5700 Step Top ACC Wood Burner
DESCRIPTION
Pioneer Double Flue Mounted Shield Universal
Shall be Fitted
With Double Flue
Shield Fitted
A
Min. Clearance from firebox to rear wall
150
B
Min. clearance from firebox to side wall
300
C
Min. distance from firebox opening to floor protector front
450
D
Min. distance from firebox to floor protector side
76
E
Min. distance from flue centre to side wall
847
F
Min. distance from rear wall to front of floor protector
1034
G
Width of floor protector
746
Quadra-fire 5700 Step Top ACC does not require a insulating Floor Protector, as they are tested and
comply with the minimum Floor Protector requirements of
AS/NZS 2918:2001.
Note:
▪ The minimum Floor Protector sizes are specified in the clearance chart, see Table 1 & 2.
▪ A Floor Protector can include ceramic tiles with grouted joints fixed directly onto a wooden floor or
a sheet of toughened glass, panel steel or any other non combustible material laid directly onto a
wooden floor.
▪ If installed directly onto a concrete slab, the concrete slab can be considered as the floor
protector,but must maintain the minimum measurement listed.
FLOOR PROTECTOR
PARALLEL POSITIONING
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS
Clearances may be reduced by provision of an appropriately located heat shield refer to
AS/NZS 2198:2001 3.2.3 TABLE 3.1