background image

 14 

 

 

 

 

 

           7082-131J 

 

 

 

 

August 3, 2015

MT VERNON E2 INSERT

C.  Negative Pressure

WARNING

USE ONLY RECOMMENDED VENTING COMPONENTS; 
OTHERWISE MAKESHIFT PARTS MAY RESULT IN PROP-
ERTY DAMAGE, PERSONAL INJURY, OR DEATH. 

Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be strongest 
in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

• Range 

hoods

•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

• Clothes 

dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 - 

Recessed 

lighting

 - 

Attic 

hatch

 - 

Duct 

leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

• 

Ensure adequate outdoor air for all combustion appliances 
and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

• 

Attic mounted duct work and air handler joints and seams 
taped or sealed

D.  Draft 

Draft is the pressure difference needed to vent an appli-
ance successfully. When an appliance is drafting suc-
cessfully, all combustion byproducts are exiting the home 
through the chimney.

Install through the warm airspace enclosed by the build-
ing envelope. This helps to produce more draft, especially 
during lighting and die-down of the fi re.

Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney

NOTICE:  Hearth & Home Technologies assumes no 
responsibility for the improper performance of the chimney 
system caused by:

•  Inadequate draft due to environmental conditions
• Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

E.  Chimney and Exhaust Connection 

1.

 

Chimney & Connector

:  Use 3 or 4 inch (76-102mm)  diameter 

type “L” or “PL” venting system.  It can be vented vertically or 
horizontally.

2.

 Mobile Home: 

Approved for all Listed pellet vent.  If using the 3 

to 6 inch (76-152mm) Top Vent Offset Adapter, use Listed double 
wall fl ue connector.  A Quadra-Fire Outside Air Kit (OAK-3) must 
be used with manufactured home installations.

3.

 Residential: 

 The 3 inch (76mm) vertical Top Vent Adapter Kit and 

the 3 to 6 inch (76-152mm) Top Vent Offset Adapter are tested 
to use 24 gauge single wall fl ue connector or Listed double wall 
fl ue connector to Class A Listed metal chimneys, or masonry 
chimneys meeting International Residential Code standards for 
solid fuel appliances.

4.

  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 

VENT MANUFACTURER.

5

.  Vent Assembly to Insert Instructions:

These instructions are for connecting the vent pipe to the 
vent assembly prior to installing the appliance in the fi replace. 

a. Unlatch the vent assembly for the exhaust blower and     
   attach to the vent pipe end using high temperature 
    silicone and at least three screws. 

b. Slide the appliance into place and line up the bent 
    assembly with the exhaust blower. 

c. Make sure the high-temperature gasket is in place. 

d. Latch the top vent assembly to the exhaust blower. 

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENT-

ING SYSTEM OF THIS UNIT.

7.  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 

ANOTHER APPLIANCE.

8.  Disconnect the vent pipe from the appliance to allow removal 

of the fi replace insert for the purpose of inspecting the fi replace 
insert and the fi replace. 

NOTE:  All pipe must be welded seam pipe whenever possible.  
Seal pipe joints with high temperature silicone (500°F [260°C] 
minimum rated only).

WARNING

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 
fumes and soot.

NOTE

: The appliance exhaust outlet is designed to ac-

commodate 3 inch venting. Use of 4 inch venting requires 
the use of a 3-to-4 inch exhaust vent increaser in addition 
to any other  venting components needed, sold separate-
ly.

Содержание MTVI-E2-MBK

Страница 1: ...able vapors and liquids in the vicinity of this or any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING Please read this entire manual before installation and use of this pellet fuel burning room heater Failure to ...

Страница 2: ... and Components 5 D Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearance To Combustibles US Canada 8 C Masonry Zero Clearance Fireplaces 9 D Floor Protection 9 E Minimum Opening for Masonry Zero Clearance Fireplaces 9 F Installation into a Factory Built Fireplace 10 G Installation into a Masonry Fireplace 11 H Prefabricated Metal Chimney 11 4 Vent Information 12 A...

Страница 3: ...hat may cause a fire hazard WARNING Fire Risk Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions C Glass Specifications This stove is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass D Electrical Rating 115 VAC 60 Hz Start 2 9 Amps Run 2 45 Amps Model Mt Vernon ...

Страница 4: ...of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney offsets Place the appliance where there will be a clear passage for a Listed chimney through the ceiling and roof vertical or through exterior wall horizontal Installing the required outside air kit wil...

Страница 5: ...n unless installing into an existing masonry fireplace B Tools And Supplies Needed C Inspect Appliance and Components Open the appliance and remove all the parts and articles packed inside the Component Pack Inspect all the parts and glass for shipping damage Report to your dealer any parts damaged in shipment All labels have been removed from the glass door Plated surfaces have been wiped clean w...

Страница 6: ... proper clearance Exterior wall roof flashing installed and sealed Terminations installed and sealed OAK installed and sealed if needed Pg 18 Electrical 120VAC unswitched power provided to the appliance Pg 21 Appliance Setup Section 6 Pg 18 All packaging and protective materials removed Accessories installed properly Started appliance and verified that all motors and blowers operate as the should ...

Страница 7: ...Panel Set Figure 7 1 Top View Figure 7 3 Side View 23 7 8 606 32 812 26 1 4 667 7 8 23 15 382 13 1 8 333 29 3 4 756 23 7 8 605 26 7 8 683 16 1 2 419 50 1270 33 838 46 1 8 1171 34 7 8 886 36 5 8 930 Figure 7 4 Front View with Cast Panel Set 3 Dimensions and Clearances A Appliance Dimensions ...

Страница 8: ...in Top or Rear Vent 2 51 B Vent Pipe to Combustible Top or Rear Vent 3 76 C Cast Side to Side Wall Top or Rear Vent 6 152 J K 3 in 76mm Outside Air 3 in 76mm 6 in 152mm 3 in 76mm Built in Unit Rear Vent with Outside Air Figure 8 1 Figure 8 2 Built in Unit Rear Vent Note In Canada where passage through a wall or partition of combustible construction is desired the installation shall conform to CAN ...

Страница 9: ...cation Inches Millimeters D Floor protection hearth extension from door opening 6 152 E Floor protection to the side of door opening 6 152 D Floor Protection F G H I Mantel Side Wall D E A B C 2 1 4 Built In Vertical Figure 9 1 3 in 76mm Outside Air J K The maximum mantel depth J is 12 inches 305mm with a minimum vertical height K of 12 inches 305mm However if your mantel has a depth of 10 inches ...

Страница 10: ...t the insert The 2 x 4 may need to be cut to the appro priate size 250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Figure 10 1 If the hearth extension is lower than the fireplace opening the portion of the insert extending onto the hearth must be supported Manufacturer...

Страница 11: ...oved chimney liner meeting type UL 103 HT requirements 2100 F per UL 1777 If the chimney is not listed as meeting HT requirements or if the factory built fireplace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and the chimney top The air flow of the factor...

Страница 12: ...es and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants wood or any other com bustible 12 in 36 in no OAK Clearance from any forced air intake of other appli ance 12 in Clearance horizontally from combustible wall...

Страница 13: ...the exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply most of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with y...

Страница 14: ...ng construction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented vertically or horizontally 2 Mobile Home Approved for all Listed pellet vent If using the 3 to 6 inch 76 152mm Top Vent Offset Adapter use Listed double wall flue connector A Quadra Fire Outside Air Kit OA...

Страница 15: ... to the equivalent feet of pipe calculated previously and the altitude above sea level of this installation Figure 15 2 a Locate the calculated equivalent feet of pipe on the vertical left side of the chart b Move to the right horizontally on the chart until you reach your altitude above sea level c If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used d If it is anywhere ab...

Страница 16: ...ide combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference A Full Reline With Outside Air Horizontal NOTE Use metal plate around exhaust vent pipe and seal all edges with ...

Страница 17: ...Air Vertical Figure 17 1 NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insulation such as fiberglass mineral wool or ceramic Do not use high temperature caulking materials to seal any edge to prevent future serviceability Outside Air Termination at Chimney Top Vertical 12 in 305mm min below 12 in 305mm min below NOTE In Canada this fireplace insert must be ins...

Страница 18: ...space such as an attic or garage Figure 18 1 Collar Wire Ties Trim Ring Termination Cap 3 inch Aluminum Flex Pipe not included Figure 18 2 OAK Exploded View Lower the leveling bolts if necessary to keep the insert level when installing Figure 18 3 Bend tabs down Shipped flat from the factory C Hearth Support Included in Kit 1 bottom 1 trim front 2 trim sides 2 trim extensions Tools Needed Phillips...

Страница 19: ...cast trim header 2 cast trim footers left and right 1 fastener package Tools Needed Powered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim pieces 2 Lay the surround set face down on protective covering to prevent scratching the painted surface 3 Secure the surround legs to top panel with the screws provided 4 Now bend the tabs down toward...

Страница 20: ... Secure with screws provided Figure 20 3 Back of Top Surround Back of Side Surround Screws Figure 20 1 Shown with trim installed on panel set G Optional Log Set Placement Instructions 2 PIECE LOG SET INSTALLATION 1 Place the left log as shown There are 2 indentations in the bottom of the log to fit over the screw heads in the firebox Figures 20 4 20 5 2 Place the right log in front of the 2 screw ...

Страница 21: ...e wires to the 2 center screws on the terminal block on the back of the product W R Programming Thermostat The thermostat maintains a desired room temperature The 5 2 day programmable function allows one program for week days and a separate program for Saturday Sunday Up to 4 periods per day Thermostat Controls Saturday and Sunday can be programmed individually by changing the format from 5 2 to 5...

Страница 22: ...ually as needed Whatever temperature you set will be maintained 24 hours a day until you manually change it or press RUN SCHED ULE to cancel Hold and resume the prgrammed sched ule To Adjust Program Schedules 1 Press SET CLOCK DAY SCHEDULE then SET SCHEDULE 2 Press to set your weekday wake time Mon Fri then press NEXT 3 Press to set the temperature for this time period then press NEXT 4 Set time a...

Страница 23: ... venting sections or more than two 90 degree Elbows QuadraFire recommends starting at a 4 trim setting and making adjustments based on fuel type and elevation From our testing we have found that 4 3 3 or 4 have worked well depending on fuels Indicators that Trim Adjustment is needed 1 The flame appears lazy 2 Smoke can be seen in the firebox after start up during normal burn 3 Excessive build up o...

Страница 24: ... Part 24 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 24 1 CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED ...

Страница 25: ...LOGS 60 AE B Y Outside Air Kit OAK 3 Top Vent Adapter TPVNT 3 Vent Adapter 3 4 811 0720 Vent Adapter 90 cleanout TPVNT 6 Vent Adapter Cleanout 811 0620 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim SP MTVS GD Component Pack 7036 042 Trim Panel Set Gold 250 4660 Surround Std Panel w Nickel Black Trim SP MTVS NB Component Pack 7036 042 Trim Set B...

Страница 26: ...26 7082 131J August 3 2015 MT VERNON E2 INSERT ...

Страница 27: ...August 3 2015 7082 131J 27 MT VERNON E2 INSERT ...

Страница 28: ...lville WA 99114 Division of HNI INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record the following per...

Отзывы: