Page 5
January 30, 2004
5100-I WOOD INSERT
R
250-1960 Rev B
SERIAL NUMBER LABEL LOCATION:
ON RIGHT SIDE OF INSERT AS YOU FACE THE APPLIANCE
In Canada a full length 6” (152mm) S635 flue liner required
as per ULC S628.
NOTE:
When installling into a masonry fireplace, the fire-
place must be built to UBC Chapter 37 standards. Do not
remove brick or mortar from masonry fireplace to accomo-
date insert. The permanent metal warning plate provided
must be attached to the back of the fireplace stating the fire-
place may have been altered to accomodate the insert and
must be returned to original condition for use as a conven-
tional fireplace.
CLEARANCES TO COMBUSTIBLES
United States and Canada
Hearth Extension
A
B
C
D
F
E
Insert
Side
W
all
Fascia or Trim
Mantel
A
B
C
D
E
F
INSTALLATION: Masonry, Heat Circulating and *Zero Clearance
12" (305)
40" (1016)
35" (889)
7" (178)
16" (406)
8"(200)
18" (457) Canada
With 5" Mantel Deflector, Part No. 831-1520
12" (305)
29" (737)
20" (889)
7" (178)
16" (406)
8"(200)
18" (457) Canada
With 8" Mantel Deflector, Part No. 831-1530
12" (305)
23" (585)
16" (406)
7" (178)
16" (406)
8"(200)
18" (457) Canada
*Zero Clearance in USA Only.
THERMAL PROTECTION USA & CANADA
Thermal protection must be 1 inch (25mm) minimum thickness (“k” value = 0.84) or equivalent material.
See Alternate Floor Protection Work Sheet on page 7.