background image

May 5, 2015 

 

 

 

             

7036-188E 

 

 

 

         

                  11

MT VERNON AE INSERT

Keep sharp edge of 
metal floor away from 
power cord

Leveling Leg

Figure 11.1.

  Place the insert into the facto-

ry-built fi rebox.  Ensure that the power cord 
can not be damaged by the sharp metal 
edge.  You may need to cut out a notch to 
accommodate the cord.

Figure 11.2.

  Ensure that the leveling leg is 

positioned over the 2 x 4 before leveling the 
insert. Minimum 1” clearance.

NOTICE:

 

In Canada when using a factory-built chim-

ney it must be safety listed,

 Type UL103 HT (2100

o

F) 

[1149

o

C] CLASS “A” 

or conforming to 

CAN/ULC-

S629M, STANDARD FOR 650

o

C FACTORY-BUILT 

CHIMNEYS.

I.  Prefabricated Metal Chimney

The chimney can be new or existing, masonry or prefabricated 
and must meet the following minimum requirements:

 

• Must be minimum 6 inch (152mm) inside diameter of 

high temperature chimney listed to UL 103 HT (2100

o

F) 

or ULC-S628.

 

• Must use components required by the manufacturer for 

installation.

 

• Must maintain clearances required by the manufacturer 

for installation.

 

• Refer to manufacturers instructions for installation

 

•This insert is listed to ASTM E 1509-12 Standard and 

is approved for installation into listed factory-built zero 
clearance  fi replaces listed to UL 127 conforming to the 
following specifi cations and instructions:

 

•The original factory-built clearance fi replace  chimney 

cap must be re-installed after installing the approved 
chimney liner meeting type UL 103 HT requirements 
(2100°F) per UL 1777.

  •If the chimney is not listed as meeting HT requirements, 

or if the factory built fi replace was tested prior to 1998, a 
full height listed chimney liner must be installed from the 
appliance fl ue collar to the chimney top.

 

•The liner must be securely attached to the insert fl ue collar 

and the chimney top. 

 •The 

air 

fl ow of the factory-built zero-clearance fi replace 

system must not be altered. The fl ue liner top support 
attachment must not reduce the air fl ow for the existing 
air-cooled chimney system.

  •No dilution air is allowed to enter the chimney.

   1. 

Secure the fi replace damper in the open position.  If 
this cannot be accomplished, it will be necessary to 
remove the damper

 

 

   

2. Seal damper area of chimney around chimney 

connector with a high temperature sealant or seal 
insert against the face of the fi replace.

   

3. Both methods must be removable and replaceable 

for cleaning and re-installation.

• Removing 

fl oor  of  fi replace must not weaken structure 

of fi rebox or reduce protection for combustible materials.

• 

Final approval of this installation type is contingent upon 
the appropriate local authority having jurisdiction.

WARNING

H. Installation into a Masonry Fireplace

All modifi cations that can be made to a Factory Built Fire-
place can be made to a Masonry Fireplace.

In addition

 

DO NOT

 

remove any brick or mortar from the 

existing fi replace.

Risk of Fire!

Follow venting manufacturer’s clearances and 
instructions when installing venting system.

WARNING

1”

Example Removal of Factory-Built Fireplace Cont.

Содержание MTVERNINSAE-PMH

Страница 1: ...instruc tions is not followed exactly a fire may result causing property damage personal injury or death Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure ...

Страница 2: ...hermostat Wall Control Location 5 C Tools And Supplies Needed 5 D Inspect Appliance and Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to Combustibles UL and ULC 8 C Masonry and Zero Clearance Fireplaces 9 D Floor Protection 9 E Minimum Opening for Masonry Zero Clearance Fireplaces 9 F Mantel Projections 9 G Removing Metal Floor of Factory Bu...

Страница 3: ... appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Operating appliance without fully assembling all components Operating appliance without legs attached if supplied with unit Do NOT Overfire If appliance or chimney connector glows you are overfiring Any suc...

Страница 4: ... be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney offsets Place the appliance where there will be a clear passage for a Listed chimney through the ceiling and roof vertical or through exterior wall horizontal Installing the required outside air kit will affect the location of the vent termination When locating vent and ve...

Страница 5: ...unspliced wire Recommended 20 gauge wire solid copper When located close to the appliance it may require a slightly higher temperature setting to keep the rest of the house comfortable When located in an adjacent room or on a different floor level you will notice higher temperatures near the appli ance CAUTION The wall control is an integral part of the appliance No other wall control or thermosta...

Страница 6: ...ney meets the minimum height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 7 Combustible materials not installed in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hearth extension installed per manual...

Страница 7: ...ide View 26 1 4 in 667mm 13 1 8 in 333mm 15 in 382mm 23 7 8 in 606mm 32 in 812mm 8 1 8 in 206mm 2 3 8 in 59mm C L 29 3 4 in 756mm 23 7 8 in 605mm 28 1 8 in 714mm 50 in 1270mm 33 in 838mm 36 5 8 in 929mm 34 7 8 in 886mm 46 1 8 in 1171mm Figure 7 4 Front View with Cast Panel Set 3 Dimensions and Clearances A Appliance Dimensions ...

Страница 8: ...learances to combustibles as specified WARNING Failure to comply may cause house fire A C B D C B 0 inch Clearance To Exposed Section And Face Trim E Location Configuration Inches Millimeters A Top of Hopper Top or Rent Vent 3 76 B Side of Outside Skin Top or Rear Vent 2 51 C Back of Hopper Top Vent 7 1 2 191 Rear Vent 2 3 4 70 D Vent Pipe to Combustible Top or Rear Vent 3 76 E Cast Side to Side W...

Страница 9: ...ers D Floor protection hearth extension from door opening 6 152 E Floor protection to the side of door opening 6 152 D Floor Protection F G H I F Mantel Projections J K Mantel Face Trim D E A C B Side Wall Figure 9 4 Built In Vertical Figure 9 1 The maximum mantel depth J is 12 inches 305mm with a minimum vertical height K of 12 inches 305mm However if your mantel has a depth of 10 inches 254mm th...

Страница 10: ...the insert The 2 x 4 may need to be cut to the appro priate size 250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Figure 10 1 If the hearth extension is lower than the fireplace opening the portion of the insert extending onto the hearth must be supported Manufacturer d...

Страница 11: ...ed chimney liner meeting type UL 103 HT requirements 2100 F per UL 1777 If the chimney is not listed as meeting HT requirements or if the factory built fireplace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and the chimney top The air flow of the factory ...

Страница 12: ...s and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants wood or any other com bustible 12 in 36 in no OAK Clearance from any forced air intake of other appli ance 12 in Clearance horizontally from combustible wall ...

Страница 13: ...al house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house Vent Configurations To reduce probability of reverse drafting during shut down conditions Hearth Home Technologies strongly rec...

Страница 14: ...himney NOTICE HEARTH Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Downdrafts Tight sealing construction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented vertical...

Страница 15: ...29m you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated previously and the altitude above sea level of this installation Figure 15 2 a Locate the calculated equivalent feet of pipe on the vertical left side of the chart b Move to the right horizontally on...

Страница 16: ...aw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference A Full Reline With Outside Air Horizontal Outside Air through Rear Wall Horizontal NOTE Use metal plate a...

Страница 17: ...de Air Vertical Figure 17 1 Outside Air Termination at Chimney Top Vertical 305mm min below 305mm min above NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insula tion such as fiberglass mineral wool or ceramic Do not use high temperature caulk ing materials to seal any edge to prevent furture serviceability NOTE In Canada this fireplace insert must be installed...

Страница 18: ... on outside of house 3 Use wire ties to secure flex pipe to collar assembly 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach flex pipe not included to outside termination cap with second wire tie 6 Secure termination cap to outside surface 7 Secure trim ring to interior wall CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an att...

Страница 19: ...then release the latch The latch hooks onto a bracket to hold the side in place Bend tabs down Shipped flat from the factory Figure 19 2 9 attachment holes 3 on each side and 3 in the front Figure 19 3 Included in Kit 1 bottom 1 trim front 2 trim sides 2 trim extensions Tools Needed Phillips head screw driver measuring tape gloves 1 Remove contents from box and lay on protective surface to avoid s...

Страница 20: ...tabs down Included in Surround Kit 2 side panels left and right 1 panel top 1 fastener package Included in Cast Trim Kit 2 cast trim legs left and right 1 cast trim header 2 cast trim footers left and right 1 fastener package Tools Needed Powered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim pieces 2 Lay the surround set face down on pro...

Страница 21: ...Control Thermostat Installation 1 When mounting the wall control thermostat on the wall be sure to follow your wall control s installation instruc tions carefully NOTE The wall control thermostat should be mount ed on an inside wall and not in direct line with the appliance convection air NOTE If the wall control thermostat is located too close to the appliance you may need to set the temperature ...

Страница 22: ...FR 3280 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 22 1 CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED Do NOT cut ...

Страница 23: ... B Y Outside Air Kit OAK 3 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim No Longer Available SP MTVS GD Component Pack 7036 042 Trim Panel Set Gold 250 4660 Surround Std Panel w Nickel Black Trim SP MTVS NB Component Pack 7036 042 Trim Set Black Nickel 7019 027 Trim Cast Matte Black 811 0930 Sienna Bronze TR CAST CSB Willow TR CAST CWL Mahogany...

Страница 24: ...ille WA 99114 Division of HNI INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record the following perti...

Отзывы: