You must use a Quadra-Fire Outside Air Kit for 

installation in a mobile home.

1.  An outside air inlet must be provided for the combustion 

air and must remain clear of leaves, debris, ice and/or 

snow. It must be unrestricted while the appliance is in 

use to prevent room air starvation which causes smoke 

spillage. Smoke spillage can also set off smoke alarms.

2.  The combustion air duct system must be made of metal. 

It must permit zero clearance to combustible construction 

and prevent material from dropping into the inlet or into 

the area beneath the dwelling and contain a rodent 

screen.

3. The appliance must be secured to the mobile home 

structure by bolting it to the floor (using lag bolts). Use the 

same holes that secured the appliance to the shipping 

pallet.

4. The appliance must be grounded with #8 solid copper 

grounding wire or equivalent, terminated at each end 

with an NEC approved grounding device.

5.  Refer to Clearances to Combustibles and floor protection 

requirements for listings to combustibles and appropriate 

chimney systems.

6.  Use  silicone  to  create  an  effective  vapor  barrier  at 

the location where the chimney or other component 

penetrates to the exterior of the structure.

7. Follow the chimney manufacturer’s instructions when 

installing the vent system for use in a mobile home.

8.  Installation shall be in accordance with the 

Manufacturers 

Home & Safety Standard (HUD) CFR 3280, Part 24

.

Spark Arrestor Cap 

Roof Flashing 

Storm Collar

Joist Shield/Firestop 

Double Wall 

Connector Pipe  

Figure 24.1

Mobile Home Installation 

Products of combustion generate carbon monoxide and 

different fuels generate different levels.

Carbon monoxide:

• 

Only use approved fuels in this appliance.

• 

Always  keep  door  shut  during  operation.  Operating 

this appliance with doors open can allow CO to leak 

into the home.

CO can kill you before you are aware it is in your home. 

At  lower  levels  of  exposure,  CO  causes  mild  effects 

that  are  often  mistaken  for  the  flu.  These  symptoms 

include headaches, dizziness, disorientation, nausea 

and fatigue. The effects of CO exposure can vary greatly 

from person to person depending on age, overall health 

and the concentration and length of exposure.

WARNING

THE  STRUCTURAL  INTEGRITY  OF  THE  MOBILE 

HOME  FLOOR,  WALL  AND  CEILING/ROOF  MUST 

BE MAINTAINED

Do NOT cut through:

•  Floor joist, wall, studs or ceiling trusses.

• 

Any supporting material that would affect the structural 

integrity.

This  appliance  is  to  be  connected  to  a  factory-built 

chimney conforming to 

CAN/ULC-S629, Standard for 

650°C Factory-Built Chimneys

.

For removal of the chimney for mobile home 

transportation, contact the proper transportation officials.

CAUTION

Never draw outside combustion air from:

• 

Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

CAUTION

It  is  critical  to  have  a  working  smoke  detector 

installed in the home of appliance operation.

•  Smoke alarms that are properly installed and 

maintained play a vital role in reducing fire deaths and 

injuries. Having a working smoke alarm reduces the 

chance of fire related injuries.

WARNING

NEVER INSTALL IN A SLEEPING ROOM.

WARNING

Содержание OUTFITTER-II

Страница 1: ...iquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearance...

Страница 2: ...nstallation Location Considerations 5 B Thermostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Removal of Appliance from Pallet 6 F Install Checklist 7...

Страница 3: ...iency 87 5 HHV Tested Efficiency 81 9 EPA BTU Output 9 605 to 40 667 per hr BTU Input 11 676 to 49 207 per hr Vent Size 3 or 4 Type L or PL Hopper Capacity 130 lbs Fuel Premium Wood Pellets Weighted a...

Страница 4: ...Stove Composition These pellet burning stoves are made of steel cast iron or a combination of both with a ceramic viewing glass These stoves incorporate a self feeding system including a fuel storage...

Страница 5: ...nstallation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restricti...

Страница 6: ...faces have been wiped clean with a soft cloth if applicable Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum saf...

Страница 7: ...ng this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check...

Страница 8: ...A Appliance Dimensions Figure 8 1 Top View 2 1 2 64mm 4 1 2 114mm Figure 8 3 Front View 24 1 2 622mm 36 1 2 927mm Figure 8 2 Side View 22 7 8 581mm 9 1 2 241mm FLUE 8 1 4 210mm AIR INLET 3 3 Dimensio...

Страница 9: ...76mm Figure 9 2 Side View w Top Vent Adapter TPVNT 7 28 711mm Figure 9 3 Top View w Top Vent Adapter TPVNT 7 3 to 4 inch Offset Adapter 811 0720 12 1 4 311mm 3 1 4 83mm Figure 9 4 Side View w Top Ven...

Страница 10: ...Adapter 812 3570 Figure 10 2 Side View w Top Vent Adapter TPVNT 7 3 to 6 inch Offset Adapter 812 3570 12 1 4 311mm 4 1 4 108mm 27 7 8 708mm 29 7 8 760mm Figure 10 3 Top View w Top Vent Adapter TPVNT...

Страница 11: ...Wall Inches Millimeters A Back Wall to Appliance 3 76 B Side Wall to Appliance 9 229 Corner Installation Inches Millimeters C Walls to Appliance 3 76 Table 11 1 Vertical Installation Inches Millimete...

Страница 12: ...tal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor protection extending beneath the flue pipe is required with horizontal venting or unde...

Страница 13: ...s A Height 52 1321 n a n a B Width 42 1 2 1080 n a n a C Depth n a n a 25 3 4 654 All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and are FOR DESIGN P...

Страница 14: ...12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants...

Страница 15: ...emand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to...

Страница 16: ...Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successful draft include Pre...

Страница 17: ...eft side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it...

Страница 18: ...ssage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 Figure 18 1 Straight Out 6 in 152mm Minimum Non combustible Hearth Pad Wall Thim...

Страница 19: ...tructions for all reduced air clearances installations B Vertical into Existing Class A Chimney Non combustible Hearth Pad Clean out Cover Tee Wall Thimble Support Bracket Every 60 in 1 5m 12 in 305mm...

Страница 20: ...with Airspace Concrete Cap Figure 20 1 Non combustible Hearth Pad Airtight Clean Out Door Clean Out cover Sheathing 3 in 76mm Minimum 1 in 25mm Clearance Flashing Fireclay flue Liner with Airspace Con...

Страница 21: ...utside of house 3 Use hose clamp to secure flex pipe to collar assembly 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach flex pipe to outside termination cap with second hose clamp...

Страница 22: ...e 2 screws Figure 22 1 5 Install the vent pipe into the top vent adapter 6 To clean the top vent adapter open the clean out cover Figure 22 1 C Rear Vent Adapter Installations 1 Put a layer of high te...

Страница 23: ...direct sunlight above a lamp television radiator a wall next to a window or direct heat from the appliance Avoid damp environments as this can lead to corrosion that may shorten thermostat life If pa...

Страница 24: ...Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 7 7 Mobile Home Installation Products of combustion generate carbon monoxide and different fuels generate different levels Carbon m...

Страница 25: ...25 02 22 8105 803B A Service Maintenance Log Date of Service Performed By Description of Service 8 8 Reference Materials...

Страница 26: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Отзывы: