CASTILE FREESTANDING
I. P
ellet Venting Charts
Figure 14.1
Fire Risk.
• Only LISTED venting components may be used.
• NO OTHER vent components may be used.
Substitute or damaged vent components may impair
safe operation.
WARNING
The maximum horizontal venting allowed with no vertical vent
-
ing attached is 48 inches (1219mm) including one 90° elbow
or two 45° elbows. This is our recommended horizontal vent
-
ing installation. Addition of any horizontal venting beyond 48
inches (1219mm) Hearth & Home Technologies strong recom
-
mends a minimum of 60 inches (1524mm) of additional ver
-
tical vent. Horizontal sections of vent pipe should have a 1/4
inch (6.35mm) rise per foot.
Hearth & Home Technologies recommends any installation
requiring more than two 90° elbows, or more than 15 feet
(4.5m) of venting to use 4 inch (102mm) vent.
NOTICE:
These are guidelines for successful venting of your pellet appliance. The more vertical rise you can obtain in
your system, the better it will perform. Horizontal vent runs can accumulate ash and will need to be cleaned more often.
Try to keep them as short as possible.
ONE 90º ELBOW
Total
Horizontal
Minimum
Vertical
Vent
Diameter
4
0
3
5
5
3
6
6
3
7
7
3
8
8
4
9
9
4
10
10
4
11
11
4
12
12
4
13
13
4
14
14
4
15
15
4
16
16
4
17
17
4
18
18
4
19
19
4
see fig. 14.1
TWO 90º ELBOWS
Total
Minimum
Vent
Horizontal Vertical
Diameter
2
5
3
3
6
3
4
7
3
5
8
3
6
9
3
7
10
4
8
11
4
9
12
4
10
13
4
11
14
4
12
15
4
13
16
4
14
17
4
15
18
4
see fig. 14.2
THREE 90º ELBOWS
Total
Minimum
Vent
Horizontal Vertical Diameter
2
11
4
3
12
4
4
13
4
5
14
4
6
15
4
7
16
4
8
17
4
9
18
4
10
19
4
11
20
4
see fig. 14.3
45° elbow is equivalent to 1 foot (30.48cm) of straight pipe
90° elbow is equivalent to 3 feet (91.44cm) of straight pipe
Minimum Vertical Vent for One Elbow
0
5
10
15
20
0
5
10
15
20
Horizontal Run, (ft)
M
in
im
um
V
er
tic
al R
is
e
(ft
)
Minimum Vertical Vent for One Elbow
Figure 14.3
Minimum Vertical Vent for Three Elbows
0
5
10
15
20
25
0
2
4
6
8
10
12
Length of Horizontal Sections (ft)
M
in
im
um
V
er
tic
al R
is
e
(ft
)
Minimum Vertical Vent for Three Elbows
Figure 14.2
Minimum Vertical Vent for Two Elbows
0
5
10
15
20
0
5
10
15
Length of Horizontal Sections, (ft)
M
in
im
um
V
er
tic
al
R
is
e,
(f
t)
Minimum Vertical Vent for Two Elbows