Lowest Discharge  
 Opening

* 3 foot minimum in snow regions

Roof Pitch       H (Min.) Ft. 
Over 11/12 to 12/12 ....... 4.0
Over 12/12 to 14/12 ....... 5.0
Over 14/12 to 16/12 ....... 6.0
Over 16/12 to 18/12 ....... 7.0
Over 18/12 to 20/12 ....... 7.5
Over 20/12 to 21/12 ....... 8.0

CLASS A PIPE

Figure 8.6    

CAUTION! Risk of Cuts/Abrasions/Flying Debris. 
Wear protective gloves and safety glasses during instal-
lation. Sheet metal edges are sharp.

Damper Flashing Kit 

(Optional)

For use with LINK-DV4-30B Liner Kit.

Note

:  Damper may have to be removed to use this kit.

• Run fl ex liners through 3” holes in damper fl ashing.

• Attach damper fl ashing to fi rebox roof with self tapping 

screws included in kit.

Figure 8.7

To prevent odors and cold drafts, the chimney must be 
sealed around the vent with non-combustible blanket in-
sulation or fi eld fabricated metal plates.

Note

: The LINK-DV4-30B system REQUIRES this 

insulation.

Masonry

Factory Built 

Wood Burning

EXHAUST

AIR

VENT PIPE 

TERMINATION 

CAP 

SEAL  GAP 

AROUND FLEX PIPE

LINK-DV30B

Installation

LINK-DV4-30B

Installation

INLET AIR 

VENT PIPE 

WARNING: 

DO NOT BLOCK 

THIS PIPE END! 

Note: Untwist the pipe 
while extending it, to 
achieve full 30’ length.

EXHAUST

AIR

VENT PIPE

INLET AIR

VENT PIPE

Remove 18 inch x 18 inch fl ashing on cap by removing 3 
screws. Connect both the LINK-ZC-ADPB to Class A Pipe 
and the termination cap to the LINK-ZC-ADPB with the 
self tapping screws provided.

OPTIONAL LINK-ZC-ADPB

FOR USE WITH CLASS A

WOODBURNING PIPE

OR

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT 
TERMINATION CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Содержание QVI-35FB-S

Страница 1: ...ated on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or techn...

Страница 2: ...e Information Model Number Not for use with solid fuel Ne doit pas entre utilise avec un combustible solide This appliance must be installed in accordance with local codes if any if not follow ANSI Z2...

Страница 3: ...B Design and Installation Considerations 16 C Tools and Supplies Needed 16 D Inspect Appliance and Components 16 5 Fireplace Size Requirements A Minimum Fireplace Opening 17 B Mantel and Wall Project...

Страница 4: ...under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular ma...

Страница 5: ...and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warranty...

Страница 6: ...als E Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or pla...

Страница 7: ...ed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch g...

Страница 8: ...roperly install one For more information refer to the instructions supplied with your decorative door or front F Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with t...

Страница 9: ...er to www fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance area for...

Страница 10: ...n will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the appliance is al lowed to burn for 20 to 40 minutes Odor from appliance When first operated...

Страница 11: ...d before servicing When properly maintained your appliance will give you many years of trouble free service We recommend an nual service by a qualified technician Doors Surrounds Fronts Frequency Annu...

Страница 12: ...rowing Cracks that penetrate entirely through the firebrick material Inspection for cracking should be run when the appliance is cool Cracks tend to close as the appliance heats up Control Compartment...

Страница 13: ...Quadra Fire QVI 35FB S 2178 900 Rev B 12 08 13 Figure 3 1 Standing Pilot Flame Patterns...

Страница 14: ...y Illustrations diagrams are not drawn to scale Actual product may vary from pictures in manual VERTICAL TERMINATION CAP SECTION 8F VENT PIPE SECTION 8 MANTEL AND MANTEL LEG SECTIONS 5 11 SURROUND HEA...

Страница 15: ...12 08 15 VERTICAL TERMINATION CAP SECTION 8F VENT PIPE SECTION 8 MANTEL AND MANTEL LEG SECTIONS 5 11 SURROUND HEARTH EXTENSION GAS LINE SECTION 9 ACCESS THROUGH EXISTING MASONRY OR WOODBURNING FIREPLA...

Страница 16: ...shipped in separate packages If packaged separately the log set and appliance grate must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read a...

Страница 17: ...mm A C TOP VIEW D FRONT VIEW MINIMUM FIREPLACE SIZE Location QVI 35FB S Inches Millimeters A Front Width 35 889 B Rear Width 22 5 8 574 7 C Depth 14 1 8 358 8 D Height 25 3 4 654 Note If exhaust coll...

Страница 18: ...ing to combustibles is 6 inches 152 mm Clearance from top of fireplace opening 152 mm to combustibles extending 1 inch is 6 inches Clearance from top of fireplace opening for combustibles extending 1...

Страница 19: ...2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with i...

Страница 20: ...o gas access hole provided an access hole of 1 inch 25 mm diameter or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner This access hole must be...

Страница 21: ...ney flue serving a separate solid fuel or gas burning appliance May impair safe operation of this appliance or other appliances connected to the flue Vent this appliance directly outside Use separate...

Страница 22: ...s or failure to use only parts specifically approved with this appliance may result in property damage or personal injury WARNING Risk of Explosion Combustion Fumes Connect vent sections per installat...

Страница 23: ...Run flex liners through 3 holes in damper flashing Attach damper flashing to firebox roof with self tapping screws included in kit Figure 8 7 To prevent odors and cold drafts the chimney must be seal...

Страница 24: ...on DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING...

Страница 25: ...cal codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 Wire the appliance junction box to 110 120 VAC This is required for use of optional accessorie...

Страница 26: ...eration after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation D Fan Replacement On units already installed removal of decorat...

Страница 27: ...MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 1050 C RATED WIRE JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT...

Страница 28: ...es is 6 inches 152 mm Clearance from top of fireplace opening 152 mm to combustibles extending 1 inch is 6 inches Clearance from top of fireplace opening for combustibles extending 1 inch to 12 inches...

Страница 29: ...ver burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CA...

Страница 30: ...LOG NUMBER 1 SRV768 701 Place log 1 onto the grate Push log back until it rests against locating tabs A and B Slide the log all the way to the left until the notches on the bottom of the log contact t...

Страница 31: ...log Push down until log is sitting flat on grate LOG NUMBER 2 SRV768 704 Position log 2 onto grate such that tab C fits into the slot on the bottom surface of the log The right side of the log rests...

Страница 32: ...0 Rev B 12 08 32 LOG NUMBER 4 SRV582 705 Place log 4 across both flat spots on log 1 and log 3 with the Y in log 4 placed on log 1 The back of log 4 should make contact with the back of the firebox 1...

Страница 33: ...cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Removing Fixed Glass Assembly Ther...

Страница 34: ...onnection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the thermocoupl...

Страница 35: ...ld read 10 14 inches w c c Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections d Glass installed improperly Che...

Страница 36: ...in 350 mm 3 1 8 in 80 mm 6 5 8 in 169 mm Two 2 13 16 in 71 mm 9 9 16 in 142 mm REF 14 14 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference...

Страница 37: ...cessory Kits Direct Vent Flex Liner Accessory Kits see Figure 15 3 Flash Damp Zero clearance damper flashing kit for use with LINK DV30B or LINK DV4 30B liner kits LINK ZC ADP Zero clearance chimney a...

Страница 38: ...2178 900 Rev B 12 08 38 C Service Parts QVI 35FB S Beginning Manufacturing Date Dec 2008 Ending Manufacturing Date ______ Service Parts Diagram Part number list on following page Log Set Assembly 5 6...

Страница 39: ...46 7 Burner 768 188A Y 8 Log Grate 2178 007 9 Glass Door Assembly GLA FBG Y 10 Piezo Ignitor 291 513 Y 11 Control Panel Valve Cover Plate 783 125 12 Blower Assembly GFK 160A Fiber Patch Kit SRV PACK G...

Страница 40: ...ll parts listed in this manual may be ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 1 Pilot Assembly NG 2103 010 Y Pilot Assembly LP 2103 011 Y 2 Pilot Gaske...

Страница 41: ..._______________________________________________________ ________________________________________________________________________________ R This product may be covered by one or more of the following p...

Отзывы: