background image

Page  40

7014-188C

November 22, 2011

CB1200-I Pellet Insert

11

Reference Materials

7.  Heat Exchangers

The heat exchangers transfer heat from the exhaust system 
into convection air.  There are 2 clean out rods located under 
the heat exchangers.

8.   Heat Output Switch

The heat output switch is located on the right side of 

fi rebox, 

behind  right  side  panel.    The  function  of  the  heat  output 
switch is to regulate the burn rates; low, medium and high 
settings.

9.  Hopper Switch

The hopper switch is located in the upper right hand corner 
of the hopper.  This switch is designed to shut down the feed 
motor whenever the hopper lid is opened.

10.  Igniter

The igniter is mounted on the base of the fi repot.  Combustion 
air travels over the red hot igniter creating super heated air 
that ignites the pellets. 

11.  Junction Box And Wiring Harness

The junction box is located on the right side of the appliance, 
behind  the  right  front  access  panel.   The  junction  box  and 
wiring harness are replaced as one component.

12.  Power Supply

The power outlet is located on the right side of the appliance.   
Check  the  wall  receptacle  for  120  volt,  60  Hz  (standard 
current).  Make sure the outlet is grounded and has the correct 
polarity.   A  good  surge  protector  is  recommended.    When 
operating  with  a  generator  you  need  at  least  600  watts  of 
power, or with an inverter at least 800 watts of power, available 
for the appliance during the start cycle.

13.  Red Call Light

The  red  call  light  is  on  the  right  side  behind  the  right  side 
panel.  The function of the red call light is to indicate that the 
thermostat is calling for heat.

14.  Reset Button

The  reset  button  is  located  on  the  right  side  of  firebox 
behind right side panel.  The function of the reset button is 
to  momentarily  open  the  thermostat  circuit,  which  restarts 
the system.  

15.  Thermocouple

The  thermocouple  is  located  on  top  of  the  fi repot  inside 
the  thermocouple  cover  (ceramic  protection  tube).  The 
thermocouple  sends  a  millivolt  signal  to  the  control  box 
indicating the preset temperatures of the green and red lights 
have been obtained.

When describing the location of a component 
part it is always AS YOU FACE THE FRONT 
OF THE APPLIANCE.

2.  Convection Blower

The convection blower is mounted at the bottom rear of the 
appliance.  There are 2 impellers, one on each side of the 
motor.  The convection blower pushes heated air through the 
heat exchange system into the room.  

3.  Combustion (Exhaust) Blower

The  combustion  blower  is  mounted  on  the  left  side  of  the 
appliance behind the left side panel.  It is accessible either 
when the insert is pulled out onto the hearth or from both 
hinged side openings.  The blower is designed to pull the 
exhaust  from  the  appliance  and  push  it  out  through  the 
venting system.  

4.  Feed System

The feed system is located behind the fi rebox and can be 
removed  as  an  entire  assembly.    The  assembly  includes 
the feed motor, mounting bracket, bearing and feed spring 
(auger).  The hollow feed spring (auger) pulls pellets up the 
feed tube from the hopper area and drops them down the 
feed chute into the fi repot.  

5.  Firepot

The  fi repot  is  made  of  high  quality  ductile  iron  and  has  a 

cleaning  pull-out  rod.    The  fl oor  of  the  fi repot  opens  for 
cleaning when you pull out the rod.  Be sure that the fl oor 
returns  to  a  completely  closed  position  or  your  appliance 
will not operate properly.

6.  Fuse

The fuse is located on the right side of the appliance behind 
the side panel.  The fuse will blow should a short occur and 
shut off power to the appliance.

NOTE:

Do 

NOT

 open the control box.  This will void the 

warranty.  If you need to plug in or remove the control 
box you must fi rst

 unplug the appliance.

1.  Control Box

 

a.  The control box is located on right side of appliance, 

behind the right side panel.

 

b. There is a  light located inside of the control box. The 

internal light will turn green when the appliance has 
reached a temperature of 200

ο

F (93

°

C) in the fi repot. 

and will turn red when it reaches 600

o

F (315

°

C).

 

c.  There is also an internal blue light located in the upper 

left corner of the control box.  When you plug in the 
appliance the blue light will automatically start blinking 
1 blink every 10 seconds for 60 seconds and then will 
stop. 

A. Component Function

E

Содержание PELLET INSERT CB1200MI-MBK

Страница 1: ...y Comply with all minimum clearances to com bustibles as specified Failure to comply may cause house fire Check building codes prior to installation Installation MUST comply with local regional state...

Страница 2: ...m 3 76mm 6 152mm 8 203mm DO NOT REMOVE THIS LABEL NE PAS ENLEVER L TIQUETTE SERIAL NO NUM RO DE S RIE Report Rapport 061 S 13 2 DO NOT REMOVE THIS LABEL NE PAS ENLEVER L TIQUETTE Manufactured by Fabri...

Страница 3: ...Rear Shroud Installation 18 19 B Outside Air Kit 20 C Adjustable Hopper Option 20 D Grille Installation 20 E Adjustable Hearth Support 21 F Panel Trim 22 23 G Brick Set Installation 24 H Brick Clip In...

Страница 4: ...3 2 TYPE Solid Fuel Room Heater Pellet Fuel Burning Type Insert STANDARD ASTM E1509 95 ULC S628 93 ULC S610 M87 ULC S628 M93 and ULC ORD C1482 M1990 Room Heater Pellet Fuel Burning Type and UM 84 HUD...

Страница 5: ...e loca tion of the vent termination CAUTION If burning shelled field corn you must use ap proved venting specifically designed for corn to prevent corro sion or degradation Follow the instructions fro...

Страница 6: ...n appliance is drafting successfully all combustion byproducts are exiting the home through the chimney Considerations for successful draft include Preventing negative pressure Location of appliance a...

Страница 7: ...erials have been met 8 The masonry chimney is inspected by a profes sional and is clean or the factory built metal chimney is installed according to the manufac turer s instructions and clearances 9 T...

Страница 8: ...3 Side View Panel A B Standard 30 inches 762mm 40 inches 1016mm Large 33 inches 838mm 50 inches 1270mm B A 30 in 762mm 22 in 559mm 19 1 2 in 495mm 11in 279mm 11 279mm 25 1 2 in 648mm 12 in 305mm 13 in...

Страница 9: ...NCE TO EXPOSED SECTION AND FACE TRIM Rear Shroud Kit is Required for Built In Installation A Top of Shroud Top Vent 3 0 76 Rear Vent 0 0 B Sides of Inside Shroud Top or Rear Vent 0 0 C Back of Inside...

Страница 10: ...TE A Quadra Fire floor protector Part 811 0730 is available through your dealer to be used as a floor protec tor for the section under the insert body only Floor protec tion to front and sides of inse...

Страница 11: ...eptable H Prefabricated Metal Chimney The chimney can be new or existing masonry or prefabricated and must meet the following minimum requirements Must be minimum 6 inch 152mm inside diameter of high...

Страница 12: ...open position Removal of smoke shelf or baffle Removal of ember catches Removel of fire grate Removal of view screen curtain Removal of doors External trim pieces which do not affect the operation of...

Страница 13: ...o be the same as minimum clearance to vinyl inside corners Clearance of a termination cap below electrical service shall be the same as minimum clearance to vinyl soffits Clearance of a termination ca...

Страница 14: ...e flow of exhaust gases under positive pressure as 1 foot of horizontal pipe and a foot of horizontal pipe is twice as restrictive as a foot of vertical pipe D Pipe Selection Chart The table below can...

Страница 15: ...er draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustratio...

Страница 16: ...e Air Vertical Figure 16 1 Outside Air Termination at Chimney Top Vertical 305mm min below 305mm min above NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insula ti...

Страница 17: ...pages 9 10 for listings to combustibles and appropriate chimney systems 6 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the the...

Страница 18: ...nt Includes Vent pipe and two 1 4 20 x 3 4 inch bolts with nuts Part 811 0660 3 inch Top Vent Adapter or Part 811 0670 4 inch Top Vent Adapter Vertical Exhaust Transition Pipe Top Vent Adapter Figure...

Страница 19: ...2 If your installation does not include an outside air kit attach cover plate with 4 screws 3 Attach left shroud panel using seven screws 3 on top and bottom and 1 along the side Figure 19 3 Top Vent...

Страница 20: ...Flex Hose Hose Clamp Collar Assembly Trim Ring Hose Clamp Termination Cap Assembly Figure 20 1 Attach hose clamp to intake air collar Outside air flex pipe D Grille Installation Figure 20 3 1 Remove...

Страница 21: ...extremely difficult once trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first a...

Страница 22: ...ure 22 4 Figure 22 5 Figure 22 6 NOTE Right and left side curtains are shipped with the insert 1 Unpack and lay out parts face down flanges up on a non abrasive surface as shown in Figure 22 1 Install...

Страница 23: ...while installing 4 8 32 x 3 8 inch screws into holes in panel support If screws have been factory installed tighten to secure panel to panel support Return hopper lid to closed position 7 Install a c...

Страница 24: ...need to be installed on the outer edge of baffle to keep the brick set in place Remove the baffles from the appliance before installing the brick clips 2 Using pliers bend the brick clip slightly past...

Страница 25: ...quipped with an adjustable heat anticipator The current rating is 05 amps The anticipator needs to be adjusted to the lowest setting available 2 When mounting a thermostat on a wall be sure to follow...

Страница 26: ...llets The only change in operation is that the feed rate may require a slight adjustment The BTU output of the appliance varies slightly compared to pellets depending on the quality of the Fire Risk W...

Страница 27: ...e heat output control switch to the desired setting Odors and vapors released during initial operation Curing of high temperature paint Open windows for air circulation Odors may be irritating to sens...

Страница 28: ...too high or too low you will F Feed Rate Adjustment Instructions need to adjust the feed rate Wait until the appliance has been burning for 15 minutes before making your adjustments and allow 15 minu...

Страница 29: ...ss The more it burns on low the more frequent clean ing of the glass is required 4 Fire has tall flames with black tails and is lazy 4 The feed rate needs to be reduced or the firepot needs cleaning H...

Страница 30: ...s clean Make sure front door is closed Replace control box Call light on No fire Partially burned fuel in firepot Firepot clean out plate not closed Firepot is dirty missed ignition Check that firepot...

Страница 31: ...of vacuum Empty hopper of fuel Use a wet dry vacuum cleaner to remove remaining fuel from hopper including feed tube Check feed chute for obstructions Loosen 2 screws and jiggle feed assembly Check th...

Страница 32: ...ove stainless steel baffle from firebox to clean ash from on top of baffle Clean behind rear brick panels Change fuel brand to pre mium Check that firepot clean out plate is fully closed Reduce feed r...

Страница 33: ...ion Exhaust More frequently depending on the fuel type OR X Blower Convection More frequently depending on operating environment OR X Door Latch Inspection Prior to heating season OR X Exhaust Path Mo...

Страница 34: ...r more frequently depending on ash build up By Homeowner WARNING NEVER pull firepot cleaning rods or cleaning slide plates when appliance is operating Hot pellets may fall into ashpan and may start a...

Страница 35: ...fles This will require removing the baffles Please refer to page 37 for instructions on removing the baffles 10 Cleaning the Glass Frequency When clear view of the firepot becomes obscure By Homeowner...

Страница 36: ...ency Yearly By Homeowner a Be sure the appliance is allowed to cool has been unplugged and the exhaust blower is off b Remove all ash from the firebox and vacuum thoroughly c Paint all exposed steel i...

Страница 37: ...s more than half way up the firepot By Homeowner Poor quality pellet fuel or lack of maintenance can create conditions that make the firepot fill quickly with ashes and clinkers This condition makes t...

Страница 38: ...s and slide the glass out the bottom d Slide new glass in reposition the 2 center posts and re install bottom glass frame e Re rope the door 2 Replacing Side Glass NOTE When removing the side glass wi...

Страница 39: ...ter are connected to the wire harness with 1 4 inch male female spade connectors These wires will pull forward approximately 4 to 5 inches 102mm to 127mm Disconnect the spade connections and remove th...

Страница 40: ...temperatures of the green and red lights have been obtained When describing the location of a component part it is always AS YOU FACE THE FRONT OF THE APPLIANCE 2 Convection Blower The convection blow...

Страница 41: ...t itself 19 Snap Disc 3 Burn Back Protector 250 F Snap disc 3 is mounted on the right side of the auger tube just below feed motor and has a reset button To access it remove the right side panel If th...

Страница 42: ...al Block Center 2 Screws for Thermostat Wires Power Outlet Heat Output Switch Reset Button Red Call Light Fuse Control Box Blue Blinking Light Red Green Light B Component Locations Figure 42 1 Exhaust...

Страница 43: ...2 2011 7014 188C Page 43 CB1200 I Pellet Insert C Exploded Drawing Figure 43 1 Part number list on following pages Classic Bay Millennium Insert Pellet 4 5 6 7 8 9 10 11 12 13 17 16 15 14 19 18 20 21...

Страница 44: ...2 3690 Y 3 1 Screw 8 32 X 3 8 PH Pkg of 40 225 0500 40 Y 3 2 Feed Motor 812 4421 Y 3 3 Collar Set 7 8 229 0520 3 4 Feed Bearing SRV7000 598 Y 3 5 Mount Feed Motor 410 7172 3 6 Gasket Feed Motor 240 07...

Страница 45: ...3171 Y 11 6 Heating Element Assembly 18 Loop Igniter Pkg of 1 SRV7000 462 Y Pkg of 10 SRV7000 462 10 Y Wing Thumb Screw 8 32 X 1 2 Pkg of 24 7000 223 24 Y 12 Door Assembly Black DR CB12 MBK B Gold DR...

Страница 46: ...l Light Lens Cover 812 0750 Y Call Light Fluorescent SRV7000 122 Component Pack Includes Firepot Cleanout Tool Power Cord Wire Harness For Thermostat Owners Manual Caution Label Paint Warranty Card Ho...

Страница 47: ...33 in x 50 in SP CB12I3350 GD Bracket L Trim Qty 2 832 0840 Logo Quadra Fire Gold 200 3180 Trim Panel Set Gold 250 4660 Panel Set Large W Nickel Trim 33 in x 50 in SP CB12I3350 NL Bracket L Trim Qty 2...

Страница 48: ...TENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Bolt Firepot 1 1 4 Long Pkg of 25 225 0120 25 Y Bumper Rubber Pkg of 12 SRV224 0340 12 Y Ceramic Nuts Igniter Pkg of 12 812 0730...

Страница 49: ...R November 22 2011 7014 188C Page 49 CB1200 I Pellet Insert Date of Service Performed By Description of Service E Service And Maintenance Log...

Страница 50: ...Page 50 7014 188C November 22 2011 R CB1200 I Pellet Insert F Warranty Policy...

Страница 51: ...R November 22 2011 7014 188C Page 51 CB1200 I Pellet Insert...

Страница 52: ...195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441...

Отзывы: