10
7062-197G
August 13, 2018
Explorer I
C. Clearances to Combustibles
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches (Millimeters)
Note: A, C, and F Dimensions are to the center of the flue collar
EXPLORER-I
INSTALLATION: FULL VERTICAL
A
B
C
D
E
F
G
H*
SINGLE WALL PIPE
17 (432)
12-1/2 (165)
24 (607)
11 (279)
7-1/2 (191)
18 (457)
53-1/2 (1359)
N/A
DOUBLE WALL PIPE
13-1/2 (343)
9 (229)
23 (584)
10 (254)
3 (77)
13-1/2 (343)
53-1/2 (1359)
N/A
INSTALLATION: 90 DEGREE ELBOW OFF TOP OF APPLIANCE THROUGH BACKWALL
SINGLE WALL PIPE
17 (432)
12-1/2 (165)
24 (607)
11 (279)
N/A
N/A
53-1/2 (1359)
18 (457)**
DOUBLE WALL PIPE
12-1/2 (165)
8 (203)
23 (584)
10 (254)
N/A
N/A
53-1/2 (1359)
18 (457)
INSTALLATION: HORIZONTAL THROUGH THE WALL
SINGLE WALL PIPE
N/A
8 (203)
24 (607)
11 (279)
N/A
N/A
53-1/2 (1359)
N/A
DOUBLE WALL PIPE
N/A
8 (203)
24 (607)
11 (279)
N/A
N/A
53-1/2 (1359)
N/A
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A
chimney or masonry chimney. Maximum depth of Alcove shall be no more than 48 inches (1219mm) and the referenced alcove
clearances. Canada must comply with
CAN/ULC-S269 M87
for the 650° factory built chimney.
* FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED
NOTE:
Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING
BACKWALL / SIDEWALL
A B
C
D
CORNER INSTALLATION
F
E
ALCOVE TOP VIEW
C
ALCOVE SIDE VIEW
G
A
G
H*
APPLIANCE TO CEILING
CLEARANCE
8”
(204mm)
24”
(610mm)
53-1/2”
(1359mm)
MANTEL
12” MAX
HORIZONTAL THROUGH
THE WALL WITH TOP
AND SIDE VIEW
11”
(280mm)