Installation Preparation 

 

Prepare the existing solid fuel masonry or factory built 
non-combustible fi rebox for installation.

A.  Inspection and Cleaning

Prior to installing the gas insert:

•  Have the chimney and adjacent structure inspected 

and cleaned by qualifi ed professionals. Hearth & Home 
Technologies recommends that NFI or CSIA certifi ed 
professionals, or technicians under the direction of certi-
fi ed professionals, conduct a minimum of a NFPA 211 
Level 2 inspection of the chimney.

•  Replace component parts of the chimney and fi replace 

as specifi ed by the professionals.

•  Ensure all joints are properly engaged and the chimney 

is properly secured.

•  Ensure combustible mantel and surround clearances 

comply with applicable codes and regulations for solid-
fuel fi replaces.  In the absence of local or regional codes, 
refer to NFPA 211.

•  Ensure chimney is constructed of non-combustible 

materials.

•  Ensure chimney is clean and in good working order.

•  Ensure that all chimney cleanouts fi t properly to prevent 

air leakage into chimney.

B. Flue Damper

Fully lock the solid fuel fi replace’s fl ue damper in the open 
position, OR completely remove it.

C. Gas Line

Note: 

If the factory built fi replace has no gas access hole 

provided, an access hole of 1 inch (25 mm) diameter or 
less may be drilled through the lower sides or bottom of the 
fi rebox in a proper workmanship - like manner. This access 
hole must be plugged with non-combustible insulation after 
the gas supply line has been installed.

•  Install gas line into fi rebox cavity.

•  Check local codes and gas line sizing requirements 

following NFPA54. See Section 8.

D.  Hearth or Hearth Extension

WARNING! Risk of Fire! A hearth or hearth extension (if 
present) must comply with either of the following:

•  The solid fuel burning fireplace manufacturer’s 

specifi cation.

•  Local building codes required by authority having 

jurisdiction.

• NFPA 

211

F.  Electrical Outlet Box

An outlet box may be installed in a bottom back corner of 
the fi replace to permit fans or other optional accessories 
to be used.  Alternatively, the supplied power cord may be 
routed out onto the hearth to a nearby outlet.

E.  Fireplace Conversion Notice

Permanently attach the label with the following warning to 
the inside lower back of the fi replace fi rebox into which the 
insert is being installed. Silicone or mechanical fasteners 
may be required to properly secure the label.

WARNING! Risk of Fire! This  fi replace has been con-
verted for use with a gas fi replace insert only and cannot 
be used for burning wood or solid fuels unless all original 
parts have been replaced, and the fi replace re-approved 
by the authority having jurisdiction.

Содержание QVI-35FB-S

Страница 1: ...ated on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or techn...

Страница 2: ...e Information Model Number Not for use with solid fuel Ne doit pas entre utilise avec un combustible solide This appliance must be installed in accordance with local codes if any if not follow ANSI Z2...

Страница 3: ...B Design and Installation Considerations 16 C Tools and Supplies Needed 16 D Inspect Appliance and Components 16 5 Fireplace Size Requirements A Minimum Fireplace Opening 17 B Mantel and Wall Project...

Страница 4: ...under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular ma...

Страница 5: ...and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warranty...

Страница 6: ...als E Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or pla...

Страница 7: ...ed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch g...

Страница 8: ...roperly install one For more information refer to the instructions supplied with your decorative door or front F Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with t...

Страница 9: ...er to www fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance area for...

Страница 10: ...n will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the appliance is al lowed to burn for 20 to 40 minutes Odor from appliance When first operated...

Страница 11: ...d before servicing When properly maintained your appliance will give you many years of trouble free service We recommend an nual service by a qualified technician Doors Surrounds Fronts Frequency Annu...

Страница 12: ...rowing Cracks that penetrate entirely through the firebrick material Inspection for cracking should be run when the appliance is cool Cracks tend to close as the appliance heats up Control Compartment...

Страница 13: ...Quadra Fire QVI 35FB S 2178 900 Rev B 12 08 13 Figure 3 1 Standing Pilot Flame Patterns...

Страница 14: ...y Illustrations diagrams are not drawn to scale Actual product may vary from pictures in manual VERTICAL TERMINATION CAP SECTION 8F VENT PIPE SECTION 8 MANTEL AND MANTEL LEG SECTIONS 5 11 SURROUND HEA...

Страница 15: ...12 08 15 VERTICAL TERMINATION CAP SECTION 8F VENT PIPE SECTION 8 MANTEL AND MANTEL LEG SECTIONS 5 11 SURROUND HEARTH EXTENSION GAS LINE SECTION 9 ACCESS THROUGH EXISTING MASONRY OR WOODBURNING FIREPLA...

Страница 16: ...shipped in separate packages If packaged separately the log set and appliance grate must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read a...

Страница 17: ...mm A C TOP VIEW D FRONT VIEW MINIMUM FIREPLACE SIZE Location QVI 35FB S Inches Millimeters A Front Width 35 889 B Rear Width 22 5 8 574 7 C Depth 14 1 8 358 8 D Height 25 3 4 654 Note If exhaust coll...

Страница 18: ...ing to combustibles is 6 inches 152 mm Clearance from top of fireplace opening 152 mm to combustibles extending 1 inch is 6 inches Clearance from top of fireplace opening for combustibles extending 1...

Страница 19: ...2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with i...

Страница 20: ...o gas access hole provided an access hole of 1 inch 25 mm diameter or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner This access hole must be...

Страница 21: ...ney flue serving a separate solid fuel or gas burning appliance May impair safe operation of this appliance or other appliances connected to the flue Vent this appliance directly outside Use separate...

Страница 22: ...s or failure to use only parts specifically approved with this appliance may result in property damage or personal injury WARNING Risk of Explosion Combustion Fumes Connect vent sections per installat...

Страница 23: ...Run flex liners through 3 holes in damper flashing Attach damper flashing to firebox roof with self tapping screws included in kit Figure 8 7 To prevent odors and cold drafts the chimney must be seal...

Страница 24: ...on DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING...

Страница 25: ...cal codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 Wire the appliance junction box to 110 120 VAC This is required for use of optional accessorie...

Страница 26: ...eration after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation D Fan Replacement On units already installed removal of decorat...

Страница 27: ...MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 1050 C RATED WIRE JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT...

Страница 28: ...es is 6 inches 152 mm Clearance from top of fireplace opening 152 mm to combustibles extending 1 inch is 6 inches Clearance from top of fireplace opening for combustibles extending 1 inch to 12 inches...

Страница 29: ...ver burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CA...

Страница 30: ...LOG NUMBER 1 SRV768 701 Place log 1 onto the grate Push log back until it rests against locating tabs A and B Slide the log all the way to the left until the notches on the bottom of the log contact t...

Страница 31: ...log Push down until log is sitting flat on grate LOG NUMBER 2 SRV768 704 Position log 2 onto grate such that tab C fits into the slot on the bottom surface of the log The right side of the log rests...

Страница 32: ...0 Rev B 12 08 32 LOG NUMBER 4 SRV582 705 Place log 4 across both flat spots on log 1 and log 3 with the Y in log 4 placed on log 1 The back of log 4 should make contact with the back of the firebox 1...

Страница 33: ...cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Removing Fixed Glass Assembly Ther...

Страница 34: ...onnection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the thermocoupl...

Страница 35: ...ld read 10 14 inches w c c Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections d Glass installed improperly Che...

Страница 36: ...in 350 mm 3 1 8 in 80 mm 6 5 8 in 169 mm Two 2 13 16 in 71 mm 9 9 16 in 142 mm REF 14 14 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference...

Страница 37: ...cessory Kits Direct Vent Flex Liner Accessory Kits see Figure 15 3 Flash Damp Zero clearance damper flashing kit for use with LINK DV30B or LINK DV4 30B liner kits LINK ZC ADP Zero clearance chimney a...

Страница 38: ...2178 900 Rev B 12 08 38 C Service Parts QVI 35FB S Beginning Manufacturing Date Dec 2008 Ending Manufacturing Date ______ Service Parts Diagram Part number list on following page Log Set Assembly 5 6...

Страница 39: ...46 7 Burner 768 188A Y 8 Log Grate 2178 007 9 Glass Door Assembly GLA FBG Y 10 Piezo Ignitor 291 513 Y 11 Control Panel Valve Cover Plate 783 125 12 Blower Assembly GFK 160A Fiber Patch Kit SRV PACK G...

Страница 40: ...ll parts listed in this manual may be ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 1 Pilot Assembly NG 2103 010 Y Pilot Assembly LP 2103 011 Y 2 Pilot Gaske...

Страница 41: ..._______________________________________________________ ________________________________________________________________________________ R This product may be covered by one or more of the following p...

Отзывы: