EXPEDITION II INSERT
HEARTH EXTENSION
(MINIMUM EMBER PROTECTION)
SIDE
TRIM (3”
max depth)
SIDE W
ALL
TOP TRIM (3/4” max depth)
24-1/4 in
(616mm)
23-3/4 in
(603mm)
34-3/4 in
(883mm)
USA 38-1/4
CANADA 46-1/4
(1175mm)
HEARTH EXTENSION
(EMBER PROTECTION)
FIREPLA
CE FR
ONT SURF
A
CE
MANTEL
(12” max depth)
3 in
(76mm)
3 in
(76mm)
47-3/4 in
(1213mm)
47-3/4 in
(1213mm)
USA 17-1/2
CANADA 19-1/2
(495mm)
40-3/4 in
(1035mm)
40-3/4 in
(1035mm)
Required Protection
Suggested Protection
NOTE:
Keep Ashlip
Clear of Ashes
Figure 10.1
Figure 10.2
Figure 10.4
Figure 10.3
C
D
A
B
Minimum Opening Dimensions Inches Millimeters
A
Height
23-3/8
594
B
Front Width
32
813
C
Back Width
23-7/8
606
D
Depth (Steel Surround)
18-1/4
464
Depth (Cast Surround)
17-1/2
445
NOTE:
Clearances may only be reduced by means
approved by the regulatory authority
having jurisdiction
In Canada a full length 6 inch (152mm) S635 flue liner
required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm)
diameter flue liner is required as per UL 1482.
To calculate mantel height requirement, multiply the
depth of the mantel by 0.78 inches then add 38.375
inches to the total.
NOTE:
If trim measurement is over 3/4 in (19mm)
in depth use mantle or side clearances
to combustibles.
NOTE:
Minimum opening dimensions include a 1/4 inch
(6mm) clearance around unit.
B. Clearances to Combustibles
United States and Canada (UL and ULC)
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING