18
02/22
8105-803B
A. Through The Wall
Horizontal termination cap must be a minimum of 6
inches. (152mm) from the wall. Approved for mobile home
installations. Must use 3 or 4 inch (76-102mm) “L” or “PL”
listed pellet venting or Listed double wall pipe and an
authorized Outside Air Kit in mobile homes.
Wall
Thimble
Illustration shows venting going in both directions.
Choose which one is best for your installation.
3 in. (76mm)
Minimum
3 in.
(76mm)
Minimum
6 in (152mm) Minimum
6 in
(152mm)
Minimum
Figure 18.2
- 45 Degree
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired, the
installation shall conform to
CAN/CSA-B365
Figure 18.1
- Straight Out
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
Wall
Thimble
Horizontal
Termination
Cap
3 in.
(76mm)
Minimum
6 in.
(152mm)
Minimum
from glass
NOTICE:
Please note that while the minimum clearance
for the termination cap is 6 inches (152mm) there is the
possibility of soot build-up around the termination area.
If this occurs we suggest to move the termination further
away from the house to prevent it.
5
5
Venting Systems
We strongly recommend that you DO NOT
DOWNWARD VENT.
The following may occur:
• The appliance will not vent properly
• Smoke spillage in the house
• Excessive sooting
CAUTION